Page  10

1)  Apply  power  using  the  proper  switch.  This  switch  should  be  fitted  with  protection  fuses.
2) You will notice that some LEDs will light up in turn for about 20 seconds, so as to test the LEDs.
3) The COUNTDOWN begins that lasts about 90 seconds (warm up) afer this the unit is ready to detect.
4)  By  pressing  the  MANUAL  TEST  button,  you  get  the  simulation  of  a  gas  leak  and  the  unit  carries  out  the
following:

a)  The  Pre-alarm  LED  lights  up  calibrated  to  13%  LEL  or  200  ppm  (referred  to  CO)  switching  the  relay  the
buzzer  will  issue  a  low  frequency  sound

b)  The  Main  alarm  LED  lights  up  calibrated  to  20%  LEL  or  300  ppm  (referred  to  CO)  switching  the  relay.
The  Main  alarm  LED  starts  flashing;  the  buzzer  will  issue  a  hight  frequency  sound

5)    To  complete  the  general  test,  issue  gas  from  a  pre-calibrated  aerosol

6)  If  you  want  to  simulate  a  zone  fault,  you  only  need  to  disconnect  the  return  cable  of  the  corresponding
probe.
-lights  up  the  flashing  LED  and  FAULT  led  of  the  MAIN  ALARM  led;
-the  buzzer  emits  a  continuous  sound;
-the  fault  relay  and  the  main  alarm  relay  will  switch.
Reconnect the return cable and press the RESET button to restore the functioning of the control unit.

If  other  problems  arise,  a  specialised  and/or  authorised  technician  and/or  the  Distributor  of  BEINAT  S.r.l.
should  be  contacted  directly.

If  the  device  does  not  start  up.
Check  that  the  230/240V  mains  power  is  correctly  connected.  If  powered  by  the  battery,  check  that  the  12Vdc
power  is  correctly  connected.
If  the  Fault  LED  lights  up.
Check  that  the  connecting  cables  from  the  BX150  to  the  probes  are  intact,  that  the  probes  are  properly
powered,    and  that  the  signal  cable  is  correctly  connected.

If  the  Over  Load  Probe  LED  lights  up.
Check: that  the power  polarity has  not been  inverted, that  no  short-circuit  is present,  that the  probes  were  not
damaged  during  installation,  that  no  excessive  current  absorption  is  present.
If  the  Over  Load  Battery  LED  lights  up.
Check  that  the  connection  cables  are  not  short-circuited,  that  the  polarity  has  not  been  inverted,  or  that  the
battery  is  not  damaged
If  the  Control  Unit  is  repeatedly  issuing  an  alarm.
Check  that  there  are  no  gas  leaks.  If  the  alarm  signal  and  the  FAULT  indicator  light  turn  on  together,  check
the  probes.
If  the  Control  Unit  is  issuing  an  alarm  and  does  not  shut  off  the  devices  connected  to  it.
Check  that  the  wiring  is  correct  and  that  the  jumper  that  carries  power  to  the  relay  has  been  set  properly.  All
relays  must  be  free  from  electrical  power
.
Check  the  drawing  of  the  connections.
If  a  12Vdc  solenoid  valve,  which  does  not  work  well,  is  connected  to  the  BX150.
Direct  connection  of  12Vdc  solenoid  valves  or  sirens  to  the  BX150  is  not  permitted.  An  external  power  unit
must  always  be  used.  The  BX150  gives  a  max  current  of  50mA.

Troubleshooting and solutions  before calling a technician

0

1

3

2

1,1

V.

Vol tmeter

WARNING.
This  measurement  should
be  performed  in  clean  air

+

+

5    4    3    2    1

R1

3   2   1

Probe  1

Turning on

Содержание BX150

Страница 1: ...he BX150 control unit has been designed and built according to European regulations to flexibly detect the presence of toxic and or explosive gas A microprocessor is used to create a complete surveillance and control system with maximum flexibility Thanks to this and its other features the BX150 is suitable for civil and industrial applications The BX150 control unit has two danger levels 1st LEVE...

Страница 2: ...mage the appliance Avoid abrupt temperature fluctuations Sudden temperature variations can cause condensation and the control unit could work poorly Cleaning Never clean the device with chemical products If necessary wash with a moist cloth Technical Specifications Precautions 90 mm 102 mm 112 mm 10 mm 43 65 mm 90 30 mm Cuttingpanel size Mains Power 230VAC 50 60Hz 10 Secondary Power Through Batter...

Страница 3: ...eon 0 300 ppm 4 20 mA 5 Yes Yes SGF108 Electrochimical IP64 Zone 2 H2S 0 300 ppm 4 20 mA 5 Yes Yes SGF110 Electrochimical IP64 Zone 2 C O 0 300 ppm 4 20 mA 5 Yes Yes SGF112 Catalytic IP64 Zone 2 Hydrogen 0 100 LEL 4 20 mA 5 Yes Yes CO100r Electrochimical IP55 Tertiary C O 0 300 ppm 4 20 mA 5 Yes Yes CO100Ar Electrochimical IP66 Zone 2 C O 0 300 ppm 4 20 mA 5 Yes Yes SG800duct Catalytic IP66 Zone 2...

Страница 4: ...C GAS selection LED This LED lights up when the internal micro switch is switched to CO 7 EXPLOSIVE GAS selection LED This LED lights up when the internal micro switch is switched to GAS 8 FAULT LED This LED will light up when the connected probe is faulty if there is an interruption in the cable connection or if an error was made during wiring 9 OVER LOAD LED probe overload If this LED turns on i...

Страница 5: ...r performing the step of waiting and switches when the BX150 is main alarm In the OFF position the positive safety function is disabled The relay is energized only when the BX150 goes into the mainl alarm Switch 2 Working mode of the main alarm relay In the ON continuous position the relay remains closed until the N button is pressed In the OFF impulse position the relay remains closed for 20 seco...

Страница 6: ...Before connecting to the mains power ensure the voltage is correct Carefully follow the instructions and the connections according to Regulations in force keeping in mind that signal cables should be separated from power cables An automatic cut off switch appropriately identified as device sectioning of the detector should be incorporated in the electrical system adequately located and easily acce...

Страница 7: ...hold Alarm Solenoid valves Ph N 230 VAC NC NA Solenoid valve GAS and Sirens 12 VDC Powersupply 230 12V Diode 1N 5406 12 V 5 4 3 2 1 R1 3 2 1 Probe 1 If a 12Vdc solenoid valve which does not work well is connected to the BX150 Direct connection of 12VDC solenoid valves or sirens to the BX150 is not permitted An external power unit must always be used The BX150 M gives a max current of 50mA Control ...

Страница 8: ...ld Alarm Solenoid valves Powersupply 230 12V Ph N 230 VAC 230 VAC Diode 1N 5406 12 V 5 4 3 2 1 R1 3 2 1 Probe 1 Electrical Connections If a 12Vdc solenoid valve which does not work well is connected to the BX150 Direct connection of 12VDC solenoid valves or sirens to the BX150 is not permitted An external power unit must always be used The BX150 M gives a max current of 50mA ...

Страница 9: ...You can connect many types of remote probes to this unit Therefore they should be positioned at different heights depending on the type of gas to be detected These heights are 30 cm from the lowest point of the floor in order to detect Heavy gases L P G etc 30 cm from the highest point of the ceiling in order to detect light gases Methane etc 160 cm from the lowest point of the floor in order to d...

Страница 10: ...ins power is correctly connected If powered by the battery check that the 12Vdc power is correctly connected If the Fault LED lights up Check that the connecting cables from the BX150 to the probes are intact that the probes are properly powered and that the signal cable is correctly connected If the Over Load Probe LED lights up Check that the power polarity has not been inverted that no short ci...

Страница 11: ...Page 11 NOTES ...

Страница 12: ...ning shall be excluded from the warranty BEINAT S r l is not liable for possible damage direct or indirect to people animals or things from product faults and from its enforced suspension of use DISPOSAL OF OLD ELECTRICAL ELECTRONIC EQUIPMENT This symbol on the product or its packaging to indicates that this product shall not be treated as household waste Instead it shall be handed over to the app...

Отзывы: