Operation and Maintenance Manual
Rev: L13
A – 6: Control Options
A – 6.1: Flow Restored Feed Delay
Enable / Disable (Op):
Once you have entered
the Flow Restored Feed Delay option, select
Enable / Disable from the menu. Here you will be
able to select whether you want to delay the
chemical feeders after flow is restored to the
system.
Delay Duration (Op):
This option is only available if
flow restored feed delay is enabled.
Enter the desired
time that the chemical feeders must wait to operate
after flow is restored.
A – 6.2: Power Saver
Power Saver is a timer triggered function that
saves energy by shutting down the recirculation
pump for programmable periods of time while the
pool is not in use.
When active, power saver has the following states:
CONTROLLING: At least one control
function is currently feeding. Once all feeds
have finished, the system will enter the
GOING TO SLEEP state.
GOING TO SLEEP: All control functions
must be satisfied (they don't turn their feeds
on) for the Enter Sleep Delay duration before
allowing system to enter the SLEEPING
state.
SLEEPING: Timed period (Sleep Duration)
where the shutdown of recirculation pump is
triggered and all feeds are disabled. After
entering SLEEPING state, the recirculation
pump will continue to run until the heater and
ozone fireman switch timers run out. The
sleep timer starts when all conditions have
been met, not when controller shuts down the
recirculation pump. Only a timer triggered
backwash, the sleep timer expiring, or the
Power Saver timer expiring will put the
system into the WAKING UP state. No
feeds or input alarms will operate while the
system is asleep or waking up.
WAKING UP: Timed period (Exit Sleep
Delay) where the recirculation pump is ran
before allowing feeds to operate. Once the
wake up time expires, if the Power Saver
timer expired, the system will remain awake
even if all feeds are satisfied. Otherwise the
system enters the CONTROLLING state,
performing a backwash if triggered, and will
reenter GOING TO SLEEP again once all
feeds have been satisfied again.
While Power Saver is active, the system
automatically uses the Alternate Temperature
set point for the Heater and the Alternate
ORP and/or Alternate ppm set points for the
Cl feed.
Enable (Op):
Enable or disable the Power Saver
feature.
4 Event 28 Day Timer (Op):
The 4 Event 28
Day Timer
allows you to program power saver's
schedule. See the section on the Chlorine
(Bromine) Control's Alt Set Point for details on
how to set this.
Sleep Duration (Op):
Sets how long the
controller will sleep.
Enter Sleep Delay (Op):
Sets how long to wait
after all of the feeds have been satisfied before
entering SLEEP (i.e. the GOING TO SLEEP
duration). If any feed starts feeding during this
time, the controller goes back to the
CONTROLLING state.
Exit Sleep Delay (Op):
Sets how long to wait
after coming out of sleep before allowing any
feeds to run. (i.e. the WAKING UP duration).
Alternate ORP (Op):
Sets the alternate ORP
value used during power saver and the Cl feed's
alternate set point event timer.
Alternate free Cl (Op):
Sets the alternate free Cl
value used during power saver and the Cl feed's
alternate set point event timer.
Alternate temp (Op):
Sets the alternate
temperature value used during power saver and the
heater's alternate set point event timer.
A – 6.3: pH Lockout
pH lockout (Manager) disables the sanitizer feed
when a pH high and/or low alarm is activated:
Full lockout: The Cl (Br) feed is disabled
when either a pH high or low
alarm occurs.
Feed direction: For pH feed up, the Cl (Br)
feed is disabled on a pH low
alarm.
For pH feed down, the Cl (Br)
feed is disabled on a pH high
alarm.
Disable:
pH alarms do not disable the
Cl (Br) feed. (
Not
Recommended
)
Warning: Disabling the pH lockout will allow
for chemical overfeeds which may damage
equipment or harm patrons.