Beijer Electronics Frequency Inverter BFI-H3
KI00363D 2021-07
9 (32)
•
Shield of the motor cable should be connected to ground/earth in both ends. On motor side an
EMC-gland is to be used.
•
For IP20 drives the shield of the motor cable can be clamped to the mounting plate with a clip
as on picture below.
•
For IP55 and IP66 drives use an EMC gland and by that get a 360 degrees grounding of the shield.
•
BFI is to be connected with ground/PE by separate grounding wire.
•
Motor must also be well attached into the mechanical frame of the machinery and have the same
potential as the electrical cabinet. Separate earth connection might be necessary.
•
Motor cable should avoid being installed close to telephone-, network- or signal wiring.
Minimum distance is 10 cm.
More detailed description is to be found in User and Installation Manual BFI-H3.
4.8 Safe Torque Off, STO
BFI-H3 has two digital inputs for Safe Torque Off. These two inputs must be correct
connected otherwise the Drive will not run and
will be shown on the display.
If safety is not to be used terminal 12 must be connected to terminal 1 and terminal 13
connected to terminal 7. More about safety inputs can be read in User Manual BFI-H3.
1 2 3 4 5 6 7 8 9 10 11 12 13
0V
+24Vdc
External
Power
Supply
Safety relay
1 2 3 4 5 6 7 8 9 10 11 12 13
Safety relay
Wires should be
protected
against short
circuits as
shown above