background image

Page  4

1)  LED  ON.  It  blinks  for  about  2  minutes  (warm  up  time)  when  the  mains  power  is  supplied.  When  ready,  the
LED  stays  on  without  blinking.
2) BATTERY LED. It lights up (fixed) when no mains power is present and the control unit is supplied by a 12Vdc
battery.  It  blinks  when  the  battery  is  flat.
Note:  During  the  warm  up  time  the  control  unit  is  not  capable  of  detecting  gas.
3) 

OVER  LOAD PROBES

  LED.  If  this  LED  turns  on,  it  means  there  is  a  short  circuit  or  high  current  absorption

in  the  probes.
4) 

OVER  LOAD  BATTERY

  LED.  If  this  Led  turns  on,  it  means  the  battery  is  not  connected  properly,  or  it  has

an  anomalous  voltage  absorption.
5)  TEST  BUTTON.  Pressing  and  holding  down  this  button,  you  can  obtain  a  gas  leakage  simulation.  In  order
to  perform  this  operation  no  failures  or  alarms  should  be  present.
6)  RESET  BUTTON.  This  button  is  pressed  to  clear  all  memories,  or  to  restore  the  control  unit  after  a  failure.
7)  1

st

  Alarm  LED.  This  LED  will  light  up  when  the  gas  concentration  level  has  reached  8%  of  LEL,  or  120ppm

(ref. CO), and the  1

st

 threshold  relay  contact is closed. The relay disenergizes when the 13%  of  LEL, or 200ppm

CO,  threshold  is  exceeded.
8) 2

nd

 Alarm  LED. This  LED will  light  up  when  the  gas  concentration  level has  reached  13%  of  LEL, or  200ppm

(ref.  CO),  and  the  2

nd

  threshold  relay  contact  is  closed.  The  buzzer  will  issue  a  low  frequency  sound.  The  relay

disenergizes  when  dropping  below  the  13%  of  LEL,  or  200ppm  CO,  threshold.
9)  MAIN  ALARM  LED.  This  LED  will  light  up  when  the  gas  concentration  level  has  reached  20%  of  LEL,  or
300ppm  (ref.  CO),  and  the  MAIN  ALARM  relay  contact  is  closed.  The  buzzer  will  issue  a  high  frequency  sound.
10)  FAULT  LED.  This  LED  blinks  when  one  of  the  connected  probes  is  faulty,  if  there  is  an  interruption  in  the
cable  connection,  or  if  an  error  was  made  during  wiring.  When  this  LED  is  blinking,  the  device  is  no  longer
capable  of  detecting.  To  reactivate  the  device,  the  damaged  probe  must  be  repaired  or  disabled  using  the
internal  micro-switch  (see  chapter  6  paragraph  A)  and  then  the  RESET  button  must  be  pressed.
11)  EXPLOSIVE  GAS  LED.  If  this  LED  is  turned  on,  the  probe  is  set  to  detect  explosive  gas  (Methane,  LPG,
etc.).
12)  DISPLAY  backlight  colours.  The  symbols  are  illustrated  in  the  draw.
a)  The  symbol  of  the  battery  light  on  when  the  BX444-Mc  is  powered  with  an  external    battery.
The drawn battery indicates the  state  of  load of the  battery  and when it blinks it means that the battery is low.
b)  The  number  on  the  display  indicates  the  concentration  of  gas  detected.
The  exchange  of    data  of  every  connected  probe  is  every  about  4  seconds.
c)  The  letters  ppm  means  when  the  connected  probe  detects  Toxic  gas.
The  letters  LEL    means  when  the  connected  probe  detects  Explosive  gas.
d)
  The  symbol  of  the  time  means  when  the  BX444-Mc  is  being  the  Warm  up    and  displays  the  countdown.

13)  TOXIC  GAS  LED.  If  this  LED  is  turned  on,  the  probe  is  set  to  detect  toxic  gas  (Carbon  Monoxide).
14) SENSORS  LEDs (of  the  probes).  These  LEDs represent  the  connected probes  and  will  light  up in  sequence.

Components and commands

Test

Reset

(5)

(6)

BX444-Mc

Main  Alarm

2  Alarm

1  Alarm

Faul t

O N

Battery

Battery
Over  Load

Sens ors
Over  Load

(1)

(2)

(3)

(4)

(7)

(8)

(9)

(10)

100

ppm

1   2  3  4

SENSORS

ppm

         

LIE

(12)       (11)

Switch 1
Intrinsic  safety  selection
Switch 2
Main  alarm  relay  functioning  mode
Switch 3
Maintaining    of    the    memory  of  alarm,only  when
you  set  the  CO  gas
Switch 4
Selecting  OXYGEN  mode

Power terminal  block               Sensors terminal  block

S1    S2    S3    S4       1  2  3  4

Deleting  or  disabling  the  probes
monitored  gas  type  selection

Содержание BX444-Mc

Страница 1: ...mall underground car parks The BX444 M control unit has three danger levels 1st LEVEL 1st Alarm This was set to 8 of L E L 120ppm 2nd LEVEL 2nd Alarm This was set at 13 of L E L 200ppm 3rd LEVEL Main Alarm This was set at 20 of L E L 300ppm For oxygen the centrol unit BX444 Mc presents three levels of danger which are 1st Pre Alarm Both in deficiency and excess of Oxygen 2nd Pre alarm Both in defi...

Страница 2: ...f Conventional Sensors that can be connected 4 Micro switches to include or exclude the probes 1 per each probe Connectable probes Semi conductor Catalytic Electrochemical cell Pellistore Infrared Rays Type of faults detected by Fault Circuit Interruption short circuit or wear Input Signal 4 20 mA on 220 ohm Device Accuracy 1 FS Response Time 2 Control Unit microprocessor Functioning Temperature 1...

Страница 3: ...FREON 0 300 ppm 4 20 mA 5 Yes Yes SGF108 Elettrochimica IP64 Zone 2 H2S 0 300 ppm 4 20 mA 5 Yes Yes SGF110 Electrochemical IP64 Zone 2 C O 0 300 ppm 4 20 mA 5 Yes Yes SGF112 Catalytic IP64 Zone 2 Hydrogen 0 100 LEL 4 20 mA 5 Yes Yes CO100r Electrochemical IP55 Tertiary C O 0 300 ppm 4 20 mA 5 Yes Yes CO100Ar Electrochemical IP66 Zone 2 C O 0 300 ppm 4 20 mA 5 Yes Yes SG800duct Catalytic IP66 Zone ...

Страница 4: ... LED blinks when one of the connected probes is faulty if there is an interruption in the cable connection or if an error was made during wiring When this LED is blinking the device is no longer capable of detecting To reactivate the device the damaged probe must be repaired or disabled using the internal micro switch see chapter 6 paragraph A and then the RESET button must be pressed 11 EXPLOSIVE...

Страница 5: ...000 a ppm LEL 1 2 3 4 d b 00LEL 300ppm The blu display shows the percentage of oxygen normal condition 20 6 20LEL FAU The green display shows an absence of leakage of gas normal conditione The display shows with red color a concentration of explosive gases in LEL greater than a threshold alarm The display shows with red color a concentration of toxic gases ppm greater than a threshold alarm The ye...

Страница 6: ... connections according to Regulations in force keeping in mind that the signal cables should be laid separate from the power cables An automatic cut off switch appropriately identified as devicesectioning of the detector should be incorporated in the electrical system adequatelylocated and easily accessible Electrical Connections Diagram of the terminal block relay Power supply 110 230 VAC PH N 4 ...

Страница 7: ...nnection examples Power supply 230 12V Diode 1N 5406 1 2 3 4 5 6 7 8 3 2 1 Probe 1 3 2 1 Probe 2 3 2 1 Probe 3 3 2 1 Probe 4 R1 R2 R3 R4 Solenoid valve GAS and Sirens 12 VDC 12 V If a 12Vdc solenoid valve which does not work well is connected to the BX444 Mc Direct connection of 12VDC solenoid valves or sirens to the BX444 Mc is not permitted An external power unit must always be used The BX444 Mc...

Страница 8: ...On the next pass the LED probe will be maintained again and the alarm will be issued In case of fault The LED of the relevant probe starts blinking and remains lit The display will show the FAU Fault fixed indication and the buzzer will issue a continuous sound until 1 The repair has been carried out 2 The relevant probe has been disabled using the micro switch 1 2 4 3 Sensors Probe Identification...

Страница 9: ...memory and the relay switches off when the connected probe no longer detects gas In compliance with the rules this function becomes active only when you select the detection of Toxic Gases reading in ppm Switch 2 4 Selecting of the control unit in oxygen detection mode By setting the micro switch to ON the device is ready to detect the oxygen The display changes color and becomes BLU ATTENTION Sel...

Страница 10: ...ition of the detection sensors You can connect many types of remote sensors to this unit Therefore they should be positioned at different heights depending on the type of gas to be detected These heights are 30 cm from the lowest point of the floor in order to detect Heavy gases L P G etc 30 cm from the highest point of the ceiling in order to detect light gases Methane etc 160 cm from the lowest ...

Страница 11: ...rectly connected If the Fault LED lights up Check that the connecting cables from the BX444 Mc to the probes are intact that the probes are properly powered and that the signal cable is correctly connected If the Over Load Probe LED lights up Check that the power polarity has not been inverted that no short circuit is present that the probes were not damaged during installation that no excessive c...

Страница 12: ...r example sales points in case you buy a new and similar product local collection points waste collection center local recycling center etc By ensuring this product is disposed of correctly you will help prevent potential negative consequence for the environment and human health which could otherwise be caused by inappropriate waste handing of this product The recycling of materials will help to c...

Отзывы: