TThe maximum equivalent capacitance and
inductance between each set of alarm terminals is:

Ceq

=      20nF

Leq

=      10µH

These figures must be subtracted from the
maximum permitted cable capacitance and
inductance specified by the system certificate of
the circuit connected to the alarm.

Fig 12  Typical application of alarms

11.1.3  Programming & adjustment

When an alarm card is added to a BA374C
transmitter the Programme Menu is extended as
shown in  Fig 13.   The additional functions 'ALr1',
'ALr2' and 'AcSP' appear between 'Cond' and
'COde' in the programme menu.  For simplicity Fig
13 only shows the functions available on alarm 1,
but alarm 2 has identical facilities.

The alarms relate to the digital display and the
setpoints are shown in the same units as the
display.

The following table summaries each of the alarm
programme functions and includes a cross
reference to more detailed information.   Again
only the functions on alarm 1 are listed, but alarm
2 has identical facilities.

11.2  Summary of programmable alarm
          functions.

   

Display

      Summary of function

'EnbL'

Alarm enable

Enables or disables the  alarm function 
without changing the alarm parameters.
See section  11.3.1

'SP1'

Alarm setpoint 1

Adjusts the alarm setpoint.  The alarm
is activated when the indicator display
equals the setpoint.
The setpoint can also be adjusted
directly from the operating mode.
See section 11.3.2

'HI.LO'

Alarm function

Defines whether the alarm has a high
or low function
See section 11.3.3

'no.nc'

Normally open or normally closed
output

Determines whether the single pole
alarm output is open or closed in the
alarm condition.
See section 11.3.4

'HStr'

Hysteresis

Adjusts the alarm hysteresis.
See section 11.3.5

'dELA'

Alarm delay

 

time

Adjusts the delay between the display
equalling the setpoint and the alarm
output being activated. 
See section 11.3.6

'SIL'

Alarm silence time

Defines the time that the alarm output
remains in the non-alarm condition
following acceptance of an alarm.
See section 11.3.7

'AcSP'

Access setpoint

Sub-menu which enables the function
allowing direct access to the alarm
setpoints from the operating mode, and
defines a separate security code.  
See section 11.3.8

      23

Содержание BA374C

Страница 1: ...BA374C Intrinsically safe field mounting indicating temperature transmitter Issue 5 3rd December 2003...

Страница 2: ...ut current calibration 6 7 Security code 6 8 Calibrating the internal references 6 8 1 Conditioning internal references 6 8 2 Voltage input reference 6 8 3 3 wire RTD reference 6 8 4 4 wire RTD refere...

Страница 3: ...Section 6 you will find information on setting up for Section 6 3 Thermocouple input Section 6 4 Resistance thermometer input Section 6 5 Voltage input A word of warning Section 6 8 explains how you...

Страница 4: ...4...

Страница 5: ...ing look up tables stored in permanent memory The resulting temperature is shown on the internal display and controls the 4 20mA output current The transmitter and the optional alarms are powered from...

Страница 6: ...BA374C to be installed in all Zones and to be used with most common industrial gases at ambient temperatures between 40 60o C Note minimum operating temperature 20o C 3 4 Certification information la...

Страница 7: ...Any certified diode return barrier may be used in the return wire For guidance System Certificate Ex96D2505 list some of these devices Fig 3 BA374C powered from a common supply When designing any loo...

Страница 8: ...d such that the environmental conditions specified by the instru ment datasheet and the EC Type Examination Certificate are not exceeded Please consult BEKA associates if the instrument is to be insta...

Страница 9: ...ogramme menu calibration procedure using the trim menu and the calibration example in sections 6 1 7 1 and 8 are read prior to changing function or calibrating the transmitter Figs 7A 7B and 9 show th...

Страница 10: ...ctions in the programme menu is described in the following summary with a cross reference to more detailed information Figs 7A and 7B illustrates the location of each function within the menu Display...

Страница 11: ...11...

Страница 12: ...12...

Страница 13: ...will reveal the current setting This setting may be changed by scrolling through the menu using the Up or Down buttons When the required input is displayed pressing P will reveal a sub menu enabling...

Страница 14: ...esistance thermometer input from the InPut sub menu press P to reveal the tYPE sub menu Press P again to display the current type of resistance thermometer which may be changed by scrolling through th...

Страница 15: ...transfer control to the next digit When the least significant digit has been adjusted press E to return to the InPut prompt from which the display prompt dISP can be selected by pressing the Up or Dow...

Страница 16: ...Voltage input 3 wire RTD 4 wire RTD Current output The input voltage reference must be adjusted first irrespective of the transmitter application but it is only necessary to adjust the other three ref...

Страница 17: ...ly 4mA The transmitter output current shown on the external current measuring instrument should be adjusted to 4 000 0 001mA using the transmitter Up and Down buttons When correct press the E push but...

Страница 18: ...temperature of the primary element operate the Up or Down buttons until the transmitter display is correct Immediately the Up or Down button is operated the annunicator in the top left hand corner of...

Страница 19: ...ple With tHC displayed press P to enter the thermocouple sub menu The first parameter tYPE will be displayed pressing P again will give access to the seven different types of thermocouple Select J usi...

Страница 20: ...erature although this may be less accurate With the transmitter displaying the ZEro prompt and the correct input connected to the transmitter push P which will cause the transmitter to display the the...

Страница 21: ...hazardous area but only certified test equipment should be used unless a gas clearance certificate is available If a BA374C fails after it has been functioning correctly the procedure shown in sectio...

Страница 22: ...74C can be supplied with two solid state single pole alarm outputs Each output may be programmed as a high or low alarm with a normally open or a normally closed output Fig 10 illustrates the conditio...

Страница 23: ...ary of programmable alarm functions Display Summary of function EnbL Alarm enable Enables or disables the alarm function without changing the alarm parameters See section 11 3 1 SP1 Alarm setpoint 1 A...

Страница 24: ...24 Fig 13 Programme structure for optional alarms...

Страница 25: ...rm output status select no nc from the alarm sub menu and press P reveal the current setting The function can be changed by pressing the Up or Down button followed by the E button to return the no nc...

Страница 26: ...AcSP prompt in the Programme Menu Code 0000 will disable the security code allowing direct access to the setpoints by pressing the P and Up buttons simultaneously New instruments are supplied with thi...

Страница 27: ...or galvanic isolator may be used providing the output parameters do not exceed Uo 30V dc Io 159mA Po 0 8W For guidance the system certificates list some of the devices which may be used Fig 15 Backli...

Отзывы: