background image

20

9.3.4  Alarm enable:  EnbL

This function allows the alarm to be enabled or
disabled  without altering any of the alarm
parameters.  To check or change the function
select 'EnbL' from the alarm menu and press P
which will reveal the current setting.  The function
can be changed by pressing the Up or Down
button followed by the E button to return to the
alarm menu.

9.3.5  Setpoint adjustment:   SP1 and SP2

The setpoint of each alarm may be positioned
anywhere between -19999 and 19999 providing
this corresponds to an input current between 3.8
and 20.2mA. e.g. If the indicator has been
calibrated to display 0 with 4mA input and 10000
with 20mA input, the two alarm setpoints may be
positioned anywhere between  -125 and 10125.

To adjust the setpoint select 'SP1' or 'SP2' from
the alarm menu and press P  which will reveal the
existing alarm setpoint.  Each digit of the setpoint
can be adjusted using the Up and Down push-
buttons, and the P button to move to the next digit.
When the required setpoint has been entered
press  to return to the alarm menu.

9.3.6  Alarm function:   HI.LO

Each alarm can be conditioned as a high or low
alarm.   To check or change the alarm function
select 'HI.LO' from the alarm menu and press P to
reveal the current setting.  The function can be
changed by pressing the Up or Down buttons
followed by the E button to return to the alarm
menu.

9.3.7  Alarm output status:   no.nc

This function allows the alarm output to be open or
to be closed in the non-alarm condition.  When
deciding which is required, care must be taken to
ensure that the alarm output is fail safe.  See Fig 8.

‘no’ Alarm output open in non-alarm condition
‘nc’ Alarm output closed in non-alarm condition

WARNING

When the 4/20mA supply is removed
both alarm outputs will open irrespective
of conditioning.  Therefore for fail safe
operation both alarm outputs should be
programmed to be open in the alarm
condition.

To check or change the alarm output status select
'no.nc' from the alarm menu and press P reveal the
current setting.  The function can be changed by
pressing the Up or Down button followed by the E
button to return to the alarm menu.

9.3.8  Hysteresis:   HStr

During programming hysteresis is shown in the
units the indicator has been calibrated to display.
To adjust the hysteresis select 'HStr' from the
alarm menu and press P which will reveal the
existing figure.  Each digit can be adjusted using
the  Up and Down push-buttons, and the P button
to move to the next digit.  When the required
hystersis has been entered press to return to the
alarm menu.

e.g.  An indicator calibrated to display 0 to 10000,
with a high alarm set at 9000 and hysteresis of 200
will perform as follows:

High alarm will be activated when display
equals or exceeds 9000, but will not reset
until the display falls below 8800.

9.3.9  Alarm delay:   dELA

This function enables activation of the alarm output
to be delayed for a fixed time following the alarm
condition occurring.  The delay can be
programmed in 1 second increments up to 3600
seconds.  If a delay is not required zero should be
entered.  To adjust the delay select 'dELA' from the
alarm menu and press P which will reveal the
existing delay.  Each digit of the delay can be
adjusted using the Up and Down push-buttons,
and the P  button to move to the next digit.  When
the required delay has been entered press E  to
return to the alarm menu.

9.3.10  Alarm silence time:   SIL

This function is primarily intended for use in small
installations where the alarm output directly
operates an annunciator such as a sounder.
When the alarm silence time is set to any figure
other than zero, the P push-button becomes an
alarm accept button.   After an alarm has occurred,
operating the P  button will cause the alarm output
to revert to the non-alarm condition for the
programmed alarm silence time.  The display will
continue to indicate an alarm after it has been
accepted and silenced.   The alarm silence time
may be adjusted between 0 and 3600 seconds in 1
second increments.

To adjust the alarm silence time select 'SIL' from
the alarm menu and press P  which will reveal the
existing time.  Each digit can be adjusted using the
Up and Down push-buttons, and the P  button to
move to the next digit.  When the required time has
been entered press to return to the alarm menu.

Содержание BA327C

Страница 1: ...BA327C BA328C intrinsically safe loop powered 4 digit panel mounting indicators issue 11 Issue 11 3rd November 2009...

Страница 2: ...rator 8 Maintenance 8 1 Fault finding during commissioning 8 2 Fault finding after commissioning 8 3 Servicing 8 4 Routine maintenance 8 5 Guarantee 8 6 Customer comments 9 Accessories 9 1 Scale card...

Страница 3: ...lt conditions the voltage current and power at the input terminals of each instrument will not exceed those specified for simple apparatus in Clause 5 4 of EN50020 1994 The BA327C and BA328C are also...

Страница 4: ...allations in Switzerland This manuals describes installations which conform with EN60079 Part 14 When designing systems for installation outside the UK th local Code of Practice should be consulted 3...

Страница 5: ...s BEKA associates name and location Non European certification information may also be shown 4 SYSTEM DESIGN FOR HAZARDOUS AREAS 4 1 Transmitter loops BA327C and BA328C indicators may be connected in...

Страница 6: ...iers a two channel Zener barrier or a galvanic isolator must be used Again it is necessary to ensure that the voltage capability of the 4 20mA signal is sufficient to drive the indicator plus the volt...

Страница 7: ...erall dimensions of each instrument and the required panel cut out dimensions To achieve an IP65 seal between the instrument enclosure and the instrument panel the smaller tolerance aperture must be u...

Страница 8: ...3 EMC The BA327C and BA328C comply with the requirements of the European EMC Directive 2004 108 EEC For specified immunity all wiring should be in screened twisted pairs with the screens earthed with...

Страница 9: ...ating decimal points for a few seconds while the new information is stored in non volatile memory All new BA327C and BA328C indicators are supplied calibrated as requested at the time of ordering If c...

Страница 10: ...10...

Страница 11: ...lowing table shows the output current from a non linearised differential flowmeter of full flow Current output mA 2 5 4 01 10 0 4 16 25 0 5 00 50 0 8 00 75 0 13 00 100 0 20 00 6 3 Resolution rESn This...

Страница 12: ...orrect pressing P will transfer control to the next digit When the least significant digit has beenadjusted press E to return to the SPAn prompt followed by E to return to the menu 6 7 Conditioning su...

Страница 13: ...calibration and conditioning of the instrument may be protected by a four digit security code which must be entered before access to the programme menu is granted New instruments are programmed with...

Страница 14: ...Down buttons select 50 and then press E twice to return to the main menu Step 5 Define function of P push button Select C P from the main menu and press P to reveal the function of the P button in the...

Страница 15: ...to the main menu Step 4 Define function of P push button Select C P from the main menu and press P to reveal the function of the P button in the display mode Select 4 20 and return to the main menu by...

Страница 16: ...ing correctly the following procedure should be followed Symptom Cause Solution No display No power Check that current 0V between supply is flowing in the loop terminals 1 and 3 Unstable 4 20mA input...

Страница 17: ...ependently programmed as high or low alarms with normally open or normally closed outputs Fig 8 illustrates the conditions available and shows which are fail safe i e in the alarm condition the output...

Страница 18: ...18...

Страница 19: ...mmable alarm functions Display Description of function EnbL Alarm enable Enables or disables the alarm function without changing the alarm parameters See section 9 3 4 SP1 Alarm setpoint 1 Adjusts the...

Страница 20: ...y pressing the Up or Down button followed by the E button to return to the alarm menu 9 3 8 Hysteresis HStr During programming hysteresis is shown in the units the indicator has been calibrated to dis...

Страница 21: ...security code allowing direct access to the setpoints by pressing the P and Up buttons simultaneously New instruments with alarms are supplied with this function disabled and the security code set to...

Страница 22: ...using the Add and dEL functions In both these functions the indicator initially displays the current break point and the total number of break points being used e g 5 13 current total number of break...

Страница 23: ...f break points Each subsequent operation of the P push button will introduce an additional break point When adding a break point to a calibrated indicator the insertion position can be selected using...

Страница 24: ...24...

Страница 25: ...e output which enhances daylight viewing but an additional IS interface and field wiring are required 9 6 1 Separately powered backlight The separately powered backlight is segregated from the measuri...

Страница 26: ...is loop powered This eliminates the need for a separate Zener barrier or galvanic isolator and associated wiring for the backlight thus significantly reducing the installation cost As shown in Fig 16...

Страница 27: ...3 A1 2 4 20mA input in nonincendive circuit The BA327C and BA328C are also Factory Mutual approved as nonincendive for Class I Division 2 locations which allows both indicators to be installed in Div...

Страница 28: ...between the backlight and the measuring circuits should be maintained by following the wiring methods recommended in ANSI NFPA70 article 504 See Fig 15 A1 3 2 2 Loop powered backlight This backlight h...

Страница 29: ...29...

Страница 30: ...30...

Страница 31: ...31...

Страница 32: ...f Conformity number IECEx ITS 05 0003 which specifies the following certification code and marking Ex ia IIC T5 Ta 40o C to 60 o C The specified intrinsic safety parameters are identical to the ATEX s...

Отзывы: