Description of Micro-switches

Installing, uninstalling or disabling probe

Through  the  Micro  switches  (see  drawing  below)  on  the  control  unit,  you  can  to  activate  or  to    deactivate    4
Zo nes 
.
You  can  connect  4  probes  to  the  BX444-Mc.  The  control  unit  is  tested  with  the  probes  connected
In  some  installations,  you may  need  only  one  probe.  In  this  case  we  will  proceed  to  disable  a  probe,  to  do  this
select  the  switch  of  the  probe  (zone)  concerned.
These  micro-switches  are  also  used  to  disable  one  or  all  probes  in  case  of  failure

N.B.  The  microswitches  are  also  used  for  switching  off  in  case  of  failure

A  row  of  LEDs  numbered  from 

1  to  4 

and  called  PROBES  has  been  fitted  on  the  BX444-Mc.  These  LEDs  are

lit  with  a  2  second  frequency  representing  the  connected  probes,  and  indicate  the  probe  being  read  on  the
display.

In  case  of  alarm:  The  LED  that  represents  the  probe  stops  for  about  15  seconds.  This  is  done  in  order  to
identify  the  relevant  zone  or  zones  easily.  The  gas  percentage  measured  by  the  probe  appears  on  the  display
and  is  maintained  for  15  seconds.  On  the  next  pass,  the  LED  (probe)  will  be  maintained  again  and  the  alarm
will  be  issued.
In case of fault:  The LED of the  relevant probe  starts blinking  and remains  lit. The  display will show the 

FAU

(Fault)  fixed  indication,  and  the  buzzer  will  issue  a  continuous  sound  until:
1)  The  repair  has  been  carried  out;
2)  The  relevant  probe  has  been  disabled  using  the  micro-switch.

1

2

4

3

Sensors

Probe Identification
Leds

  from  n°1  to  n°4

Components and Commands continue

Zone1  Zone2    Zone3  Zone4

Micro-switch  (1)  to  enable  or  to  disable  the  probe.

Position ON enabled - In  position OFF  disabled

The  simultaneous  and  prolonged  pressure  for  5  sec  of  the  "TEST"  and  "RESET"  buttons  enables  the  test-on
mode  in  which  the  control  unit  does  not  switch  the  general  alarm  relay  for  a  period  of  15  minutes;  Not  even
pressing  the  external  manual  button.

A  further  keypress  in  the  same  mode  extends  the  time  of  15  minutes  to  a  maximum  of  60  minutes.
In this mode, before the passage from the current channel to the next, the "TESt-On" string is displayed followed
by  the  minutes  of  the  general  alarm  relay  being  switched  off.
You can  terminate this  mode  before the  natural deadline by resetting  the control  unit by pressing 3  consecutive
times  and  within  5  seconds  the  RESET  button.

Mantinance Test

Содержание BX444-Mc

Страница 1: ...mall underground car parks The BX444 M control unit has three danger levels 1st LEVEL 1st Alarm This was set to 8 of L E L 120ppm 2nd LEVEL 2nd Alarm This was set at 13 of L E L 200ppm 3rd LEVEL Main Alarm This was set at 20 of L E L 300ppm For oxygen the centrol unit BX444 Mc presents three levels of danger which are 1st Pre Alarm Both in deficiency and excess of Oxygen 2nd Pre alarm Both in defi...

Страница 2: ...f Conventional Sensors that can be connected 4 Micro switches to include or exclude the probes 1 per each probe Connectable probes Semi conductor Catalytic Electrochemical cell Pellistore Infrared Rays Type of faults detected by Fault Circuit Interruption short circuit or wear Input Signal 4 20 mA on 220 ohm Device Accuracy 1 FS Response Time 2 Control Unit microprocessor Functioning Temperature 1...

Страница 3: ...FREON 0 300 ppm 4 20 mA 5 Yes Yes SGF108 Elettrochimica IP64 Zone 2 H2S 0 300 ppm 4 20 mA 5 Yes Yes SGF110 Electrochemical IP64 Zone 2 C O 0 300 ppm 4 20 mA 5 Yes Yes SGF112 Catalytic IP64 Zone 2 Hydrogen 0 100 LEL 4 20 mA 5 Yes Yes CO100r Electrochemical IP55 Tertiary C O 0 300 ppm 4 20 mA 5 Yes Yes CO100Ar Electrochemical IP66 Zone 2 C O 0 300 ppm 4 20 mA 5 Yes Yes SG800duct Catalytic IP66 Zone ...

Страница 4: ... LED blinks when one of the connected probes is faulty if there is an interruption in the cable connection or if an error was made during wiring When this LED is blinking the device is no longer capable of detecting To reactivate the device the damaged probe must be repaired or disabled using the internal micro switch see chapter 6 paragraph A and then the RESET button must be pressed 11 EXPLOSIVE...

Страница 5: ...000 a ppm LEL 1 2 3 4 d b 00LEL 300ppm The blu display shows the percentage of oxygen normal condition 20 6 20LEL FAU The green display shows an absence of leakage of gas normal conditione The display shows with red color a concentration of explosive gases in LEL greater than a threshold alarm The display shows with red color a concentration of toxic gases ppm greater than a threshold alarm The ye...

Страница 6: ... connections according to Regulations in force keeping in mind that the signal cables should be laid separate from the power cables An automatic cut off switch appropriately identified as devicesectioning of the detector should be incorporated in the electrical system adequatelylocated and easily accessible Electrical Connections Diagram of the terminal block relay Power supply 110 230 VAC PH N 4 ...

Страница 7: ...nnection examples Power supply 230 12V Diode 1N 5406 1 2 3 4 5 6 7 8 3 2 1 Probe 1 3 2 1 Probe 2 3 2 1 Probe 3 3 2 1 Probe 4 R1 R2 R3 R4 Solenoid valve GAS and Sirens 12 VDC 12 V If a 12Vdc solenoid valve which does not work well is connected to the BX444 Mc Direct connection of 12VDC solenoid valves or sirens to the BX444 Mc is not permitted An external power unit must always be used The BX444 Mc...

Страница 8: ...On the next pass the LED probe will be maintained again and the alarm will be issued In case of fault The LED of the relevant probe starts blinking and remains lit The display will show the FAU Fault fixed indication and the buzzer will issue a continuous sound until 1 The repair has been carried out 2 The relevant probe has been disabled using the micro switch 1 2 4 3 Sensors Probe Identification...

Страница 9: ...memory and the relay switches off when the connected probe no longer detects gas In compliance with the rules this function becomes active only when you select the detection of Toxic Gases reading in ppm Switch 2 4 Selecting of the control unit in oxygen detection mode By setting the micro switch to ON the device is ready to detect the oxygen The display changes color and becomes BLU ATTENTION Sel...

Страница 10: ...ition of the detection sensors You can connect many types of remote sensors to this unit Therefore they should be positioned at different heights depending on the type of gas to be detected These heights are 30 cm from the lowest point of the floor in order to detect Heavy gases L P G etc 30 cm from the highest point of the ceiling in order to detect light gases Methane etc 160 cm from the lowest ...

Страница 11: ...rectly connected If the Fault LED lights up Check that the connecting cables from the BX444 Mc to the probes are intact that the probes are properly powered and that the signal cable is correctly connected If the Over Load Probe LED lights up Check that the power polarity has not been inverted that no short circuit is present that the probes were not damaged during installation that no excessive c...

Страница 12: ...r example sales points in case you buy a new and similar product local collection points waste collection center local recycling center etc By ensuring this product is disposed of correctly you will help prevent potential negative consequence for the environment and human health which could otherwise be caused by inappropriate waste handing of this product The recycling of materials will help to c...

Отзывы: