background image

Page  3

Main Compatible Probes

MAINTENANCE

The  user  periodically  (every  6  months)  must  perform  a  check  of  the  operation  of  the

control  unit  by spraying  a  suitable  test gas  at  the  base  of  the probes  connected until  the

alarm  condition  is  reached.

•  At  least  once  a  year  make  a  more  accurate  check  by  a  specialist  technician.
                •  The  disabling  of  the  detector  must  be  carried  out  by  qualified  personnel.

Installation  of  the  detector  does  not  exonerate.  From  the  observance  of  all  rules  regarding  the  characteristics,
installation and use of gas appliances. The ventilation of the premises and the discharge of the combustion products
prescribed by UNI norms as from ART. 3 LAW 1083/71 and the relevant provisions of law

.

Protec     ZONE            Detected         Working                                              Automatic

Probe

Sensor          Degree     Suitable for   GAS

 Range             OutPut       Calibration   Calibration  Relay

SG500

Catalytic

IP30

Hausold

CH4-LPG

0÷100% LEL       4÷20 mA

±5 %

NO

NO

SG544

Catalytic

IP44

Tertiary

CH4-LPG

0÷100% LEL       4÷20 mA

±5 %

NO

NO

SGM595

Catalytic

IP55

Tertiary

SeePricelist

0÷100% LEL       4÷20 mA

±5 %

Yes

NO

SGM595/A

Catalytic

IP66

Zone  2

SeePricelist

0÷100% LEL       4÷20 mA

±5 %

Yes

NO

SGM533

Catalytic

IP55

Tertiary

SeePricelist

0÷100% LEL       4÷20 mA

±5 %

Yes

Yes

SG800

Catalytic

IP66

Zone  2

SeePricelist

0÷100% LEL       4÷20 mA

±5 %

Yes

Yes

HCF100

SemiConduct

IP55

Tertiary

Freon

0÷300% ppm     4÷20 mA

±5 %

NO

Yes

SG895

Catalytic

ATEX

Zone  1

SeePricelist

0÷100% LEL       4÷20 mA

±5 %

Yes

NO

SG580

Catalytic

IP66

Zone  2

SeePricelist

0÷100% LEL       4÷20 mA

±5 %

NO

NO

SGF100

Catalytic

IP64

Zone  2

Methane

0÷100% LEL       4÷20 mA

±5 %

Yes

Yes

SGF102

Catalytic

IP64

Zone  2

LPG

0÷100% LEL       4÷20 mA

±5 %

Yes

Yes

SGF104

Optical  Fluo

IP64

Zone  2

Oxigen

In  %

  4÷20 mA

±5 %

Yes

Yes

SGF106

SemiConduct

IP64

Zone  2

Freon

0÷300% ppm     4÷20 mA

±5 %

Yes

Yes

SGF108

Electrochimical IP64

Zone  2

H2S

0÷300% ppm     4÷20 mA

±5 %

Yes

Yes

SGF110

Electrochimical IP64

Zone  2

C O

0÷300% ppm     4÷20 mA

±5 %

Yes

Yes

SGF112

Catalytic

IP64

Zone  2

Hydrogen

0÷100% LEL       4÷20 mA

±5 %

Yes

Yes

CO100r

Electrochimical IP55

Tertiary

C O

0÷300% ppm     4÷20 mA

±5 %

Yes

Yes

CO100Ar

Electrochimical IP66

Zone  2

C O

0÷300% ppm      4÷20 mA

±5 %

Yes

Yes

SG800

duct

Catalytic

IP66

Zone  2

CH4-LPG

0÷100% LEL        4÷20 mA

±5 %

Yes

Yes

CO200

duct

Electrochimical IP66

Zone  2

C O

0÷300% ppm      4÷20 mA

±5 %

Yes

Yes

Legend

Households:  Family  Housing.  Boiler  rooms  max  70  kW-h
Tertiary  Rooms:  Large  Boiler  Rooms,  Offices,  Material  Deposits,  Industrial  Kitchens,  Large  Building  Complexes,  Factories.
Zone 2- Mixed  IP65  ATEX:  Locations  with  a  high probability  of  leekage, High  Risk Areas,  Rooms for which  the applicable  Standards are
in  force.
Area  1-  Hazard  ATEX:  High  Risk  Areas,  Rooms  for  which  Regulations  are  in  force,  Tank  Deposits,  Control  Valves  or  Joint  Railings

WARNING! Actions to be taken in case of alarm

Gas
1) P
ut out all free flames.
2) Close the main gas tap or the LPG cylinder tap.
3) Do not turn any lights on or off; do not turn on any electrical device or appliance.
4) Open windows and doors in order to increase ventilation.
If the alarm stops, its cause must be found and the relevant consequent measures taken.
If the alarm continues and the cause of gas presence cannot be found or removed, abandon the building and call
the emergency services when outside (fire department, distributors, etc.)

