3. INTRINSIC SAFETY CERTIFICATION

3.1 ATEX certificate

The BA374C has been issued with an EC-Type
Examination Certificate number
BAS02ATEX1185X by EECS showing compliance
with the European ATEX Directive 94/9/EC for
Group II, Category 1 gas atmospheres, EEx ia IIC
T5.   The instrument bears the Community Mark
and, subject to local codes of practice, may be
installed in any of the European Economic Area
(EEA) countries.  i.e.  Austria, Belgium, Denmark,
Finland, France, Germany, Greece, Ireland, Italy,
Luxembourg, The Netherlands, Norway, Portugal,
Spain, Sweden and the United Kingdom.   ATEX
certificates are also accepted in Norway, Iceland,
Liechtenstein, Switzerland and the Czech Republic

This manual describes installations which conform
with BS EN60079: Part 14:1997 Electrical
Installation in Hazardous Areas.  When designing
systems for installation outside the UK, the local
Code of Practice should be consulted.

3.2   Other intrinsic safety certifications

Please contact BEKA for a list of non-European
intrinsic safety approvals.

3.3  Zones, Gas Groups and T rating

The BA374C and accessories have been certified
EEx ia IIC T5.   When connected to an approved
system the transmitter may be installed in:

Zone 0 explosive gas air mixture

continuously present.

Zone 1 explosive gas air mixture likely

to occur in normal operation.

Zone 2 explosive gas air mixture not

likely to occur, and if it does,
it will only exist for a short time.

Be used with gases in groups:

Group   A    propane
Group   B    ethylene
Group   C    hydrogen

Having a temperature classification of:

T1

450

o

C

T2

300

o

C

T3

200

o

C

T4

135

o

C

T5

100

o

C

This allows the BA374C to be installed in all Zones
and to be used with most common industrial gases
at ambient temperatures between -40 & +60

o

C.   

Note: minimum operating temperature -20

o

C.

3.4   Certification information label

The certification information label is fitted on the
top outside surface of the enclosure.  The
instrument serial number and date of manufacture
are shown on a separate label inside the
enclosure.

3.5   Input terminals 1, 2, 3 & 4 

When the BA374C is installed in a hazardous area
the input terminals may be connected to any
floating or earthed sensor complying with the
requirements for 

simple apparatus 

as defined in

Clause 5.4 of EN50020:1994

 i.e. the sensor

generates less than 1.5V, 100mA, or 25mW.   

Thermocouples and resistance thermometers are

simple apparatus

 and any floating or earthed

device may be connected to the BA374C,
providing that both are installed within the
hazardous area.   

The permitted maximum parameters for the cables
connecting the transmitter to the sensor are 4µF
and 9.2mH in the most onerous gas group IIC
(hydrogen).  These are large and are very unlikely
to be exceeded on any thermocouple or resistance
thermometer installation.

If the transmitter input is to be connected to a
device which does not comply with the
requirements for simple apparatus, a system
certificate should be obtained, or the safety of the
system assessed using the entity concept.   The
certified safety description of the BA374C input
terminals is:

Uo

=

8.61V

Io

=

62mA dc

Po

=

0.14W

 

3.6  4/20mA output - terminals 5 & 6

The BA374C transmitter is powered via these
terminals, and the current drawn is the 4/20mA
output signal.  The transmitter is normally powered
from the safe area so a Zener barrier or galvanic
isolator is required to protect the circuit.  Any
single channel Zener barrier or galvanic isolator

      6

Содержание BA374C

Страница 1: ...BA374C Intrinsically safe field mounting indicating temperature transmitter Issue 5 3rd December 2003...

Страница 2: ...ut current calibration 6 7 Security code 6 8 Calibrating the internal references 6 8 1 Conditioning internal references 6 8 2 Voltage input reference 6 8 3 3 wire RTD reference 6 8 4 4 wire RTD refere...

