Configuration and Settings – 3
3–3
Nm Frequency:
Nm Voltage: 120
Nm Current: 5.00
59/27 Mag Select:
Phase Rotation:
OK LED Flash:
Control Number: 0
User Logo: Beckwith Electric Co.
M-3410
(50 to 500 V)
(0.50 to 6.00 A)
Configuration
60 Hz
50 Hz
RMS
DFT
Enable
Disable
ABC
ACB
Figure 3-2
M-3811A IPScom
®
for Palm OS
®
Configuration Screen #1
VT Config:
CT Secondary Rating:
VT Phase Ratio: 1.0
:1
(1.0 to 6550.0)
VT Neutral Ratio: 1.0
:1
(1.0 to 6550.0)
CT Phase Ratio: 10
:1
(1 to 65500)
Delta-Y Transform:
Configuration
L-G
L-L LG-LL
Enable
Disable
5A
1A
Figure 3-3
M-3811A IPScom for Palm OS
Configuration Screen #2
Input Active State:
Configuration
1
2
Open
Close
Open
Close
Normal
Latching
Output
Contact
Mode:
1
2
Normal
Latching
Relay Seal-In Time:
Out1: 30
(2 to 8160 Cycles)
Out 2: 30
(2 to 8160 Cycles)
Output
Relay
(Actuate):
Energize
Deenergize (FS)
Energize
Deenergize (FS)
Figure 3-4
M-3811A IPScom for Palm OS
Configuration Screen #3
Path
: M-3811A/Setup/Configuration
COMMANDS: CONFIGURATION/ACTION/...
Send
This command sends the individual
setpoint/setting contained in the
handheld edit buffer to the relay. The
difference between the Send command
and the Download command is that the
Download command sends (overwrites)
the entire data record file that exists on
the relay.
Receive
This command reads the individual
setpoint/setting from the relay into the
handheld edit buffer. The difference
between the Receive command and the
Upload command is that the Upload
command receives (overwrites) the
entire data record file that exists on the
handheld unit.
Save
This command saves the individual
setpoint/setting from the handheld edit
buffer to the handheld data record. A
successful Save operation will result in
a Save confirmation.
Retrieve
This command loads the setpoint/setting
values that correspond to the displayed
edit screen from the handheld data
record into the handheld edit buffer.
Load Default
The Load Default command loads the
default setpoint/setting values into the
handheld edit buffer, and displays on
the current screen.
Done
This command returns the user to the
handheld Main screen.
■
■
■
■
■
NOTES:
The “active” or asserted states for the
individual status inputs are:
1.
Selected Closed causes the “active” or
“operated” condition to be initiated by
the external contact
closing.
2.
Selecting Open causes the “active” or
“operated” condition to be initiated by
the external contact
opening.
Содержание Syncrocloser M-3410A
Страница 1: ...Instruction Book M 3410A Intertie Generator Protection Relay ...
Страница 39: ...xiv M 3410A Instruction Book This Page Left Intentionally Blank ...
Страница 71: ...M 3410A Instruction Book 2 28 This Page Left Intentionally Blank ...
Страница 121: ...M 3410A Instruction Book 3 50 This Page Left Intentionally Blank ...
Страница 161: ...1 3 A B C M 3410A Instruction Book 4 40 This Page Left Intentionally Blank ...
Страница 223: ...M 3410A Instruction Book F 2 This Page Left Intentionally Blank ...