certified by an EEC approved body to [EEx ia] IIC
with output parameters equal to, or less than, those
shown below may be used.
Uo
=
30V
Io
=
280mA dc
Po
=
0.85W
4. ELECTRICAL SYSTEM DESIGN FOR
INSTALLATION IN HAZARDOUS AREAS
4.1 Using Zener barriers
There are three basic requirements when
designing a loop incorporating the BA374C:
1.
The intrinsic safety parameters of the Zener
barrier must be equal to or less than:
Uo
=
30V
Io
=
280mA
Po
=
0.85W
2.
The voltage between terminals 5 & 6 of the
BA374C must be between 10 and 30V.
3.
The maximum supply voltage must not
exceed the maximum working voltage of the
Zener barrier.
Fig 2 illustrates the simplest configuration in which
a BA374C is powered from an isolated (floating)
power supply. Only one barrier is required as the
other wire is earthed at the barrier busbar.
Fig 2 BA374C powered from floating supply
If a common power supply is used to operate more
than one loop the negative side of the supply is
normally connected to earth. To enable the
negative side of the 4/20mA load also to be
earthed it is necessary to have a Zener barrier in
each wire going into the hazardous area as shown
in Fig 3. Any certified diode return barrier may be
used in the return wire. For guidance System
Certificate Ex96D2505 list some of these devices.
Fig 3 BA374C powered from a common supply
When designing any loop it is necessary to
establish that the sum of the voltage drops caused
by the BA374C transmitter, both Zener barriers,
the load and the cable resistance is less than the
minimum supply voltage.
For the transmitter loop shown in Fig 3:
Minimum operating voltage of BA374C 10.0V
Maximum voltage drop caused by 28V 6.8V
300ohm Zener barrier
(340ohms x 20mA)
Maximum voltage drop caused by
1.3V
diode return barrier
Maximum voltage drop caused by
250ohm load
5.0V
(250ohms x 20mA)
Maximum voltage drop caused by cable 0.2V
resistance (10ohms x 20mA)
-------
Total maximum voltage drop
23.3V
The power supply must therefore be above 23.3V,
but below the maximum working voltage of the
28V 300ohm Zener barrier which is typically 25.5V.
4.2 Using Galvanic Isolators
Galvanic isolators, although more expensive than
Zener barriers, do not require a high integrity earth
connection. For small systems where a high
integrity earth is not already available, the use of a
galvanic isolator often reduces overall installation
cost and will simplify the design of the loop.
Galvanic isolators also enable higher resistance
loads to be driven by the 4/20mA current.
7
Содержание BA374C
Страница 1: ...BA374C Intrinsically safe field mounting indicating temperature transmitter Issue 5 3rd December 2003...
Страница 4: ...4...
Страница 11: ...11...
Страница 12: ...12...
Страница 24: ...24 Fig 13 Programme structure for optional alarms...