Display
Summary of function
dEbounCE
[for Input-b]
Defines level of input debounce
applied to the pulse input b to
prevent false counting:
dEFAuLt
HEAVY
LiGHt
See section 6.9
CntEdG-A
Input A pulse counting edge
Defines whether the Counter is
incremented/decremented
on
the
leading or trailing edge of a pulse on
input A.
See section 6.10
CntEdG-b
Input b pulse counting edge
Defines whether the Counter is
incremented/decremented
on
the
leading or trailing edge of a pulse on
input b.
See section 6.11
updAtE
Display update interval
Defines the interval between display
updates between 0.5 and 5 seconds.
See section 6.12
Count
Counting function
Defines the arithmetic relationship of
the two pulse inputs.
The total
display can be derived from:
A:b
Input A + Input b
A:-b
Input A - Input b
A con b
Input A controlled by
Input b.
a rel b
Quadrature input
(for position display)
See section 6.13
di5P-1
Upper display
Defines whether
rAtE
or
totAL
is
shown on the upper display. The
other variable will be shown on the
lower display, providing the lower
display is
on
in function
dI5P-2
.
See section 6.14
Display
Summary of function
di5P-2
Lower display
Turns the lower display, which
normally shows rate,
on
or
oFF
.
See section 6.15
dP
Position of decimal points
Defines the position of the decimal
point in both the total and rate
displays.
See section 6.16
5CALE
.
t
Total Scale Factor
5CALE . t
is a dividing factor that
converts the pulse output from
arithmetic
Count
function into the
required total display in engineering
units.
5CALE . t
may be adjusted
between. 0.0001 and 99999. e.g. if
one pulse represents 1 centimetre of
dispensed cable and the total display
is required in metres,
5CALE
.
t
should
be set to 100.0 which is the number
of centimetres in a metre.
The total display is independent of
the rate display.
See section 6.17
5CALE
.
r
Rate scale factor
5CALE . r
is a dividing factor that
converts the pulse output from the
arithmetic
Count
function into the
required rate display in engineering
units.
5CALE . r
may be adjusted
between 0.0001 and 99999. e.g. if
one
pulse
represents
2
pump
strokes and the rate display is
required in pump strokes,
5CALE . r
should be set to 0.5.
The rate display is independent of
the total display.
See section 6.18
t-bA5E
Timebase
Selectable multiplier allowing rate to
be displayed in units per second, per
minute or per hour.
Select:
tb-01
for rate / second
tb-60
for rate / minute
tb-3600
for rate / hour
See section 6.19
18
Содержание BA364E
Страница 1: ...Issue 5 9th July 2019 BA364G and BA364E Two Input Intrinsically safe Counter Issue 5 ...
Страница 20: ...20 ...
Страница 21: ...21 ...
Страница 47: ...47 ...
Страница 48: ...48 ...
Страница 49: ...49 ...
Страница 50: ...50 ...
Страница 51: ...51 ...
Страница 52: ...52 ...
Страница 53: ...53 ...
Страница 54: ...54 ...
Страница 55: ...55 ...
Страница 56: ...56 ...
Страница 57: ...57 ...
Страница 58: ...58 ...