IMPORTANT:  The  operation  test  should  not  be  carried  out  with  the  gas  tap  as  this  does  not  guarantee  a  sufficient
concentration  to  activate  the  general  alarm.

Warning !!

If you have the following symptoms: vomiting, sleepiness, or else, go to the closest first aid station
and inform the operators that you could have been poisoned by Carbon Monoxide

or by an excess

or  deficiency  of  oxygen

Содержание BX150

Страница 1: ...he BX150 control unit has been designed and built according to European regulations to flexibly detect the presence of toxic and or explosive gas A microprocessor is used to create a complete surveillance and control system with maximum flexibility Thanks to this and its other features the BX150 is suitable for civil and industrial applications The BX150 control unit has two danger levels 1st LEVE...

Страница 2: ...mage the appliance Avoid abrupt temperature fluctuations Sudden temperature variations can cause condensation and the control unit could work poorly Cleaning Never clean the device with chemical products If necessary wash with a moist cloth Technical Specifications Precautions 90 mm 102 mm 112 mm 10 mm 43 65 mm 90 30 mm Cuttingpanel size Mains Power 230VAC 50 60Hz 10 Secondary Power Through Batter...

Страница 3: ...eon 0 300 ppm 4 20 mA 5 Yes Yes SGF108 Electrochimical IP64 Zone 2 H2S 0 300 ppm 4 20 mA 5 Yes Yes SGF110 Electrochimical IP64 Zone 2 C O 0 300 ppm 4 20 mA 5 Yes Yes SGF112 Catalytic IP64 Zone 2 Hydrogen 0 100 LEL 4 20 mA 5 Yes Yes CO100r Electrochimical IP55 Tertiary C O 0 300 ppm 4 20 mA 5 Yes Yes CO100Ar Electrochimical IP66 Zone 2 C O 0 300 ppm 4 20 mA 5 Yes Yes SG800duct Catalytic IP66 Zone 2...

Страница 4: ...C GAS selection LED This LED lights up when the internal micro switch is switched to CO 7 EXPLOSIVE GAS selection LED This LED lights up when the internal micro switch is switched to GAS 8 FAULT LED This LED will light up when the connected probe is faulty if there is an interruption in the cable connection or if an error was made during wiring 9 OVER LOAD LED probe overload If this LED turns on i...

Страница 5: ...r performing the step of waiting and switches when the BX150 is main alarm In the OFF position the positive safety function is disabled The relay is energized only when the BX150 goes into the mainl alarm Switch 2 Working mode of the main alarm relay In the ON continuous position the relay remains closed until the N button is pressed In the OFF impulse position the relay remains closed for 20 seco...

Страница 6: ...Before connecting to the mains power ensure the voltage is correct Carefully follow the instructions and the connections according to Regulations in force keeping in mind that signal cables should be separated from power cables An automatic cut off switch appropriately identified as device sectioning of the detector should be incorporated in the electrical system adequately located and easily acce...

Страница 7: ...hold Alarm Solenoid valves Ph N 230 VAC NC NA Solenoid valve GAS and Sirens 12 VDC Powersupply 230 12V Diode 1N 5406 12 V 5 4 3 2 1 R1 3 2 1 Probe 1 If a 12Vdc solenoid valve which does not work well is connected to the BX150 Direct connection of 12VDC solenoid valves or sirens to the BX150 is not permitted An external power unit must always be used The BX150 M gives a max current of 50mA Control ...

Страница 8: ...ld Alarm Solenoid valves Powersupply 230 12V Ph N 230 VAC 230 VAC Diode 1N 5406 12 V 5 4 3 2 1 R1 3 2 1 Probe 1 Electrical Connections If a 12Vdc solenoid valve which does not work well is connected to the BX150 Direct connection of 12VDC solenoid valves or sirens to the BX150 is not permitted An external power unit must always be used The BX150 M gives a max current of 50mA ...

Страница 9: ...You can connect many types of remote probes to this unit Therefore they should be positioned at different heights depending on the type of gas to be detected These heights are 30 cm from the lowest point of the floor in order to detect Heavy gases L P G etc 30 cm from the highest point of the ceiling in order to detect light gases Methane etc 160 cm from the lowest point of the floor in order to d...

Страница 10: ...ins power is correctly connected If powered by the battery check that the 12Vdc power is correctly connected If the Fault LED lights up Check that the connecting cables from the BX150 to the probes are intact that the probes are properly powered and that the signal cable is correctly connected If the Over Load Probe LED lights up Check that the power polarity has not been inverted that no short ci...

Страница 11: ...Page 11 NOTES ...

Страница 12: ...ning shall be excluded from the warranty BEINAT S r l is not liable for possible damage direct or indirect to people animals or things from product faults and from its enforced suspension of use DISPOSAL OF OLD ELECTRICAL ELECTRONIC EQUIPMENT This symbol on the product or its packaging to indicates that this product shall not be treated as household waste Instead it shall be handed over to the app...