6

3.4  Remote reset terminals

The BA344D total display may be reset to zero
by connecting the reset terminals 7 and 8
together.  These two terminals have the
following input and output safety parameters:

Uo

=

3.7V dc

Io

=

3.7mA dc

Po

=

3.5mW

Ui

=

28V dc

Ii

=

100mA dc

Pi

=

0.7W

The maximum equivalent capacitance and
inductance between them is:

Ci     =

30nF

Li      =

10

µ

H

The total display may be reset to zero from
within the hazardous area by any mechanically
operated switch connected directly to terminals
7 and 8. The switch and associated wiring
must be capable of withstanding a 500V rms
insulation test to earth for one minute and have
IP20 protection.

To reset the total display from the safe area a
Zener barrier or intrinsically safe relay is
required to transfer the contact closure into the
hazardous area.  Almost any intrinsically safe
relay with certification permitting the contacts
to be connected to equipment in the hazardous
area may be used.  A positive diode return
Zener barrier  may also be used as shown in
Fig 3.  The system certificates list suitable
devices and define the maximum cable
parameters.

Notes:

The BA344D may be programmed so that the
total display is reset to zero when the 

Up

 and

Down

 push-buttons are operated

simultaneously.  See 6.13

Each time the

 

total display is reset to zero, the

grand total is transferred to permanent
memory.

3.5  Zones, gas groups and T rating

The BA344D has been issued with an EC Type
Examination certificate confirming that it
complies with the requirements for Group II
Category 1 G EEx ia IIC T5 (Tamb –40 to
50

o

C) specified in the ATEX Directive.  When

connected to a suitable system the BA344D
may be installed in:

Zone 0

explosive gas air mixture
continuously present.

Zone 1

explosive gas air mixture
likely to occur in normal
operation.

Zone 

2

explosive gas air mixture
not likely to occur, and if it
does will only exist for a
short time.

Be used with gases in groups:

Group   A    propane
Group   B    ethylene
Group   C    hydrogen

Having a temperature classification of:

T1

450oC

T2

300oC

T3

200oC

T4

135oC

T5

100oC  

At an ambient temperature between –40 and
+50

o

C.

Note

: the guaranteed operating temperature

range is –20 to +50

o

C

This allows the BA344D to be installed in all
Zones and to be used with most common
industrial gases.

3.6 Certification Label Information

The certification label is fitted in a recess on
the top outer surface of the enclosure.  It
shows the ATEX certification information plus
BEKA associates name and location. Non
European certification information may also be
included.  The serial number and date of
manufacture are recorded on a separate label
inside the terminal compartment.

Содержание BA344D

Страница 1: ...Issue 5 7th April 2009 BA344D Intrinsically safe Battery powered pulse input field mounting rate totaliser Issue 5...

Страница 2: ...0 Rate filter 6 11 Total scale factor 6 12 Clip off 6 13 Local reset 6 14 Resetting grand total 6 15 Security code 7 Calibration Example 7 1 Calibration procedure 8 Maintenance 8 1 Fault finding durin...

Страница 3: ...es or via the optional external keypad Optional alarms which may be programmed to function on the rate or total displays further extend the applications of this instrument The BA344D contains an inter...

Страница 4: ...mospheres which conform with BS EN60079 Part14 2003 Electrical Installation in Hazardous Areas When designing systems for installation outside the UK the local Code of Practice should be consulted For...

Страница 5: ...and 4 is Ci 30nF Li 10 H To determine the maximum permissible cable parameters these figures should be subtracted from the maximum permitted cable parameters specified for the device connected to ter...

Страница 6: ...perated simultaneously See 6 13 Each time the total display is reset to zero the grand total is transferred to permanent memory 3 5 Zones gas groups and T rating The BA344D has been issued with an EC...

Страница 7: ...onnected to terminals 5 6 The maximum input counting frequency is 10kHz 4 1 System certificates When the input signal is derived from the safe area or the total display is to be reset from within the...

Страница 8: ...rconnected within the BA344D see Fig 1 4 3 Use with Galvanic Isolators Galvanic isolators are probably the simplest intrinsically safe interface as they provide isolation and do not require a high int...

Страница 9: ...nstallation procedure a Remove the instrument terminal cover by unscrewing the two captive A screws b Mount the instrument on a flat surface and secure with two M6 screws through the B holes Alternati...

Страница 10: ...ssembly The discharged battery may be removed and the replacement fitted while the BA344D rate totalisers is installed in the hazardous area Fig 7 illustrates the replacement sequence a If the instrum...

Страница 11: ...the instrument enclosure Before replacing the terminal cover turn the instrument ON by moving the slide switch to the right Fig 7 Replacement of internal battery 5 5 Disposal of used batteries The BEK...

Страница 12: ...ond minute or hour Similarly to calculate the total flow in the required units of measurement the number of input pulses is divided by the total scale factor SCALE t Total flow is continuously added t...

Страница 13: ...13...

Страница 14: ...section 6 6 dISPLAY 2 Lower display Turns the lower display which normally shows rate on or off See section 6 7 Display Description of function SCALE r Rate Scale Factor Defines the arithmetic relatio...

Страница 15: ...ype select InPut from the menu and press P which will reveal the current input type Pressing Up or Down will scroll through the four options UOLts Voltage pulse input Threshold 1V and 3V 10kHz max Inp...

Страница 16: ...int position and simultaneously press the Up and Down buttons When the required rate scale factor has been entered press E to store the number and return to the main menu 6 9 Timebase t bASE The timeb...

Страница 17: ...ecimal point in the scale factor move the flashing digit to the left hand side of the required decimal point position and simultaneously press the Up and Down buttons When the required total scale fac...

Страница 18: ...d before access to the programme menu is granted New instruments are programmed with the default security code 0000 which allows unrestricted access to all programming functions without entering a sec...

Страница 19: ...3 Select the type of input Using the Up or Down button scroll through the main menu until InPut is displayed then press P to reveal the existing setting Select COIL the input for a magnetic pick off u...

Страница 20: ...A344D is required to display 1 cubic metre for every 105 x 1 000 pulses received SCALE t should therefore be set to 105 000 Select SCALE t from the main menu and press P which will reveal the current...

Страница 21: ...rument to the CLr Gtot prompt in the main menu Step 12 Define the security code Defining a security code prevents unauthorised access to the programme functions Select COdE from the main menu and pres...

Страница 22: ...equipment should be used unless a gas clearance certificate is available If a BA344D fails after it has been functioning correctly the following table may help Symptom Cause Check No display Instrume...

Страница 23: ...larm annunciators on the instrument display indicate the status of both alarms If an alarm delay or silence time has been selected the annunciator will flash during the delay or silence period Program...

Страница 24: ...lay Description of function EnbL Alarm enable Enables or disables the alarm function without changing the alarm parameters See section 9 2 4 tYPE Type of alarm Defines whether the alarm operates on th...

Страница 25: ...rn to the alarm menu 9 2 5 Type of alarm tYPE Alarm 1 and Alarm 2 may both be rate or total alarms or one may be conditioned for rate and the other for total To check or change the type of alarm selec...

Страница 26: ...select HStr from the alarm menu and press P which will reveal the existing figure Each digit can be adjusted using the Up and Down push buttons and the P button to move to the next digit When the req...

Страница 27: ...o the setpoints in the display mode by pressing the P and Up buttons simultaneously New instruments with alarms are supplied with the security code set to 0000 9 2 13 Adjusting alarm setpoints from th...

Страница 28: ...mounting kits are available for securing the BA344D to a horizontal or vertical pipe BA392D Stainless steel bracket secured by two worm drive hose clips for 60 to 80mm outside diameter pipes BA393 He...

Страница 29: ...ertification Appendix 1 EnbL 9 2 3 9 2 4 Fault finding during commissioning 8 1 after commissioning 8 2 FILtEr 6 10 Flow indicator 2 2 Galvanic isolators 4 3 Gas groups 3 5 Grand total 2 2 clear 6 14...

Страница 30: ...ve atmosphere in the form of a cloud of combustible dust in air is likely to occur occasionally in normal operation Zone 22 explosive atmosphere in the form of a cloud of combustible dust in air is no...

Страница 31: ...ctioning immediately it is switched on When a replacement battery is fitted or when the rate totaliser is turned on after not being used for an extended period the battery should be conditioned by dra...

Отзывы: