background image

 

Beijer Electronics Frequency Inverter BFI-H3 

                         

KI00363D           2021-07

 

 

 

www.beijerelectronics.com

             

 

27 (32)                                   

 

 

6.7 Monitoring from Keypad  

Parameter group 0 contain variables to be monitored as table below: 

 

Description 

Display range 

Explanation 

P0-01 

1st Analog Input Value 

-100 %  to 100% 

100% = max input voltage 

P0-02 

2nd Analog Input Value 

0 to 100% 

100% = max input voltage 

P0-03 

Digital Input Status 

00000 to 11111 

MSB: Dig In1 / LSB: Dig In 5 

P0-04 

Speed Reference Input 

-P1-

01 … P1-01 

Displayed in Hz if P-10 = 0, otherwise displayed in RPM 

P0-07 

Fieldbus Speed Reference 

-P1-

01 … P1-01 

Displays se-point received from Fieldbus interface. 

P0-08 

PID Reference 

0 to 100 % 

Displays the setpoint input to the PID controller. 

P0-09 

PID feedback 

0 to 100 % 

Displays the feedback value to the PID controller. 

P0-11 

Motor Voltage 

0 … 600V AC 

Value of RMS voltage applied to motor 

P0-13 

Trip Log 

 

Displays the four latest fault codes 

P0-19 

Cascade Run Time Log 

hours 

Run Time values for pumps in cascade mode. 

0 = Master, 1 = Pump1, 2 = Pump2 

P0-20 

DC Bus Voltage 

0 … 1000V dc 

Internal DC bus voltage 

P0-21 

Internal Temperature 

-

20 … 100 °C 

Temperature of heatsink in 

°

P0-22 

Time Left to next service 

 

When 0 => service indicator is led on the display  

P0-26 

kWh meter 

0 to 999,9 

When overflow P00-27 increases by 1 and reset to 0. 

P0-27 

MWh meter 

0 to 65535 

Displays the amount of energy consumed by the drive. 

P0-28 

Software Version 

 

I/O-version, I/O Checksum, DSP version, DSP checksum. 

P0-29 

Drive Type 

 

Frame size, Power rating and output phases 

P0-30 

Drive Serial Number 

 

Unique drive serial number. 

P0-31 

Total Run Time 

0 to 99999 hours 

Displays the total operating time of the drive. 

P0-35 

Fan Run Time 

0 to 99999 hours 

Displays total operating time of internal cooling fans. 

P0-36 

DC Bus Voltage at Trip  

V DC 

Values logged before trip with 8 samples total (256 msec). 

P0-37 

DC Bus Voltage Ripple at Trip 

V DC 

Values logged before trip with 8 samples total (20 msec). 

P0-38 

Heatsink Temperature at Trip 

-

20 … 100 °C 

Values logged before trip with 8 samples total (30 sec). 

P0-39 

Ambient Temperature at Trip 

°C 

Values logged before trip with 8 samples total (30 sec). 

P0-40 

Motor Current Log at Trip 

Values logged before trip with 8 samples total (256 msec). 

P0-41 

Over Current Fault Counter 

 

Over Current fault counter 

P0-42 

Over Voltage Fault Counter 

 

Over Voltage fault counter 

P0-43 

Under Voltage Fault Counter 

 

Under Voltage fault counter 

P0-44 

Heatsink Over Temperature  

 

Heatsink Over Temperature fault counter 

P0-45 

Brake Chopper Short Circuit  

 

Brake Chopper Short Circuit fault counter 

P0-46 

Ambient Over Temperature  

 

Ambient Over Temperature fault counter 

P0-49 

Modbus RTU / BACnet  

 

Modbus RTU/BACnet  communication fault counter  

P0-58 

Load Torque Profile Current 

Values 

5 Autotuned values of Load Torque Characteristic function. 

First display 

–Current at minimum speed 

Second display 

–Current at first measurement interval 

Third display 

–Current at second measurement interval 

Fourth display 

–Current at third measurement interval 

Fifth display 

–Current at maximum speed 

 

P0-64 

Switching Frequency 

kHz 

Displays the actual effective Switching frequency 

P0-65 

Drive Life Time 

 

Powered up time, hours, min, and sec 

P0-70 

Option Module ID-code 

 

Identifies Type of Option Module in option module slot 

P0-71 

Fieldbus module ID 

 

Fieldbus module Identification Code 

Содержание BFI-H3

Страница 1: ...t disconnect until 10 minutes have elapsed after turning off the supply Ensure correct earthing connections The earth cable must be sufficient to carry the maximum supply fault current which normally...

Страница 2: ...22 6 KEYPAD 23 6 1 SELECTING LANGUAGE 23 6 2 DRIVE OPERATING DISPLAY 23 6 3 CHANGING PARAMETER VALUES 24 6 4 PARAMETERS FACTORY RESET USER RESET 25 6 5 SELECTING BETWEEN HAND AND AUTO CONTROL 25 6 6...

Страница 3: ...ght kg 1 x 230 V 3 x 230 V 3 x 400 V 0043 0105 0 75 2 2 kW 0043 0105 0 75 2 2 kW 0022 0140 0 75 5 5 kW 2 257 188 186 200 176 172 4 8 None 0180 0240 4 0 5 5 kW 0180 0300 7 5 15 kW 3 310 211 235 252 198...

Страница 4: ...00 V 0300 0460 7 5 11 kW 0300 0460 15 22 kW 4 450 171 252 428 110 12 0610 0900 15 22 kW 0610 0900 30 45 kW 5 540 235 270 515 175 23 1100 1500 30 37 kW 1100 1800 55 90 kW 6 865 330 330 830 200 55 1800...

Страница 5: ...B 4 x M10 Size 8 4 x M12 Required tightening Torques Control terminals All Sizes 0 5 Nm Required tightening Torques Power terminals Size 2 3 1 0 Nm Size 4 2 Nm Size 5 4 Nm Size 6A 12 Nm Size 6B 15 Nm...

Страница 6: ...n hardware limitations and do NOT take into consideration any requirements for compliance to any EMC standards Maximum motor cable length stated applies to using a screened motor cable When using an u...

Страница 7: ...pplying Derating Factors A 4kW IP66 drive is to be used at an altitude of 2000 metres above sea level with 16 kHz switching frequency and 45 C ambient temperature Rated current of the drive is 9 5 Amp...

Страница 8: ...hould be dimensioned according to any local codes or regulations 400V 230V 690V 400V STAR DELTA Motor cable must be a symmetrical shielded cable where the screen covers at least 85 of the cable surfac...

Страница 9: ...he electrical cabinet Separate earth connection might be necessary Motor cable should avoid being installed close to telephone network or signal wiring Minimum distance is 10 cm More detailed descript...

Страница 10: ...mally called IT net IT net is normally being used in all types of boats and also some parts of Norway In the rest of Europe TN net is most common were EMC filter can be used The EMC filter on BFI IP20...

Страница 11: ...nalog ref 1 10 VDC AOUT1 0 10 V 24 VDC Output frequency 0 10 V 0 VDC 0 V reference Relay Output 2 Drive Enabled 17 18 10 12 13 AIN2 Analog ref 2 STO Safety in STO Safety in AOUT2 0 10 V 24 VDC Output...

Страница 12: ...are accessible All other parameters are accessible with this parameter put to 201 P2 24 Switching Frequency Drive depending Keep as low as possible Higher value decreases audible noise in motor but i...

Страница 13: ...r Analog setpoint Start in forward or reverse direction by digital signal and set frequency is either a fixed preset speed or analog input signal on terminal 6 Analog input is either 0 10 V or 4 20 mA...

Страница 14: ...ed 2 10 Hz Select Select Select P2 03 PresetSpeed 3 25 Hz Not used Select Select P2 04 PresetSpeed 4 50 Hz Select Select P2 05 PresetSpeed 5 0 Not used Select P2 06 PresetSpeed 6 0 Select P2 07 Preset...

Страница 15: ...rnal PID controller P2 13 Analog Output 2 Function 9 P2 12 Analog Output 1 0 If outputs is to be transistor outputs these parameters do not need to be configured 0 0 to 10 VDC 1 10 to 0 VDC 2 0 to 20...

Страница 16: ...sd P5 01 EtherNet IP Set manually by PC program Modbus TCP CC Link Ver1 Remote device station Exclusive station 2 P5 01 P5 03 9 6 156 kbs 19 2 625 kbs 38 4 2 5 Mbs 57 6 5 Mbs 115 10 Mbs Ethercat Conta...

Страница 17: ...DI3 0 What to be written in word 3 0 Not used No function 1 User PID Reference 0 to 1000 0 to 100 0 2 User Register 3 Variable in PLC program or group 9 parameters P5 13 Fieldbus Module PDI4 0 What to...

Страница 18: ...mmand Source 0 4 4 Control by Modbus RTU P1 14 Parameter Access 0 201 Get access to all parameter P5 01 Drive Fieldbus Adress 0 Stationnumber 0 63 First Drive should be stationnumber 1 P5 03 Baud Rate...

Страница 19: ...t P1 09 Motor Rated Frequency motor rated frequency P4 05 Motor Power Factor normally called cos of the motor P4 01 0 Standard induction motor with variable torque demand like fans 1 Standard inductio...

Страница 20: ...1 P9 01 Enable Input source 1 1 Enable on Digital Input1 terminal 2 P9 03 Forward Run Input Source 1 1 Start signal on Digital Input1 terminal 2 P9 07 Reset Input Source 1 1 Alarm Reset on Digital Inp...

Страница 21: ...PID Error to Enable Ramp 0 0 Internal ramps are always used 0 1 100 When PID error is less than setting internal ramps are not used and PID controller ramps output frequency Drive can react quickly to...

Страница 22: ...ected to BFI through it s RJ45 connector BFI Smartstick also has a memory for parameter settings that can be read or written by it s buttons Choose BFI Stick Smart BLE in Communication Settings Push S...

Страница 23: ...Inverter BFI H3 KI00363D 2021 07 www beijerelectronics com 23 32 6 Keypad The drive is configured and its operation monitored via the keypad and display 6 1Selecting language 6 2Drive Operating Displa...

Страница 24: ...Beijer Electronics Frequency Inverter BFI H3 KI00363D 2021 07 www beijerelectronics com 24 32 6 3Changing Parameter Values BFI H3 BFI H3 BFI H3 BFI H3 BFI H3 BFI H3 BFI H3 BFI H3 BFI H3 BFI H3...

Страница 25: ...1 If required the User Default Parameters may be cleared by setting P6 29 2 If the user wishes to reload Factory Defaults parameters to the drive memory then follow the procedure shown below left If t...

Страница 26: ...can be used to speed up selecting and changing parameters when using the keypad When extended or advanced parameter access is enabled additional parameter groups are visible and may be selected quick...

Страница 27: ...1 Total Run Time 0 to 99999 hours Displays the total operating time of the drive P0 35 Fan Run Time 0 to 99999 hours Displays total operating time of internal cooling fans P0 36 DC Bus Voltage at Trip...

Страница 28: ...p Stop Mode Ramping Fast stop Coasting DC brake Zero speed holding time Motor Overload protect Current limit Input and output loss phase detection Trip level is resistance 2 5 kOhm General Functions P...

Страница 29: ...plier for further information For disposal in countries outside of the European Union If you wish to discard this product please contact your local authorities or dealer and ask for the correct method...

Страница 30: ...ctions into the drive fuses contactors 08 Over temperature trip Heatsink over temperature The heatsink temperature can be displayed in P0 21 A historical log is stored at 30 sec intervals prior to a t...

Страница 31: ...rectly connected and free from faults Measured motor stator resistance varies between phases Check the windings for correct resistance and balance 41 Autotune fail 2 Measured motor stator resistance i...

Страница 32: ...Beijer Electronics Frequency Inverter BFI H3 KI00363D 2021 07 www beijerelectronics com 32 32...

Отзывы: