BECS BECSys5 Скачать руководство пользователя страница 24

 

Page 20 

  

 

  

www.becs.com

 

9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132

 

Operation and Maintenance Manual 

Rev: L13 

A – 8.4:  Date, Time & Units 

Once you have entered System Configuration, 

select Date, Time & Units from the menu. Here 
you can enter the values for the following:

 

 

Units (Op):  

Here you can choose from U.S. or 

Metric measurements. 

 

Date Format (Op):  

Here you can choose the 

format for the date. 

 

Current Date (Op):  

Here you can set the current 

date. 

 

Current Time (Op):

  Here you can set the 

current time. Use the + / - key to toggle between 

AM and PM. 

 

A – 8.5:  User Setup 

Once you have entered System Configuration, 
select User Setup from the menu. Here you can 

enter the access codes for Operators and 
Managers. You can enter 6 codes for Operators 

and 2 codes for Managers.   

 

See the section on Access Codes for more 

information. 
 

A – 8.6:  Display Options 

Once you have entered System Configuration, 

select Display Options from the menu.  

 

Page Delay (Op): 

 Here you can set the delay for 

scrolling to the next page in the normal display. 
These screens will only scroll when not in a menu 

screen. 

 

Backlight Delay (Op):

 

Only shown if the LCD 

display with the white backlight display is installed and one 
of the two-state backlight modes is used.

  When a key is 

pressed, delay this amount of time before dimming 
or shutting off the backlight. 

 

Toggle LCD Mode (Op):

  Toggles the LCD 

display between negative and positive modes. 

 
 

A – 9:  VFD Turndowns 

VFD Turndowns allow you to trigger or cancel 
manual turndowns (must have a manual turndown 

enabled for this menu to appear).  This will also 
display the next scheduled turndown. 

 

A – 10:  4-20mA Outs 

The 4-20mA output board allows you to connect to 
either a building management system or to control a 

VFD. 
If you have a 4-20 mA board installed in your system 

you may choose 4-20mA outputs from the main 
menu.  By selecting one of the 4-20mA output 

channels you will be able to select the following: 

 

Usage (Mgr):

  Selects what to use the selected 4-

20mA output channel for.   

 

Recorder Out:  

Output a 4-20mA signal based 

on one of the controller’s inputs, feed set points, 
or alarm set points.  Once you have selected 

Recorder Out, you will need to then select the 
Source (see below).

 

 

VFD Control Out:

  Use this channel to control 

a VFD unit connected to the recirculation 

pump.

 

 

Disable:

  Disables the 4-20mA output. 

 

Source (Mgr):

 

Only shown if the usage is set to Recorder 

Out.  

Configures the recorder out's signal source.  

This is broken up into four different categories to 
make selection of the source easier.  Select the 

Recorder Out's source from one of the following 
lists: 

 

Inputs:

  Lists all enabled inputs compatible for 

outputting on the selected 4-20mA output 

channel. 

 

Feed Set Points:

  Lists all enabled controls 

using feed set points.  Note that some feeds 
have more than one set point to control to.  If 

a control's feed point is selected, the output 
signal will be whatever value that feed is 

controlling to. 

 

High Alarm Set Points:

  Lists all available 

high alarm set points for use as the source. 

 

Low Alarm Setpoints:

  Lists all available low 

alarm set points for use as the source. 

 

Disable:

 Disables the recorder out. 

 

20 ma value (Mgr):

 

Only shown if usage is set to 

Recorder Out. 

Enter the value which the recorder 

will output 20 mA for.   

 

4 ma value (Mgr):

 

Only shown if usage is set to 

Recorder Out. 

Enter the value which the recorder 

will output 4 mA for.   

 
Example: Source: ORP input, 4 mA value = 600 

mV, 20 mA value = 900 mV.  ORP values 
between 600 and 900 mV are lineally scaled 

between 4 and 20 mA as shown below. 
 

 

0

4

8

12

16

20

24

500

600

700

800

900

1000

ORP (mV)

out

put

 (

m

A

)

Содержание BECSys5

Страница 1: ...Operation and Maintenance Manual ...

Страница 2: ......

Страница 3: ...l 11 A 5 3 Chlorine Booster Control 13 A 5 4 Super Chlorination 13 A 5 5 Dechlorination 14 A 5 6 Ozone Control 14 A 5 7 Heater 14 A 5 8 Autofill 15 A 5 9 TDS Control 15 A 5 10 Sensor Wash 15 A 5 11 Enzyme 15 A 5 12 UV Turndown 15 A 5 13 Polymer 16 A 5 14 Recirculation Pump 16 A 5 9 1 VFD Control 16 A 5 15 Alarm Relay 16 A 6 Control Options 17 A 6 1 Flow Restored Feed Delay 17 A 6 2 Power Saver 17 ...

Страница 4: ......

Страница 5: ...ance Manual Rev L13 Warnings Pay particular attention to the following warnings encountered while utilizing your BECSys5 Water Chemistry Controller Caution Various caution boxes may be found throughout the manual text Warning Various other warning boxes may be found throughout the manual text ...

Страница 6: ...ntal specifications from being exceeded see table below Environmental Specifications Specification Rating Storage Temperature 40 to 85 Deg C Ambient Operating Temperature 18 to 50 Deg C Ambient Humidity 95 non condensing maximum humidity Electrical Specifications The BECSys5 may be ordered in either an 115VAC model or a 230VAC model Following are the electrical specifications for each model Contro...

Страница 7: ... 14 0 pH ORP 1500mV to 1500mV Temperature 32 F to 212 F 0 C to 100 C Reed Flow Switch Switch Point On 2 0 gpm Rotary Flow Switch Switch Point On 1 5 gpm Optional Sensors Amperometric ppm 0 ppm to 20 ppm Total Chlorine 0 ppm to 20 ppm Pressure Transducer 0 to 100 PSI Vacuum Transducer 14 7 to 85 PSI Vacuum Swichgage 0 30 in HG Pressure Swichgage 0 50 PSI Differential Swichgage 0 50 PSI Conductivity...

Страница 8: ...the Operators A 2 3 Controller Options Depending on how a particular controller is configured not all of the options listed in this manual may be available A 3 Navigating the menus The controller s menus incorporate built in help text to aid in understanding the function of each parameter item and option A 3 1 Common status messages The very bottom line of the display contains the time and date on...

Страница 9: ...esult in an error beep and the message Bad Value Retry being displayed in the status area For some values certain keys may take on special functions that are explained in the lower lines of the screen The Down up message in the example above is one of them A 3 2 2 List Screens The list screens are mainly composed of lists of menu items that you can choose from by either pressing an item s number o...

Страница 10: ... enter the program menu press the Menu button on the front face panel of your controller This will allow the viewing of the Main Menu where the programming options are displayed The Cl inputs Cl Inventory Input Chlorine Control and Chlorine booster control are all displayed as either Chlorine and Cl or Bromine and Br depending on the chemical selected in the Cl feed menu This manual is written usi...

Страница 11: ...ill have the following options High Alarm Op The high alarm will activate when the total Cl reaches or rises above this setting You may disable this alarm by holding down the key for 1 second Low Alarm Op The low alarm will activate when the total Cl reaches or falls below this setting You may disable this alarm by holding down the key for 1 second Alarm Hysteresis Mgr This value sets the amount t...

Страница 12: ... the level that the turbidity reading has to rise above the high alarm setting before the alarm will shut off A 4 9 Surge Pit Level If your controller is configured to monitor the Surge Pit Level a sensor may be used or a contact switch If a sensor is used you will have the following options High Alarm Op The high alarm will activate when the input reaches or rises above this setting You may disab...

Страница 13: ...uum either a transducer or a gauge may be used If a transducer is used you will have the following options High Vac Alarm Op The high vacuum alarm will activate when the pressure reaches or falls below this setting This is actually a low pressure alarm that operates in the negative pressure range which is a vacuum You may disable this alarm by holding down the key for 1 second If the recirc pump i...

Страница 14: ...ed pH set point Span Prop Bnd Op This option is only shown if the Control Type is Time Base Proportional This value sets the distance or span from the set point that the output will be proportionally controlled Time Base Op This option is only shown if the Control Type is Time Base Proportional This sets the total time that control is based on During this time the feeder will turn on for a percent...

Страница 15: ... activate the chemical feeder whenever the ORP falls below the set point and will feed for a percentage of the Time Base default one minute proportional to the offset from set point For the remainder of the Time Base the feeder will be paused The feeder will continue this feed and pause cycle until the controller achieves the set point plus hysteresis The closer to set point the less time the feed...

Страница 16: ...every day the alternate set point should be used Once you make your selection you will be returned to the 4Event 28Day Timer menu where you will have a new menu item Event 1 Times Select the Event1 Times from the 4Event 28Day Timer menu This screen allows you to set both the start time and the end time for the event s programmed weeks days To toggle AM PM press the key while the cursor is on the t...

Страница 17: ...e face panel and display a message to alert the operator If in TBP Pause mode the controller will reset the timer An operator must reset the failsafe through the Reset Fail Safe button to re enable normal control A 5 4 Super Chlorination If your controller is configured for Super Chlorination you will have the following options Control Input Op This option is only available if the free Cl probe is...

Страница 18: ... if the free Cl probe is installed Choose between free Cl ORP or both to use to control the Ozone feed ORP Set Point Op This option is only shown if the Control Input is ORP or Both This value sets the ORP level that the input must drop below to activate the Ozone Free Cl Set Point Op This option is only shown if the Control Input is free Cl or Both This value sets the free Cl level that the input...

Страница 19: ... controller will cut power to the relay flash the Reset Fail Safe LED on the face panel and display a message to alert the operator An operator must reset the failsafe through the Reset Fail safe button to re enable normal control A 5 10 Sensor Wash If your controller is set up to do a Sensor Wash you will have the following options 4 Event 28 Day Timer Op Once you have entered Sensor Wash select ...

Страница 20: ...e following options Pres Alarm Delay Op Delay pressure and vacuum alarms from triggering for this amount of time whenever the recirc pump starts up Heater Fireman Switch Op This option is only shown if a relay is assigned to the Heater control This value sets the minimum amount of time to leave the recirculation pump on or delay the start of backwash after the heater shuts off Ozone Fireman Switch...

Страница 21: ...the wake up time expires if the Power Saver timer expired the system will remain awake even if all feeds are satisfied Otherwise the system enters the CONTROLLING state performing a backwash if triggered and will reenter GOING TO SLEEP again once all feeds have been satisfied again While Power Saver is active the system automatically uses the Alternate Temperature set point for the Heater and the ...

Страница 22: ...DHCP is enabled the controller will retrieve its IP address information from a DHCP server on the network If DHCP is disabled the IP address information must be set manually via the remaining items listed here IP Address Mgr This option is only shown if DHCP is disabled Sets the controllers IP address IP Netmask Mgr This option is only shown if DHCP is disabled Sets the controllers IP netmask IP D...

Страница 23: ...email Enter the recipients email address Enter the local part of the email address the part before the into the first screen then enter the domain part of the email address the part after the into the second screen Email address text message This option is only shown if the call out type is set to text message The recipients email address for text messaging is usually in the form of the pager s or...

Страница 24: ...ent system or to control a VFD If you have a 4 20 mA board installed in your system you may choose 4 20mA outputs from the main menu By selecting one of the 4 20mA output channels you will be able to select the following Usage Mgr Selects what to use the selected 4 20mA output channel for Recorder Out Output a 4 20mA signal based on one of the controller s inputs feed set points or alarm set point...

Страница 25: ...o enter the menus or set any values under the quick set keys The controller automatically displays the access screen whenever a user does not have a high enough access level to enter a specific screen To enter an Operator access code press 1 To enter a Manager access code press 2 If at anytime you wish to logon as another access level you may do so by pressing the Menu key and selecting Logon from...

Страница 26: ... than there is room for the controller the controller will page through them until they all have been displayed then start over Pressing the right arrow key Next will display the next page Pressing the Lock Screen button will prevent the controller from paging the screen to show more inputs alarms and other status information You can adjust the rate at which the controller pages by pressing the up...

Страница 27: ...r showing what is assigned to those relays and their current state By selecting one of the assigned relays you are allowed to choose between automatic manual on or manual off Unused relays and the alarm relay cannot be manually overridden but their current state is always displayed If Manual On is selected you will be prompted to enter how long the relay can stay in Manual On before returning to A...

Страница 28: ...ssed provides the following information and options Lists any active failsafe alarms and provides the option to reset them A failsafe alarm is generally triggered when one of the relays has remained on past the set time the function has been given to reach its set point By choosing to reset the failsafe the control that triggered the failsafe will be able to resume operating normally once again Di...

Страница 29: ...ell clean it as in routine maintenance then store it in the wetting cap using a pH 4 buffer saturated with potassium chloride KCl The potassium chloride will prevent electrolyte from leaching out of the sensors reference cell The wetting cap only needs to be half full If a number of sites are going to be serviced for example at the end of a season then it might be a good idea to carry a pint of 4 ...

Страница 30: ...damage to the membrane Clean the electrode finger using a clean dry paper towel The special abrasive paper is used on just the electrode tip Place the special abrasive paper on a paper towel and hold it at one corner Hold the probe perpendicular to the paper towel and abrasive paper and rub the electrode tip two or three times across the abrasive paper Once the tip has been cleaned replace the ele...

Страница 31: ... use of a DPD test kit D 4 Conductivity Sensor D 4 1 Cleaning The sensor should be kept as clean as possible for optimum measurement accuracy The frequency of cleaning will depend upon the application When necessary wash with strong detergent something similar to Dawn liquid detergent and warm water using a pipe cleaner or small soft brush for most fouling Rinse with tap water to completely remove...

Страница 32: ...ntity of Bicarbonate of Soda Needed to Raise Total Alkalinity Desired Increase In ppm Gallons in Spa 100 150 250 500 750 1000 10 1 25 ts 2 00 ts 4 00 ts 2 50 tb 0 25 cp 0 33 cp 20 1 00 tb 1 50 tb 2 50 tb 5 00 tb 0 50 cp 0 50 cp 30 1 50 tb 2 00 tb 3 50 tb 0 50 cp 0 67 cp 1 00 cp 40 2 00 tb 3 00 tb 0 33 cp 0 50 cp 1 00 cp 1 00 cp 50 2 50 tb 3 50 tb 6 00 tb 0 75 cp 1 00 cp 1 50 cp 60 3 00 tb 0 25 tb ...

Страница 33: ...00 00 lb 900 00 lb 1200 00 lb 90 13 50 lb 33 75 lb 67 50 lb 101 25 lb 135 00 lb 270 00 lb 675 00 lb 1012 50 lb 1350 00 lb 100 15 00 lb 37 50 lb 75 00 lb 112 50 lb 150 00 lb 300 00 lb 750 00 lb 1125 00 lb 1500 00 lb lb pounds of dry chemical Quantity of Calcium Chloride Needed to Increase Calcium Hardness Desired Increase In ppm Gallons in Pool 10 000 25 000 50 000 75 000 100 000 200 000 500 000 75...

Страница 34: ...ducer only no cable range 14 7 to 85 PSI 9660019 Vacuum Swichgage range 0 to 30 in HG 9660020 Pressure Swichgage range 0 50 PSI 8660021 Differential Swichgage range 0 50 PSI Conductivity TDS 9660012 BECSys Conductivity Sensor range 0 to 20 000 micromho Turbidimeter 1210261 BECSys Turbidimeter range 0 to 20 00 NTU 9680024 Dessicant Tray Refill Flowmeters 8660008 Flowmeter 1 2 to 4 range 0 to 655 35...

Страница 35: ...0201 2 Sensor Rectangular Flow Cell Body 1220200 Acrylic Cover for 2 Sensor Rectangular Flow Cell 8060669 O Ring for 2 Sensor Rectangular Flow Cell 1220288 3 Sensor Rectangular Flow Cell Body 1220287 Acrylic Cover for 3 Sensor Rectangular Flow Cell 8060695 O Ring for 3 Sensor Rectangular Flow Cell Common Flow Cell Components 8060189 Screws Acrylic Cover 8060623 Elbow 90 PVC 8060624 Elbow 45 PVC 80...

Страница 36: ...have the sole right to determine whether to repair or replace a product BECS will not be responsible for any expense associated with installation of repaired or replacement parts LIMITATIONS AND EXCLUSIONS This is a LIMITED WARRANTY BECS makes NO WARRANTIES other than those contained herein The LIMITED WARRANTY replaces and is in lieu of any WARRANTIES of MERCHANTABILITY or of FITNESS FOR A PARTIC...

Страница 37: ...g the industry s most reliable water chemistry controller for over 20 years Our 24 000 ft2 facility in Saint Louis Missouri is home to an exceptional design team and all manufacturing is performed onsite at this facility where we can personally assure the quality of our products The BECS commitment to excellence drives the most innovative new products and unparalleled customer service ...

Отзывы: