A Quick Guide to the Use of this Instruction Manual

Your BA374C has been factory set to the requirements specified on your purchase
order.   If no requirements were given, the instrument will be supplied with default
settings i.e.  3 wire RTD input; high resolution display in °C; 4 to 20mA output
corresponding to an input and display of 0.0 to 100.0°C.

If the BA374C is set to your requirements before putting it into use you should
refer to: 
                                        Section 4               Electrical System Design

                                        Section 5               Installation

                                        Section 2.1            Controls

If optional alarms are fitted you should refer to Section 11.

You will also find the 'Trim' menu described in Section 7 useful if you wish to
calibrate the complete control loop.

If the BA374C has been supplied with default settings and you wish to change
these you will need to refer to:

                                        Section 6               Programming and Calibration

This section explains the programme functions of the push-buttons and leads you
through the various stages of programming the unit. Among the sub-divisions of
Section 6 you will find information on setting up for:

                                       Section 6.3             Thermocouple input

                                       Section 6.4              Resistance thermometer input

                                       Section 6.5              Voltage input

A word of warning:

 Section 6.8 explains how you can calibrate the instrument's

internal references. It is only necessary to carry out this operation if you will be
using these internal references to calibrate the instrument display, 

i.e not using an

external calibrator,

 and then only annual or less frequent adjustment is required. 

It

is not necessary to calibrate these references before putting the BA374C into
operation, 

we've already done that for you. For this reason the calibration section

of the programme menu is protected by an additional security code. You should
only enter this section of the programme if you are sure that you want to carry out
this calibration.

By following the notes in this manual you should be able to set up your BA374C
without any problem. However, If you do run into difficulties Section 9 provides
some guidance on typical problems you may find during commissioning. If you still
have difficulties please contact our Sales

 

Department (01462 438301). Our Sales

Engineers will be able to talk you through the procedure.

Содержание BA374C

Страница 1: ...BA374C Intrinsically safe field mounting indicating temperature transmitter Issue 5 3rd December 2003...

Страница 2: ...ut current calibration 6 7 Security code 6 8 Calibrating the internal references 6 8 1 Conditioning internal references 6 8 2 Voltage input reference 6 8 3 3 wire RTD reference 6 8 4 4 wire RTD refere...

Страница 3: ...Section 6 you will find information on setting up for Section 6 3 Thermocouple input Section 6 4 Resistance thermometer input Section 6 5 Voltage input A word of warning Section 6 8 explains how you...

Страница 4: ...4...

Страница 5: ...ing look up tables stored in permanent memory The resulting temperature is shown on the internal display and controls the 4 20mA output current The transmitter and the optional alarms are powered from...

Страница 6: ...BA374C to be installed in all Zones and to be used with most common industrial gases at ambient temperatures between 40 60o C Note minimum operating temperature 20o C 3 4 Certification information la...

Страница 7: ...Any certified diode return barrier may be used in the return wire For guidance System Certificate Ex96D2505 list some of these devices Fig 3 BA374C powered from a common supply When designing any loo...

Страница 8: ...d such that the environmental conditions specified by the instru ment datasheet and the EC Type Examination Certificate are not exceeded Please consult BEKA associates if the instrument is to be insta...

Страница 9: ...ogramme menu calibration procedure using the trim menu and the calibration example in sections 6 1 7 1 and 8 are read prior to changing function or calibrating the transmitter Figs 7A 7B and 9 show th...

Страница 10: ...ctions in the programme menu is described in the following summary with a cross reference to more detailed information Figs 7A and 7B illustrates the location of each function within the menu Display...

Страница 11: ...11...

Страница 12: ...12...

Страница 13: ...will reveal the current setting This setting may be changed by scrolling through the menu using the Up or Down buttons When the required input is displayed pressing P will reveal a sub menu enabling...

Страница 14: ...esistance thermometer input from the InPut sub menu press P to reveal the tYPE sub menu Press P again to display the current type of resistance thermometer which may be changed by scrolling through th...

Страница 15: ...transfer control to the next digit When the least significant digit has been adjusted press E to return to the InPut prompt from which the display prompt dISP can be selected by pressing the Up or Dow...

Страница 16: ...Voltage input 3 wire RTD 4 wire RTD Current output The input voltage reference must be adjusted first irrespective of the transmitter application but it is only necessary to adjust the other three ref...

Страница 17: ...ly 4mA The transmitter output current shown on the external current measuring instrument should be adjusted to 4 000 0 001mA using the transmitter Up and Down buttons When correct press the E push but...

Страница 18: ...temperature of the primary element operate the Up or Down buttons until the transmitter display is correct Immediately the Up or Down button is operated the annunicator in the top left hand corner of...

Страница 19: ...ple With tHC displayed press P to enter the thermocouple sub menu The first parameter tYPE will be displayed pressing P again will give access to the seven different types of thermocouple Select J usi...

Страница 20: ...erature although this may be less accurate With the transmitter displaying the ZEro prompt and the correct input connected to the transmitter push P which will cause the transmitter to display the the...

Страница 21: ...hazardous area but only certified test equipment should be used unless a gas clearance certificate is available If a BA374C fails after it has been functioning correctly the procedure shown in sectio...

Страница 22: ...74C can be supplied with two solid state single pole alarm outputs Each output may be programmed as a high or low alarm with a normally open or a normally closed output Fig 10 illustrates the conditio...

Страница 23: ...ary of programmable alarm functions Display Summary of function EnbL Alarm enable Enables or disables the alarm function without changing the alarm parameters See section 11 3 1 SP1 Alarm setpoint 1 A...

Страница 24: ...24 Fig 13 Programme structure for optional alarms...

Страница 25: ...rm output status select no nc from the alarm sub menu and press P reveal the current setting The function can be changed by pressing the Up or Down button followed by the E button to return the no nc...

Страница 26: ...AcSP prompt in the Programme Menu Code 0000 will disable the security code allowing direct access to the setpoints by pressing the P and Up buttons simultaneously New instruments are supplied with thi...

Страница 27: ...or galvanic isolator may be used providing the output parameters do not exceed Uo 30V dc Io 159mA Po 0 8W For guidance the system certificates list some of the devices which may be used Fig 15 Backli...

Отзывы: