Version 3.04
| Beijer BFI-P2 User Guide |
47
www.beijerelectronics.com
8. Extended Parameters
8.1. Parameter Group 2 - Extended Parameters
Par
Parameter Name
Minimum
Maximum
Default
Units
P2-01
Preset Jog Frequency / Speed 1
P1-02
P1-01
5.0
Hz / Rpm
P2-02
Preset Jog Frequency / Speed 2
P1-02
P1-01
10.0
Hz / Rpm
P2-03
Preset Jog Frequency / Speed 3
P1-02
P1-01
25.0
Hz / Rpm
P2-04
Preset Jog Frequency / Speed 4
P1-02
P1-01
50.0 (60.0)
Hz / Rpm
P2-05
Preset Jog Frequency / Speed 5
P1-02
P1-01
0.0
Hz / Rpm
P2-06
Preset Jog Frequency / Speed 6
P1-02
P1-01
0.0
Hz / Rpm
P2-07
Preset Jog Frequency / Speed 7
P1-02
P1-01
0.0
Hz / Rpm
P2-08
Preset Jog Frequency / Speed 8
P1-02
P1-01
0.0
Hz / Rpm
Preset Speeds / Frequencies selected by digital inputs depending on the setting of P1-13.
If P1-10 = 0, the values are entered as Hz. If P1-10 > 0, the values are entered as Rpm.
Setting a negative value will reverse the direction of motor rotation.
P2-09
Skip Frequency Center Point
P1-02
P1-01
0.0
Hz / Rpm
P2-10
Skip Frequency Band Width
0.0
P1-01
0.0
Hz / Rpm
The Skip Frequency function is used to avoid the BFI drive operating at a certain output frequency, for example at a frequency which
causes mechanical resonance in a particular machine. Parameter P2-09 defines the centre point of the skip frequency band, and is
used in conjunction with P2-10. The BFI drive output frequency will ramp through the defined band at the rates set in P1-03 and P1-04
respectively, and will not hold any output frequency within the defined band. If the frequency reference applied to the drive is within
the band, the BFI drive output frequency will remain at the upper or lower limit of the band.
P2-11
Analog Output 1 Function (Terminal 8)
0
12
8
-
Digital Output Mode. Logic 1 = +24V DC
0
Drive running
Logic 1 when the BFI drive is enabled (Running).
1
Drive healthy
Logic 1 when no Fault condition exists on the drive.
2
At speed
Logic 1 when the output frequency matches the setpoint frequency.
3
Motor speed > 0
Logic 1 when the motor runs above zero speed.
4
Motor speed >= limit
Logic 1 when the motor speed exceeds the adjustable limit.
5
Motor current >=limit
Logic 1 when the motor current exceeds the adjustable limit.
6
Motor torque >= limit
Logic 1 when the motor torque exceeds the adjustable limit.
7
Analog input 2 >=limit
Logic 1 when the signal applied to the Analog Input 2 exceeds the adjustable limit.
NOTE
When using settings 4 – 7, parameters P2-16 and P2-17 must be used together to control the behaviour. The output will switch
to Logic 1 when the selected signal exceeds the value programmed in P2-16, and return to Logic 0 when the signal falls below the
value programmed in P2-17.
Analog Output Mode
8
Motor speed
0 to 100% of P1-01 (Maximum Frequency).
9
Motor current
0 to 200% of P1-08 (Motor Nominal Current).
10
Motor torque
0 to 200% of motor rated torque.
11
Motor power
0 to 150% of drive rated power.
12
PID Output
Output from the internal PID Controller, 0 – 100%.
P2-12
Analog Output 1 Format
See Below
-
-
-
0 to10V
-
10 to 0V
-
0 to 20mA
-
20 to 0mA
-
4 to 20mA
-
20 to 4mA
8
Extended P
arameters