GT-600/GT-800 Instruction Manual
42
AUTO Test (GT-800 only)
This is most common used test mode as it leads the operator through the whole
test procedure. There are 13 factory-programmed Auto-Tests and free space for
additional 17 customer-created ones.
Factory-programmed Auto-Tests for class I appliances (GERMAN REGION)
(listed figures present limit values in each test)
Tests
145 146 147 148 149 150 151 160 161
Visual
Inspection
Yes Yes Yes Yes Yes Yes Yes Yes Yes
Protective bonding
resistance 200 mA (
)
0.30
-
0.30
0.30
0.30
- - - -
Protective bonding
resistance 5 A (
)
- 0.3 - - - 0.3
1.00 - -
Insulation resistance 500 V
(M
)
1.00
1.00
0.30
-
- 1.00 1.00 1.00
1.00
Substitute leakage current
(mA)
- - 3.50
- - 3.50
3.50 - -
Protective conductor
current (mA)
3.50
3.50
- 3.50
3.50
- - 3.50
3.50
Touch
current
(mA)
- - - - 0.50
- - - 0.50
Apparent
power
(kVA) 3.7
3.7
- 3.7
3.7
- - 3.7
3.7
Factory-programmed Auto-Tests for class II appliances (GERMAN REGION)
(listed figures present limit values in each test)
Tests
241 242 243 244
Visual
Inspection
Yes Yes Yes Yes
Protective bonding
resistance 200 mA (
)
- - - -
Protective bonding
resistance 5 A (
)
- - - -
Insulation resistance 500 V
(M
)
2.00
2.00
- -
Substitute leakage current
(mA)
- 0.50
- -
Protective conductor
current (mA)
- - -
0.50
Touch current (mA)
0.50
-
0.50
-
Apparent power (kVA)
3.7
-
3.7
3.7