M-3410A Instruction Book
4–2
An optional 10 foot null modem cable (M-0423) is
available from the factory, for direct connection
between a PC and the relay’s front panel COM1
port, or the rear COM2 port.
When fabricating communication cables, every effort
should be made to keep cabling as short as
possible. Low capacitance cable is recommended.
The RS-232 standard specifies a maximum cable
length of 50 feet for RS-232 connections. If over 50
feet of cable length is required, other technologies
should be investigated, such as RS-485 or fiber
optics.
4.2
Activating Communications
After the relay has been set up, the modems
initialized, and IPScom
®
installed, communication
is activated as follows:
M-3810A IPScom for Windows™
1.
Select the IPScom icon from the
Becoware folder.
2.
The IPScom splash screen is displayed
briefly, providing the software version
number and copyright information. This
information is also available by choosing
the
About
... command from the
Help
menu.
3.
Choose the
Comm
menu selection.
Complete the appropriate information in
the window for the relay to be addressed.
a.
If communication is through a
modem, choose the
Modem
command to expand the com-
munications dialog box. Choose the
desired relay location, then select
Dial
. This action establishes contact
and automatically opens com-
munication to the relay.
b.
If the computer is directly connected
to the relay through either COM1 or
COM2, select
Open COM
. This
action establishes communications.
4.
Enter any valid IPScom command(s) as
desired.
5.
To end communication when
communicating by modem, choose the
Hang Up
command from the expanded
Communication dialog box. To close the
communication channel when connected
locally, choose the
Close COM
command.
M-3811A IPScom for Palm OS
®
1.
Select the BECO M-3811A icon from
the handheld desktop.
2.
Select
Connect
from the IPScom for
Palm OS
Main Screen
Figure 4-33.
IPScom will display the
Connect
dialog
screen Figure 4-35.
3.
The user is prompted to select the
Baud
Rate
,
Parity
and
Stop Bits
and then
input the individual M-3410A
Address
(1 to 247) and
Communication Access
Code
(0 to 9999). A
Communication
Access Code
of 9999 is the default
value.
4.
If
OK
is selected, and the correct
Connect
information has been entered
the relay will respond with a confirmation
screen (Figure 4-38).
5.
If
OK
is selected, and the incorrect
Connect
information has been entered
the relay will respond with a Security
error screen (Figure 4-36).
6.
All IPScom for Palm OS features are
available to the user. The user may
disconnect from the M-3410A at anytime.
However, the Monitor, Upload and
Download features are only available
when connected to the M-3410A.
Содержание Syncrocloser M-3410A
Страница 1: ...Instruction Book M 3410A Intertie Generator Protection Relay ...
Страница 39: ...xiv M 3410A Instruction Book This Page Left Intentionally Blank ...
Страница 71: ...M 3410A Instruction Book 2 28 This Page Left Intentionally Blank ...
Страница 121: ...M 3410A Instruction Book 3 50 This Page Left Intentionally Blank ...
Страница 161: ...1 3 A B C M 3410A Instruction Book 4 40 This Page Left Intentionally Blank ...
Страница 223: ...M 3410A Instruction Book F 2 This Page Left Intentionally Blank ...