All new BA344D rate totalisers are supplied
calibrated as requested at the time of ordering.
If calibration information is not supplied, the
instrument will be conditioned for an open
collector input, with SCALE-r and SCALE-t set
to 1 and a  timebase of seconds.

6.3  Summary of programmable functions

This section summarises all the programmable
functions.  When read in conjunction with Fig 9
it provides a quick aid for programming the
instrument.  If more detail is required, each
section contains a reference to a full
description of the function.

SUMMARY

Display

Description of function

‘UpdAtE’

Display update time

Allows the interval between
display updates to be selected.
Updating the display less
frequently lengthens battery
life.
See section 6.4

'InPut'

Type of input

Enables one of four types of
input to be selected:

‘UOLtS’

Voltage pulse

‘COIL’

Magnetic pick-off

‘ContACt’ Switch contact
‘OP.COL’ Open collector

See section 6.5

'd.P.'

Decimal points

Defines the position of the
decimal point in both the rate
and total displays and enables
the rate and total displays to
be interchanged.
See section 6.6

‘dISPLAY.2’ Lower display

Turns the lower display, which
normally shows rate, on or off.
See section 6.7

Display

Description of function

'SCALE-r' Rate Scale Factor

Defines the arithmetic relationship
between the pulse input frequency
and the rate display.  May be
adjusted between 0.001 and
99999999.
When used with a flowmeter,
SCALE-r should be set to the
flowmeter K factor (pulses per unit
of measurement) if the display is
required in the same units as the
K factor.
See section 6.8

't-bASE'

Timebase

Selectable multiplier to display
flow rate in units per second, per
minute or per hour.
Select:

‘tb-1’

for flow / second

‘tb-60’

for flow / minute

‘tb-3600’ 

for flow / hour

See section 6.9

'FILtEr'

Rate filter

Adjustable digital filter to reduce
noise on the rate display.  Two
parameters each adjustable
between 0 and 9.
See section 6.10

'SCALE-t' Total Scale Factor

Defines the arithmetic relationship
between the number of input
pulses and the total display.

 

May be adjusted between 0.001
and 99999999.
When used with a flowmeter
SCALE-t should be set to the
flowmeter K factor (pulses per unit
of measurement).

 

See section 6.11

'CLIP-OFF'  Clip off

To prevent the totalisation of very
low flow rates, clip-off enables the
user to select a flow rate below
which totalisation is inhibited.
See section 6.12

Содержание BA344D

Страница 1: ...Issue 5 7th April 2009 BA344D Intrinsically safe Battery powered pulse input field mounting rate totaliser Issue 5...

Страница 2: ...0 Rate filter 6 11 Total scale factor 6 12 Clip off 6 13 Local reset 6 14 Resetting grand total 6 15 Security code 7 Calibration Example 7 1 Calibration procedure 8 Maintenance 8 1 Fault finding durin...

Страница 3: ...es or via the optional external keypad Optional alarms which may be programmed to function on the rate or total displays further extend the applications of this instrument The BA344D contains an inter...

Страница 4: ...mospheres which conform with BS EN60079 Part14 2003 Electrical Installation in Hazardous Areas When designing systems for installation outside the UK the local Code of Practice should be consulted For...

Страница 5: ...and 4 is Ci 30nF Li 10 H To determine the maximum permissible cable parameters these figures should be subtracted from the maximum permitted cable parameters specified for the device connected to ter...

Страница 6: ...perated simultaneously See 6 13 Each time the total display is reset to zero the grand total is transferred to permanent memory 3 5 Zones gas groups and T rating The BA344D has been issued with an EC...

Страница 7: ...onnected to terminals 5 6 The maximum input counting frequency is 10kHz 4 1 System certificates When the input signal is derived from the safe area or the total display is to be reset from within the...

Страница 8: ...rconnected within the BA344D see Fig 1 4 3 Use with Galvanic Isolators Galvanic isolators are probably the simplest intrinsically safe interface as they provide isolation and do not require a high int...

Страница 9: ...nstallation procedure a Remove the instrument terminal cover by unscrewing the two captive A screws b Mount the instrument on a flat surface and secure with two M6 screws through the B holes Alternati...

Страница 10: ...ssembly The discharged battery may be removed and the replacement fitted while the BA344D rate totalisers is installed in the hazardous area Fig 7 illustrates the replacement sequence a If the instrum...

Страница 11: ...the instrument enclosure Before replacing the terminal cover turn the instrument ON by moving the slide switch to the right Fig 7 Replacement of internal battery 5 5 Disposal of used batteries The BEK...

Страница 12: ...ond minute or hour Similarly to calculate the total flow in the required units of measurement the number of input pulses is divided by the total scale factor SCALE t Total flow is continuously added t...

Страница 13: ...13...

Страница 14: ...section 6 6 dISPLAY 2 Lower display Turns the lower display which normally shows rate on or off See section 6 7 Display Description of function SCALE r Rate Scale Factor Defines the arithmetic relatio...

Страница 15: ...ype select InPut from the menu and press P which will reveal the current input type Pressing Up or Down will scroll through the four options UOLts Voltage pulse input Threshold 1V and 3V 10kHz max Inp...

Страница 16: ...int position and simultaneously press the Up and Down buttons When the required rate scale factor has been entered press E to store the number and return to the main menu 6 9 Timebase t bASE The timeb...

Страница 17: ...ecimal point in the scale factor move the flashing digit to the left hand side of the required decimal point position and simultaneously press the Up and Down buttons When the required total scale fac...

Страница 18: ...d before access to the programme menu is granted New instruments are programmed with the default security code 0000 which allows unrestricted access to all programming functions without entering a sec...

Страница 19: ...3 Select the type of input Using the Up or Down button scroll through the main menu until InPut is displayed then press P to reveal the existing setting Select COIL the input for a magnetic pick off u...

Страница 20: ...A344D is required to display 1 cubic metre for every 105 x 1 000 pulses received SCALE t should therefore be set to 105 000 Select SCALE t from the main menu and press P which will reveal the current...

Страница 21: ...rument to the CLr Gtot prompt in the main menu Step 12 Define the security code Defining a security code prevents unauthorised access to the programme functions Select COdE from the main menu and pres...

Страница 22: ...equipment should be used unless a gas clearance certificate is available If a BA344D fails after it has been functioning correctly the following table may help Symptom Cause Check No display Instrume...

Страница 23: ...larm annunciators on the instrument display indicate the status of both alarms If an alarm delay or silence time has been selected the annunciator will flash during the delay or silence period Program...

Страница 24: ...lay Description of function EnbL Alarm enable Enables or disables the alarm function without changing the alarm parameters See section 9 2 4 tYPE Type of alarm Defines whether the alarm operates on th...

Страница 25: ...rn to the alarm menu 9 2 5 Type of alarm tYPE Alarm 1 and Alarm 2 may both be rate or total alarms or one may be conditioned for rate and the other for total To check or change the type of alarm selec...

Страница 26: ...select HStr from the alarm menu and press P which will reveal the existing figure Each digit can be adjusted using the Up and Down push buttons and the P button to move to the next digit When the req...

Страница 27: ...o the setpoints in the display mode by pressing the P and Up buttons simultaneously New instruments with alarms are supplied with the security code set to 0000 9 2 13 Adjusting alarm setpoints from th...

Страница 28: ...mounting kits are available for securing the BA344D to a horizontal or vertical pipe BA392D Stainless steel bracket secured by two worm drive hose clips for 60 to 80mm outside diameter pipes BA393 He...

Страница 29: ...ertification Appendix 1 EnbL 9 2 3 9 2 4 Fault finding during commissioning 8 1 after commissioning 8 2 FILtEr 6 10 Flow indicator 2 2 Galvanic isolators 4 3 Gas groups 3 5 Grand total 2 2 clear 6 14...

Страница 30: ...ve atmosphere in the form of a cloud of combustible dust in air is likely to occur occasionally in normal operation Zone 22 explosive atmosphere in the form of a cloud of combustible dust in air is no...

Страница 31: ...ctioning immediately it is switched on When a replacement battery is fitted or when the rate totaliser is turned on after not being used for an extended period the battery should be conditioned by dra...

Отзывы: