![background image](http://html1.mh-extra.com/html/beijer-electronics/bfi-h3/bfi-h3_start-up_2723572003.webp)
Beijer Electronics Frequency Inverter BFI-H3
KI00363D 2021-07
3 (32)
4
Installation
The drive should be mounted in a vertical position only on a flat, flame resistant, vibration free
mounting using the integral holes. IP55/66 is allowed to be mounted outdoors but must be
protected from sunlight and it also recommended having a roof to avoid snow directly on the
drive. BFI will not start if ambient temperature is below 10 Celsius. See User Manual BFI-H3
for more details.
4.1 Physical dimensions IP66, Outdoor rated
BFI-H3-IP66
Drive
size
A
Height
[mm]
B
Width
[mm]
C
Depth
[mm]
D
[mm]
E
[mm]
F
[mm]
Weight
[kg]
1 x 230 V
3 x 230 V
3 x 400 V
0043
– 0105
[0,75
–2,2 kW]
0043
– 0105
[0,75
–2,2 kW]
0022
– 0140
[0,75- 5,5 kW]
2
257
188
186
200
176
172
4,8
None
0180
– 0240
[4,0
– 5,5 kW]
0180
– 0300
[7,5
– 15 kW]
3
310
211
235
252
198
225
7,7
None
0300
– 0460
[7,5
– 11 kW]
0390
– 0460
[18
– 22 kW]
4
360
240
271
227
230
260
9,5
NOTE
Mounting Bolts
All Sizes: : 4 x M4.
Required tightening Torque Control terminals
All Sizes: : 0,5 Nm.
Required tightening Torque Power terminals
Size 2 and 3: 0,8 Nm; Size 4: 2 Nm
Drive IP-
class and
Size
X [mm]
Above
&
Below
Y
[mm]
Either
Side
Z [mm]
Between
drives
Minimum
Airflow
[m3/min]
IP20, size 2
75
10
46
0,3
IP20, size 3
100
10
52
0,9
IP20, size 4
200
25
70
1,7
IP20, size 5/6
200
25
70
2,9
IP20, size 8
350
50
412
20
All IP55 and
IP66
200
10
10
No require-
ment
Note
All BFI-H3 IP20 can be mounted close to each
without any space in between