58
| Beijer BFI-P2 User Guide |
Version 3.04
www.beijerelectronics.com
Par
Name
Minimum
Maximum
Default
Units
P5-07 Fieldbus Ramp Control
0
1
0
-
0
Disabled
Ramps are controlled from internal drive parameters P1-03 and P1-04.
1
Enabled
Ramps are controlled directly by the Fieldbus PDI4 Data Word.
P5-08 Fieldbus PDO-4 Data Select
0
7
0
-
0
Motor torque
0 to 2000 = 0 to 200.0%
1
Motor power
Output power in kW to two decimal places, e.g. 400 = 4.00kW
2
Digital Input Status
Bit 0 indicates digital input 1 status, bit 1 indicates digital input 2 status etc
3
Analog Input 2
0 to 1000 = 0 to 100.0%
4
Heatsink Temperature
0 to 100 = 0 to 100°C
5
User register 1
User Defined Register 1 Value
6
User register 2
User Defined Register 1 Value
7
P0-80 value
User Selected data value
P5-12
Fieldbus PDO-3 Data Select
0
7
0
-
0
Motor current
Output current to 1 decimal place, e.g. 100 = 10.0 Amps
1
Motor power
Output power in kW to two decimal places, e.g. 400 = 4.00kW
2
Digital input status
Bit 0 indicates digital input 1 status, bit 1 indicates digital input 2 status etc
3
Analog Input 2
0 to 1000 = 0 to 100.0%
4
Heatsink Temperature
0 to 100 = 0 to 100°C
5
User register 1
User Defined Register 1 Value
6
User register 2
User Defined Register 2 Value
7
P0-80 value
User Selected data value
P5-13
Fieldbus PDI-4 Function Select
0
1
0
-
0
Fieldbus ramps
This option must be selected if the drive acceleration and deceleration ramps are to
be controlled from the fieldbus. P5-07 must also be set to 1 to enable this function.
1
User register 4
The value received by the drive in PDI 4 is transferred to User Register 4. This option
allows the function of the process data word to be defined in Parameter Group 9.
In this case, User Register 4 should not be written to within any PLC function code,
although the value can be read.
P5-14
Fieldbus PDI-3 Function Select
0
2
0
-
0
Torque reference / limit
This option must be selected if the drive output torque limit / setpoint is to be controlled
from the fieldbus. This also requires setting P4-06 = 3.
1
PID reference
This option allows the setpoint to the PID controller to be received from the Fieldbus. In
order for this option to be used, P9-38 must be set to 1, and the PID User setpoint must
not be utilised within the PLC function.
2
User register 3
The value received by the drive in PDI 3 is transferred to User Register 3. This option
allows the function of the process data word to be defined in Parameter Group 9.
In this case, User Register 3 should not be written to within any PLC function code,
although the value can be read.
P5-15
Modbus Response Delay
0
16
0
Chr
Allows the user to configure an additional delay between the drive receiving a request via the Modbus RTU interface, and transmitting a
reply. The value entered represents the delay in addition to the minimum delay permissible according to the Modbus RTU specification,
and is expressed as the number of additional characters.
P5-16
Drive Modbus Address
0
247
0
-
The drive Modbus (and Optibus) address is set in P5-01 which has a maximum value of 63. If a higher Modbus address is required for a
larger network, it can be set in this parameter.
If this parameter is set to a value greater than 0, this address will become the Drive Modbus address. If this value is set to 0, P5-01
determines the Drive Modbus address.
8
Extended P
arameters