Страница 3: ...Section 6 you will find information on setting up for Section 6 3 Thermocouple input Section 6 4 Resistance thermometer input Section 6 5 Voltage input A word of warning Section 6 8 explains how you...

Страница 4: ...4...

Страница 5: ...ing look up tables stored in permanent memory The resulting temperature is shown on the internal display and controls the 4 20mA output current The transmitter and the optional alarms are powered from...

Страница 6: ...BA374C to be installed in all Zones and to be used with most common industrial gases at ambient temperatures between 40 60o C Note minimum operating temperature 20o C 3 4 Certification information la...

Страница 7: ...Any certified diode return barrier may be used in the return wire For guidance System Certificate Ex96D2505 list some of these devices Fig 3 BA374C powered from a common supply When designing any loo...

Страница 8: ...d such that the environmental conditions specified by the instru ment datasheet and the EC Type Examination Certificate are not exceeded Please consult BEKA associates if the instrument is to be insta...

Страница 9: ...ogramme menu calibration procedure using the trim menu and the calibration example in sections 6 1 7 1 and 8 are read prior to changing function or calibrating the transmitter Figs 7A 7B and 9 show th...

Страница 10: ...ctions in the programme menu is described in the following summary with a cross reference to more detailed information Figs 7A and 7B illustrates the location of each function within the menu Display...

Страница 11: ...11...

Страница 12: ...12...

Страница 13: ...will reveal the current setting This setting may be changed by scrolling through the menu using the Up or Down buttons When the required input is displayed pressing P will reveal a sub menu enabling...

Страница 14: ...esistance thermometer input from the InPut sub menu press P to reveal the tYPE sub menu Press P again to display the current type of resistance thermometer which may be changed by scrolling through th...

Страница 15: ...transfer control to the next digit When the least significant digit has been adjusted press E to return to the InPut prompt from which the display prompt dISP can be selected by pressing the Up or Dow...

Страница 16: ...Voltage input 3 wire RTD 4 wire RTD Current output The input voltage reference must be adjusted first irrespective of the transmitter application but it is only necessary to adjust the other three ref...

Страница 17: ...ly 4mA The transmitter output current shown on the external current measuring instrument should be adjusted to 4 000 0 001mA using the transmitter Up and Down buttons When correct press the E push but...

Страница 18: ...temperature of the primary element operate the Up or Down buttons until the transmitter display is correct Immediately the Up or Down button is operated the annunicator in the top left hand corner of...

Страница 19: ...ple With tHC displayed press P to enter the thermocouple sub menu The first parameter tYPE will be displayed pressing P again will give access to the seven different types of thermocouple Select J usi...

Страница 20: ...erature although this may be less accurate With the transmitter displaying the ZEro prompt and the correct input connected to the transmitter push P which will cause the transmitter to display the the...

Страница 21: ...hazardous area but only certified test equipment should be used unless a gas clearance certificate is available If a BA374C fails after it has been functioning correctly the procedure shown in sectio...

Страница 22: ...74C can be supplied with two solid state single pole alarm outputs Each output may be programmed as a high or low alarm with a normally open or a normally closed output Fig 10 illustrates the conditio...

Страница 23: ...ary of programmable alarm functions Display Summary of function EnbL Alarm enable Enables or disables the alarm function without changing the alarm parameters See section 11 3 1 SP1 Alarm setpoint 1 A...

Страница 24: ...24 Fig 13 Programme structure for optional alarms...

Страница 25: ...rm output status select no nc from the alarm sub menu and press P reveal the current setting The function can be changed by pressing the Up or Down button followed by the E button to return the no nc...

Страница 26: ...AcSP prompt in the Programme Menu Code 0000 will disable the security code allowing direct access to the setpoints by pressing the P and Up buttons simultaneously New instruments are supplied with thi...

Страница 27: ...or galvanic isolator may be used providing the output parameters do not exceed Uo 30V dc Io 159mA Po 0 8W For guidance the system certificates list some of the devices which may be used Fig 15 Backli...

Отзывы: