background image

Page  2

CHECK the integrity of the unit after having removed it from the box.
Check that the data written on the box correspond to the type of gas used.
When doing the electrical connections, follow the drawing closely.
Any use of the detector for purposes other than the intended one is considered improper, and as
a result of which BEINAT S.r.l. therefore disclaims any responsibility for possible damages caused
to people, animals or objects.
IMPORTANT:  Do  not test  the device using the  gas tap as this  does  not necessarily provide
sufficient concentration to activate the main alarm.
TERMS and EXPECTATIONS: The installation of the control unit, its ordinary and extraordinary
maintenance, every six months, and its out of service removal at the end of the functional life
guaranteed by the manufacturer, must be carried out by authorized or specialized personnel.
In order to achieve long and satisfactory use of your digital control unit, use it by respecting the following precautions.
Do not wet.
The control unit can be seriously damaged as it is not waterproof either when immersed in water or exposed to high
levels of humidity.
Do not drop it.
Heavy knocks or falls during transportation or installation can damage the appliance.
Avoid abrupt temperature fluctuations.
Sudden temperature variations can cause condensation and the control unit could work poorly.
Cleaning
Never clean the device with chemical products. If necessary, wash with a moist cloth.

Technical Specifications

Precautions

9

0

 mm

102 mm

112 mm

10 mm

43,65 mm

9

0

,3

0

 mm

Cutt

ing p

ane

l siz

e

Mains  Power  ......................................................................................................  230VAC  50/60Hz  ±10%
Secondary Power Through Battery max 2.2 Ah  ...............................................................12,7 V           ±10%
Battery Charger  max 2.2 Ah

  ...............................................................    By  means  of  a  microprocessor

Power Demand

  ....................................................................................................   4  W  max @  230V

Power  Demand      ..............................................................................................   3 W  max @  12 V
Relay  Contact  Range    ..............................................................................................................10A  250V
Pre Alarm  ........................................................................................... Set  to  13%  of L.E.L.  or 200ppm  CO
Final Alarm  ........................................................................................ Set  to  20% of L.E.L. or 300ppm  CO
Sensor’s faults detected  by Fault Circuit   .................................................. Interruption, short circuit,  or wear
OVER  LOAD Check    .................................................................................1 for each  probe  and  1  for battery
Micro-switches  to  include  or  exclude  the  probes  ...........................................................................  2  built  in
Max number of probes that can be connected 2 .......................... Catalityc, Electrochemical Cell, Semiconductor
Input  Signal    .......................................................................................................  4  ÷  20  mA on  220  ohm
Device  Accuracy    ......................................................................................................................  1%  FS
Control Unit  ............................................................................................................... 8-bit microprocessor
Functioning  Temperature    .................................................................................................  -10°C  ÷  +60°C
Waiting, blinking period

 ....................................................................................................... 90 seconds

Manual  Test  .............................................................................................................................  Built  in
Max.  distance  between  probes  and  unit........    ................................................................................  100  m
Cable  diameter  for  connecting  probes  .............................................................................................  1  mm

2

Connection: The cable of connection of the probe must not be installed together with the power cables.
Otherwise, make sure to use a shielded cable
Case modular type size DIN EN 50092 ....................................................................................... 112x96x44
Degree  of  Protection    ....................................................................................................................  IP44

Содержание BX150

Страница 1: ...he BX150 control unit has been designed and built according to European regulations to flexibly detect the presence of toxic and or explosive gas A microprocessor is used to create a complete surveillance and control system with maximum flexibility Thanks to this and its other features the BX150 is suitable for civil and industrial applications The BX150 control unit has two danger levels 1st LEVE...

Страница 2: ...mage the appliance Avoid abrupt temperature fluctuations Sudden temperature variations can cause condensation and the control unit could work poorly Cleaning Never clean the device with chemical products If necessary wash with a moist cloth Technical Specifications Precautions 90 mm 102 mm 112 mm 10 mm 43 65 mm 90 30 mm Cuttingpanel size Mains Power 230VAC 50 60Hz 10 Secondary Power Through Batter...

Страница 3: ...eon 0 300 ppm 4 20 mA 5 Yes Yes SGF108 Electrochimical IP64 Zone 2 H2S 0 300 ppm 4 20 mA 5 Yes Yes SGF110 Electrochimical IP64 Zone 2 C O 0 300 ppm 4 20 mA 5 Yes Yes SGF112 Catalytic IP64 Zone 2 Hydrogen 0 100 LEL 4 20 mA 5 Yes Yes CO100r Electrochimical IP55 Tertiary C O 0 300 ppm 4 20 mA 5 Yes Yes CO100Ar Electrochimical IP66 Zone 2 C O 0 300 ppm 4 20 mA 5 Yes Yes SG800duct Catalytic IP66 Zone 2...

Страница 4: ...C GAS selection LED This LED lights up when the internal micro switch is switched to CO 7 EXPLOSIVE GAS selection LED This LED lights up when the internal micro switch is switched to GAS 8 FAULT LED This LED will light up when the connected probe is faulty if there is an interruption in the cable connection or if an error was made during wiring 9 OVER LOAD LED probe overload If this LED turns on i...

Страница 5: ...r performing the step of waiting and switches when the BX150 is main alarm In the OFF position the positive safety function is disabled The relay is energized only when the BX150 goes into the mainl alarm Switch 2 Working mode of the main alarm relay In the ON continuous position the relay remains closed until the N button is pressed In the OFF impulse position the relay remains closed for 20 seco...

Страница 6: ...Before connecting to the mains power ensure the voltage is correct Carefully follow the instructions and the connections according to Regulations in force keeping in mind that signal cables should be separated from power cables An automatic cut off switch appropriately identified as device sectioning of the detector should be incorporated in the electrical system adequately located and easily acce...

Страница 7: ...hold Alarm Solenoid valves Ph N 230 VAC NC NA Solenoid valve GAS and Sirens 12 VDC Powersupply 230 12V Diode 1N 5406 12 V 5 4 3 2 1 R1 3 2 1 Probe 1 If a 12Vdc solenoid valve which does not work well is connected to the BX150 Direct connection of 12VDC solenoid valves or sirens to the BX150 is not permitted An external power unit must always be used The BX150 M gives a max current of 50mA Control ...

Страница 8: ...ld Alarm Solenoid valves Powersupply 230 12V Ph N 230 VAC 230 VAC Diode 1N 5406 12 V 5 4 3 2 1 R1 3 2 1 Probe 1 Electrical Connections If a 12Vdc solenoid valve which does not work well is connected to the BX150 Direct connection of 12VDC solenoid valves or sirens to the BX150 is not permitted An external power unit must always be used The BX150 M gives a max current of 50mA ...

Страница 9: ...You can connect many types of remote probes to this unit Therefore they should be positioned at different heights depending on the type of gas to be detected These heights are 30 cm from the lowest point of the floor in order to detect Heavy gases L P G etc 30 cm from the highest point of the ceiling in order to detect light gases Methane etc 160 cm from the lowest point of the floor in order to d...

Страница 10: ...ins power is correctly connected If powered by the battery check that the 12Vdc power is correctly connected If the Fault LED lights up Check that the connecting cables from the BX150 to the probes are intact that the probes are properly powered and that the signal cable is correctly connected If the Over Load Probe LED lights up Check that the power polarity has not been inverted that no short ci...

Страница 11: ...Page 11 NOTES ...

Страница 12: ...ning shall be excluded from the warranty BEINAT S r l is not liable for possible damage direct or indirect to people animals or things from product faults and from its enforced suspension of use DISPOSAL OF OLD ELECTRICAL ELECTRONIC EQUIPMENT This symbol on the product or its packaging to indicates that this product shall not be treated as household waste Instead it shall be handed over to the app...

Отзывы: