Selection of the type of gas monitored by each probe
The BX444-Mc if fitted with four micro-switches in order to select the type of gas that the connected probes
should monitor.
The LEL reading is obtained by shifting the switch to ON. Explosive gas.
The ppm reading is obtained by shifting the switch to OFF. Toxic gas
Components and Commands continue
Switch 1 – Selection of the intrinsic safety
In the ON position, the intrinsic safety function is enabled.
In the OFF position, the intrinsic safety function is disabled
Switch 2 - Working Mode of Main alarm relay
In the OFF (impulse) position, the relay remains closed for seconds, and then disenergizes afterwards.
In the ON (continuous) position, the relay remains closed until the RESET button is pressed.
Switch 1 (3) - Alarm memory logging
By setting the micro-switch to ON, the device will log the alarm, maintain the relay closed, and the main alarm
LED will blink, until the RESET button is pressed.
By setting the micro-switch to OFF, the device will not maintain the alarm memory and the relay switches
off when the connected probe no longer detects gas; In compliance with the rules this function
becomes active only when you select the detection of Toxic Gases (reading in “ppm”)
Switch 2 (4) - Selecting of the control unit in oxygen detection mode
By setting the micro-switch to ON, the device is ready to detect the oxygen. The display changes color and
becomes BLU
ATTENTION !! Selecting the detection of oxygen the control unit will be enabled to detect OXYGEN,
and not other types of Gas
By setting the micro-switch to OFF, The control unit is ready to explosive or toxic gas detection.
The display changes color and becomes green.
Zone1 Zone2 Zone3 Zone4
Micro-switch (2) to select the type of gas monitored
Position ON lreading in LEL - Explosive gas
Position OFF reading in ppm - Toxic gas
Light signaling the type of gas selected
ppm is the reading of the concentration for the CO gas
LEL is reading of the concetrazione for Explosive Gas (Methane or LPG)
ppm LEL
Relay’s working mode and the memory of the Main alarm
Zone1 Zone2 Zone3 Zone4
Micro-switch 1 Positive Safety
Micro-switch 2 working mode of the Main Alarm relay
Micro-switch 3 Maintaining Memory
Micro-switch 4 Enabling Oxygen mode
1 2 3 4