background image

 certified by an EEC approved body to [EEx ia] IIC
with output parameters equal to, or less than, those
shown below may be used.

Uo

=

30V

Io

=

280mA dc

Po

=

0.85W

4. ELECTRICAL SYSTEM DESIGN FOR 
    INSTALLATION IN HAZARDOUS AREAS

4.1  Using Zener barriers

There are three basic requirements when
designing a loop incorporating the BA374C:

1.

The intrinsic safety parameters of the Zener
barrier must be equal to or less than:

Uo

=

30V

Io

=

280mA

Po

=

0.85W

2.

The voltage between terminals 5 & 6 of the
BA374C must be between 10 and 30V.

3.

The maximum supply voltage must not
exceed the maximum working voltage of the
Zener barrier.

Fig 2 illustrates the simplest configuration in which
a BA374C is powered from an isolated (floating)
power supply.   Only one barrier is required as the
other wire is earthed at the barrier busbar.

Fig 2  BA374C powered from floating supply

If a common power supply is used to operate more
than one loop the negative side of the supply is
normally connected to earth.  To enable the
negative side of the 4/20mA load also to be
earthed it is necessary to have a Zener barrier in
each wire going into the hazardous area as shown
in Fig 3.    Any certified diode return barrier may be
used in the return wire.  For guidance System
Certificate Ex96D2505 list some of  these devices.

  

Fig 3  BA374C powered from a common supply

When designing any loop it is necessary to
establish that the sum of the voltage drops caused
by the BA374C transmitter, both Zener barriers,
the load and the cable resistance is less than the
minimum supply  voltage.

For  the transmitter loop shown in Fig 3:

Minimum operating voltage of BA374C 10.0V

Maximum voltage drop caused by 28V  6.8V
300ohm Zener barrier
(340ohms x 20mA)

Maximum voltage drop caused by

1.3V

diode return barrier

Maximum voltage drop caused by
250ohm load

5.0V

(250ohms x 20mA)

Maximum voltage drop caused by cable  0.2V
resistance  (10ohms x 20mA)

                                                                                
                                                                  -------

Total maximum voltage drop

23.3V

The power supply must therefore be above 23.3V,
but below the maximum working voltage of the
28V 300ohm Zener barrier which is typically 25.5V.

4.2  Using Galvanic Isolators

Galvanic isolators, although more expensive than
Zener barriers, do not require a high integrity earth
connection.  For small systems where a high
integrity earth is not already available, the use of a
galvanic isolator often reduces overall installation
cost and will simplify the design of the loop.
Galvanic isolators also enable higher resistance
loads to be driven by the 4/20mA current.

      7

Содержание BA374C

Страница 1: ...BA374C Intrinsically safe field mounting indicating temperature transmitter Issue 5 3rd December 2003...

Страница 2: ...ut current calibration 6 7 Security code 6 8 Calibrating the internal references 6 8 1 Conditioning internal references 6 8 2 Voltage input reference 6 8 3 3 wire RTD reference 6 8 4 4 wire RTD refere...

Страница 3: ...Section 6 you will find information on setting up for Section 6 3 Thermocouple input Section 6 4 Resistance thermometer input Section 6 5 Voltage input A word of warning Section 6 8 explains how you...

Страница 4: ...4...

Страница 5: ...ing look up tables stored in permanent memory The resulting temperature is shown on the internal display and controls the 4 20mA output current The transmitter and the optional alarms are powered from...

Страница 6: ...BA374C to be installed in all Zones and to be used with most common industrial gases at ambient temperatures between 40 60o C Note minimum operating temperature 20o C 3 4 Certification information la...

Страница 7: ...Any certified diode return barrier may be used in the return wire For guidance System Certificate Ex96D2505 list some of these devices Fig 3 BA374C powered from a common supply When designing any loo...

Страница 8: ...d such that the environmental conditions specified by the instru ment datasheet and the EC Type Examination Certificate are not exceeded Please consult BEKA associates if the instrument is to be insta...

Страница 9: ...ogramme menu calibration procedure using the trim menu and the calibration example in sections 6 1 7 1 and 8 are read prior to changing function or calibrating the transmitter Figs 7A 7B and 9 show th...

Страница 10: ...ctions in the programme menu is described in the following summary with a cross reference to more detailed information Figs 7A and 7B illustrates the location of each function within the menu Display...

Страница 11: ...11...

Страница 12: ...12...

Страница 13: ...will reveal the current setting This setting may be changed by scrolling through the menu using the Up or Down buttons When the required input is displayed pressing P will reveal a sub menu enabling...

Страница 14: ...esistance thermometer input from the InPut sub menu press P to reveal the tYPE sub menu Press P again to display the current type of resistance thermometer which may be changed by scrolling through th...

Страница 15: ...transfer control to the next digit When the least significant digit has been adjusted press E to return to the InPut prompt from which the display prompt dISP can be selected by pressing the Up or Dow...

Страница 16: ...Voltage input 3 wire RTD 4 wire RTD Current output The input voltage reference must be adjusted first irrespective of the transmitter application but it is only necessary to adjust the other three ref...

Страница 17: ...ly 4mA The transmitter output current shown on the external current measuring instrument should be adjusted to 4 000 0 001mA using the transmitter Up and Down buttons When correct press the E push but...

Страница 18: ...temperature of the primary element operate the Up or Down buttons until the transmitter display is correct Immediately the Up or Down button is operated the annunicator in the top left hand corner of...

Страница 19: ...ple With tHC displayed press P to enter the thermocouple sub menu The first parameter tYPE will be displayed pressing P again will give access to the seven different types of thermocouple Select J usi...

Страница 20: ...erature although this may be less accurate With the transmitter displaying the ZEro prompt and the correct input connected to the transmitter push P which will cause the transmitter to display the the...

Страница 21: ...hazardous area but only certified test equipment should be used unless a gas clearance certificate is available If a BA374C fails after it has been functioning correctly the procedure shown in sectio...

Страница 22: ...74C can be supplied with two solid state single pole alarm outputs Each output may be programmed as a high or low alarm with a normally open or a normally closed output Fig 10 illustrates the conditio...

Страница 23: ...ary of programmable alarm functions Display Summary of function EnbL Alarm enable Enables or disables the alarm function without changing the alarm parameters See section 11 3 1 SP1 Alarm setpoint 1 A...

Страница 24: ...24 Fig 13 Programme structure for optional alarms...

Страница 25: ...rm output status select no nc from the alarm sub menu and press P reveal the current setting The function can be changed by pressing the Up or Down button followed by the E button to return the no nc...

Страница 26: ...AcSP prompt in the Programme Menu Code 0000 will disable the security code allowing direct access to the setpoints by pressing the P and Up buttons simultaneously New instruments are supplied with thi...

Страница 27: ...or galvanic isolator may be used providing the output parameters do not exceed Uo 30V dc Io 159mA Po 0 8W For guidance the system certificates list some of the devices which may be used Fig 15 Backli...

Отзывы: