Installation measures and positioning

The  position  of  the  detector  is  a  crucial  factor  for  its  correct  functioning  during  gas  detection.
In  order  to  obtain  the  maximum  results  from  a  device  and  minimize  the  probability  of  false  alarms,
it  is  recommended  to  follow  this  scheme  and  keep  in  mind  the  following  general  regulations.

The  detector  must  be  located  at  different  heights,  according  to  the  type  of  gas.  These  heights  are:

-  30  cm  from  the  lowest  point  of  the  floor  in  order  to  detect

heavy gases, LPG, etc.

-  30  cm  from  the  highest  point  of  the  ceiling  in  order  to  detect

light gases, Methane

- The detector should not be placed near the appliances to be controlled (boilers, burners, industrial
kitchens,  etc.)  but  on  the  opposite  wall.
- The detector should not be affected by smoke, vapour, etc. as they could distort its measurement.
It  should  be  located  away  from  sources  of  heat,  ventilators  or  fans.

It must not be installed, on a wall in plasterworch.
It must be installed only on walls in masonry

Once the device has been turned on, the MAINS LED will start blinking for about 60 seconds, after
which it will remain ON. Now the GS920 is ready for detection of explosive gas.

After 24 hours from installation begin the self-learning antiseismic period (from this time the detector
MUST NOT be moved from the installation position for any reason).

After  10  days,  the  self-learning  period  is  finished  and  the  device  is  capable  to  detect  seismic
movement.

Testing

Press  the  button  near  the  detection  capsule  to  simulate  the  presence  of  gas.
The  ALARM  LED  lights  up,  and  the  relay  shifts  its  functioning  mode  after  5  seconds.  After  the
alarm,  the LED  will turn  off,  the buzzer  will stop,  and the  connected  appliances will  be turned  off.
To complete the general test, issue gas from a pre-calibrated aerosol within 20% of  L.E.L. Testing
using a common cigarette lighter could damage the sensor. This test should be carried out at least
once  a  year.

Содержание GS920

Страница 1: ...an activate solenoid valves sirens and any other alarm signal device The micro switch makes it possible to select the relay impulse functioning to connect manual reset solenoid valves or the continuous functioning and to activate N C class A solenoid valves and sirens Another micro switch allows turning on off the Intrinsic Safety The power supply unit allows driving of a manual reset solenoid val...

Страница 2: ...traordinary maintenance and its out of service removal at the end of the functional life guaranteed by the manufacturer must be carried out by authorized and or specialized personnel Do not allow it to become wet The detector can be seriously damaged when immersed in water Remember that the probe has an IP30 protection degree Do not drop it Heavy knocks or falls during transportation or installati...

Страница 3: ...er level at 10 of L E L 4 Micro switches Switch 1 Positioning the switch to ON Intrinsically safe operation the relay is excited at the end of the latency time and switches on each alarm Positioning the switch to OFF Normal operation the relay switches on each alarm Switch 2 Positioning the switch to ON the relay is set to impulse functioning Each pulse lasts about 30 seconds Positioning the switc...

Страница 4: ...Pagina 4 34 mm 50 mm Embedded box 503 70 mm 105 mm 5 mm 115 mm 84 mm 115mm Dimensions ...

Страница 5: ... its measurement It should be located away from sources of heat ventilators or fans It must not be installed on a wall in plasterworch It must be installed only on walls in masonry Once the device has been turned on the MAINS LED will start blinking for about 60 seconds after which it will remain ON Now the GS920 is ready for detection of explosive gas After 24 hours from installation begin the se...

Страница 6: ...les cornices also unbraced parapets and architectural ornaments Some cracks in masonry C Waves on ponds water turbid with mud Small slides and caving in along sand or gravel banks Large bells ring Concrete irrigation ditches damaged Steering of motor cars affected Damage to masonry C partial collapse Some damage to masonry B none to masonry A Fall of stucco and some masonry walls Twisting fall of ...

Страница 7: ...ndon the building and call the emergency services when outside fire department distributors etc If the device does not start up Check that the 230V power is correctly connected If the fault LED lights up If the YELLOW LED is remains ON check the detection capsule status It is probably faulty and has to be replaced Call an authorized technician If the detector is repeatedly issuing an alarm Check t...

Страница 8: ...tion Scheme of GS920 Detector N C C NO N Ph 12 V 1 2 3 4 5 6 7 8 Without Intrinsic Safety With Intrinsic Safety Normally closed electrovalve 230VAC The Relay is free of voltage Range of relay contact 10A resistive The electrovalve is a N C Automatic or manual retrig Note To connect a N O Electrovalve swap the connections between pin 8 and 6 The Relay is free of voltage Range of relay contact 10A r...

Страница 9: ... free of voltage Range of relay contact 10A resistive The drawn electrovalve is a Normally Open type with manual reset and with a power supply of 12V 600mA MAX The activation is impulsive Power Supply 230 V AC Normally open electrovalve 230V AC with intrinsic safety Ph N 1 2 3 4 5 6 7 8 The Relay is free of voltage Range of relay contact 10A resistive The drawn electrovalve is a N C type with manu...

Страница 10: ...open electrovalve 230V AC without intrinsic safety The Relay is free of voltage Range of relay contact 10A resistive The drawn electrovalve is a Normally Open type with manual reset and with a power supply of 12V 600mA MAX The activation is impulsive Power Supply 230 V AC Electricalconnections ...

Страница 11: ...Page 11 Note ...

Страница 12: ... 3 years from manufacturing date in agreement with the following conditions The components acknowledged as faulty will be replaced free of charge excluding the replacement of plastic or aluminium cases bags packing batteries and technical reports The device must arrive free of shipment charges to BEINAT S r l Defects caused by unauthorized personnel tampering incorrect installation and negligence ...

Отзывы: