6.0 CONFIGURATION & CALIBRATION
The BA364G Counter is configured and calibrated
via four front panel push buttons.
All the
configuration functions are contained in an easy to
use intuitive menu that is shown diagrammatically in
Fig 10.
Each menu function is summarised in section 6.3 of
this manual and each summary includes a reference
to more detailed information.
The isolated pulse output, including configuration, is
described in section 7 of this manual. When factory
fitted optional alarms and the optional 4/20mA output
are included, additional functions appear in the
configuration menu which are described in section
10 of this manual.
All new BA364G Counters are supplied calibrated as
requested at the time of ordering. If calibration is not
requested, Counters will have default configuration
as shown in the following table, but can easily be re-
configured on-site.
Function
Display Default
Input A
inP
.
tYPE
oP
.
CoL
Debounce
dEbounCE
dEFAuLt
Input b
inP
.
tYPE
oP
.
CoL
Debounce
dEbounCE
dEFAuLt
Counting edge A
CntEdG-A
EdGE 1
Counting edge b
CntEdG-b
EdGE 1
Update
uPdAtE
0.5
Count
Count
A:b
Upper display
di5p-1
totAL
Lower display
di5P-2
on
Decimal point
dP
Rate
00000
.
0
Total
00000000
Total scale factor
5CALE
.
t
001
.
00
Rate scale factor
5CALE
.
r
001
.
00
Timebase
t-bA5E
tb-01
Filter
FiLter
24
Counter direction
uP
or
dn
uP
Clear value
clr val
00000000
Local clear
loc clr
Local total reset
Clr tot
oFF
Local grand total reset
Clr Gtot
oFF
Security code
CodE
0000
Note:
While the instrument is being configured
counting continues so that any input pulses
occurring during this time are recorded.
6.1 Calibration structure
Fig 9 shows the calibration structure of the BA364G
Counter. The two pulse inputs are processed by the
count function to produce a single output having the
selected arithmetic function, such as the sum of
pulse input A and pulse input b.
This output is
passed to the
5cALE
.
R
and
5CALE . T
functions
allowing the rate and total displays to have different
engineering units.
5CALE . t
is a dividing factor that converts the output
from the Counter function into the required total
display in engineering units. e.g. if the output from
the Counter function is two pulses per pump stroke
and a total display of thousands of pump strokes is
required,
5CALE
.
t
should be set to 2000.
5CALE . r
is a dividing factor that converts the output
from the Counter function into a rate display with the
required engineering units. e.g. if the output from the
Counter function is two pulses per pump stroke and
it is required to display the pump stroke rate,
5CALE . r
should be set to 2.
The timebase
t-bA5E
is a multiplying factor that
determines if the instrument displays rate per
second, per minute or per hour.
The BA364G uses ‘real’ decimal points. Moving the
position of a decimal point in a scale factor will affect
the instrument calibration.
Fig 9 Calibration structure
16
Содержание BA364E
Страница 1: ...Issue 5 9th July 2019 BA364G and BA364E Two Input Intrinsically safe Counter Issue 5 ...
Страница 20: ...20 ...
Страница 21: ...21 ...
Страница 47: ...47 ...
Страница 48: ...48 ...
Страница 49: ...49 ...
Страница 50: ...50 ...
Страница 51: ...51 ...
Страница 52: ...52 ...
Страница 53: ...53 ...
Страница 54: ...54 ...
Страница 55: ...55 ...
Страница 56: ...56 ...
Страница 57: ...57 ...
Страница 58: ...58 ...