78
configurAtion StepS
Behnke AT6 manual
Routine tests
*17*
#
Destination phone number for
the test
Phone number of the alarm receiver
for routine test call.
*19*
#
Manual callback test
Triggers a test call to the entered
phone number.
*27*
00 to
99 #
Days between tests
Number of days between routine tests.
Always enter two digits. To deactivate
test "00".
Maximum 3 days according to EN81-
28: *27*03#
*31*
0.3 or 4 # Type of routine test
Protocol of the routine test call.
0 = P100
3= CPC
4 = CLIP (use phone number for iden-
tification)
LMS (Lift Monitoring System)
*16*
#
Destination phone number for
LMS
Telephone number of the alarm
receiver for monitoring.
*30*
0 or 3 #
LMS message type
The protocol for elevator monitoring
(LMS).
0 = P100
3 = CPC (Battery alarm only)
*39*
0 or 1 #
Message repetition
LMS messages (faulty battery, bus unit
or button) are sent either only once
upon the first occurrence (parameter
set to 0 = default) or repeated every
24 hours (parameter set to 1).
*84*
0 to 2 #
Message via emergency call
Select which message(s) will be sent
to the recipient in the event of an
emergency call.
0 = none (default)
1 = Emergency call start
2 = Emergency call start and end