Page 14
www.becs.com
9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132
Operation and Maintenance Manual
Rev: L13
A – 5.4: Super Chlorination (continued)
Maximum Time On (Op):
This value sets the
maximum time you want the Super Chlorination
on to reach the set point. If the time expires
before set point is reached, the controller will
trigger the SuperChlor failsafe alarm and end the
SuperChlor feeds. (the range is from 0:00 to
18:00 hours)
An operator can reset the failsafe through the
Reset Fail/Safe button; however the failsafe
alarm will automatically clear itself when the
regular Cl feed begins feeding.
ORP Set Point (Op):
This option is only shown if the
Control Input is set to ORP.
This value sets the
desired ORP level to shock the pool.
Free Cl Set Point (Op):
This option is only shown if
the Control Input is set to free Cl.
This value sets the
desired free Cl level to shock the pool.
A – 5.5: Dechlorination
If your controller is configured for Dechlorination,
you will have the following options:
Control Input (Op):
This option is only available if
the free Cl probe is installed.
Choose between free Cl
and ORP to use to control the dechlor feed.
Follow Super Chlorination (Op):
Choose
whether or not you want your dechlorination to
automatically follow your super chlorination.
4 Event 28 Day Timer (Op):
The 4 Event 28
Day Timer
allows you to program the
dechlorination on a schedule. See the section on
Super Chlorination's 4 Event 28 Day Timer for
details on how to set this.
Maximum Time On (Op):
This value sets the
maximum time you want the dechlorination on to
reach the set point. (the range is from 0:00 to
18:00 hours)
ORP Set Point (Op):
This option is only shown if the
Control Input is set to ORP.
This value sets the
desired final ORP level.
Free Cl Set Point (Op):
This option is only shown if
the Control Input is set to free Cl.
This value sets the
desired final free Cl level.
A – 5.6: Ozone Control
If your controller is configured for Ozone Control,
you will have the following options:
Control Input (Op):
This option is only available if
the free Cl probe is installed.
Choose between free Cl,
ORP, or both to use to control the Ozone feed.
ORP Set Point (Op):
This option is only shown if the
Control Input is ORP or Both.
This value sets the
ORP level that the input must drop below to
activate the Ozone.
Free Cl Set Point (Op):
This option is only shown if
the Control Input is free Cl or Both.
This value sets the
free Cl level that the input must drop below to
activate the Ozone.
Fireman Switch (Op):
This option is only shown if a
relay is assigned to the recirculation pump or backwash.
This value sets the minimum amount of time to
leave the recirculation pump on or delay the start
of backwash after the Ozone relay shuts off.
Failsafe Timer (Op):
This value sets the time
that the relay is allowed to stay continuously on.
A – 5.7: Heater
If your controller is configured for Heater Control,
you will have the following options:
Temp. Ctrl Enable (Op):
Enables or disables
controlling the Heater using the Temperature
Input.
Set Point (Op):
Only shown if Temp. Ctrl is enabled.
This value sets the desired temperature. (the
range is from the temperature low alarm to the
temperature high alarm)
Failsafe Timer (Op):
Only shown if Temp. Ctrl is
enabled.
This value sets the time that the relay is
allowed to stay on without reaching set point
before the relay is locked out. If the heater has
been trying to achieve set point without success
for the selected time, the controller will cut power
to the heater, flash the Reset Fail/Safe LED on
the face panel and display a message to alert the
operator.
An operator must reset the failsafe through
the Reset Fail/safe button to re-enable normal
control.
Fireman Switch (Op):
This option is only shown if a
relay is assigned to the recirculation pump or backwash.
This value sets the minimum amount of time to
leave the recirculation pump on or delay the start
of backwash after the heater relay shuts off.
Alternate Temperature (Op):
Only shown if Temp.
Ctrl is enabled.
The 4 Event 28 Day Timer
allows
you to program an alternate set point on a
schedule. See the Chlorine (Bromine) Control's
Alt Set Point for details on how to set this.
After the schedule is set, you may choose the
alternate temperature set point option and enter
the desired setting.