M-3410A Instruction Book
5–10
6.
Sync Check Time Delay Test
: Apply Nominal Voltage to V1 and V2, and establish a phase angle
difference of more than
PA
+5°. With the output contacts connected to a timer, remove the phase
angle difference and start timing. The contacts will close after
SD
cycles within
&
2 cycles.
7.
Delta Voltage Test
: Set the Upper and Lower Voltage limits to their maximum and minimum
values, respectively. Set V2 to 140 V and V1 to 80 V. Hold the
TARGET RESET
button in and
slowly increase the voltage on V1 until Output
Z
LED operates, or the pickup indicator operates on
the computer target screen. The voltage difference should be equal to
&
0.5 V or
&
5%. Release
the
TARGET RESET
button, and decrease the voltage, the
OUTPUT
LED will extinguish. If
desired, repeat the test using V2 with V1 at 140 volts.
8.
Delta Frequency Test
: Set V1 and V2 to Nominal Voltage, and set the frequency of V1 to 0.05 Hz
lower than Nominal Frequency and V2 at Nominal Frequency. Hold the
TARGET RESET
button
in, and slowly increase the frequency of V1 until Output
Z
LED operates, or the pickup indicator
operates on the computer target screen. The frequency difference level should be equal to
ΔΔΔΔΔ
F
&
0.001 Hz or 5%. Release the
TARGET RESET
button and decrease the frequency, the
OUTPUT
LED will extinguish. If desired, repeat the test using V2 with V1 at Nominal Frequency.
9.
Dead Volt Limit Test
:
Dead V1 & Hot V2 Test
: Enable Dead V1 & Hot V2 and disable Dead V2 & Hot V1 (if enabled). Set
V2 to Nominal Voltage, and V1 to
DVL
+5 V. Hold the
TARGET RESET
button in, and slowly
decrease the voltage on V1 until Output
Z
LED operates, or the pickup indicator operates on the
computer target screen. The voltage level should be equal to
DVL
&
0.5 V or
&
5%. Release the
TARGET RESET
button and increase the voltage level, the
OUTPUT
LED will extinguish.
Set V1 to Nominal Voltage, and decrease V2 below
DVL
and verify that the function does not
operate.
Dead V2 & Hot V1 Test
: Enable Dead V2 & Hot V1 and disable Dead V1 & Hot V2 (if enabled). Set
V1 to Nominal Voltage, and V2 to
DVL
+5 V. Hold the
TARGET RESET
button in, and slowly
decrease the voltage on V2 until Output
Z
LED operates, or the pickup indicator operates on the
computer target screen. The voltage level should be equal to
DVL
&
0.5 V or
&
5%. Release the
TARGET RESET
button and increase the voltage level and the
OUTPUT
LED will extinguish.
Set V2 to Nominal Voltage, and decrease V1 below
DVL
, and verify that the function does not
operate.
Dead V1 and Dead V2 Test
: Enable Dead V1 & Dead V2 . Disable Dead V1 & Hot V2 and Dead
V2 & Hot V1, if enabled. Set V1 and V2 to
DVL
+5 V. Hold the
TARGET RESET
button in, and
slowly decrease the voltage on V1 and V2 until Output
Z
LED operates, or the pickup indicator
operates on the computer target screen. The voltage level should be equal to
DVL
&
0.5 V or
&
5%. Release the
TARGET RESET
button and increase the voltage level, the
OUTPUT
LED will
extinguish.
Set V1 to Nominal Voltage, decrease V2 below
DVL
, and verify that the function does not operate.
Set V2 to Nominal Voltage, decrease V1 below
DVL
, and verify that the function does not operate.
10.
Dead Input Initiate Test
: Select one of the Dead Inputs (
DIN
) and activate it. Repeat step 9,
verify that the function operates as in step 9. Deactivate the
DIN
and repeat step 9 once more.
Verify that the function does not operate. Disable Dead Input feature when this step is complete.
11.
Dead Timer Test
: Enable Dead V1 & Dead V2. Disable Dead V1 & Hot V2 and Dead V2 & Hot V1
(if enabled). Set V1 and V2 to
DVL
+5 V. With output contacts connected to a timer, remove V1
and V2 and start timing. The contacts will close within
&
2 cycles.
12.
If testing is complete, enable any functions disabled for this test. If further testing is desired,
check the proper functions to disable for the next test and continue from this point.
Содержание Syncrocloser M-3410A
Страница 1: ...Instruction Book M 3410A Intertie Generator Protection Relay ...
Страница 39: ...xiv M 3410A Instruction Book This Page Left Intentionally Blank ...
Страница 71: ...M 3410A Instruction Book 2 28 This Page Left Intentionally Blank ...
Страница 121: ...M 3410A Instruction Book 3 50 This Page Left Intentionally Blank ...
Страница 161: ...1 3 A B C M 3410A Instruction Book 4 40 This Page Left Intentionally Blank ...
Страница 223: ...M 3410A Instruction Book F 2 This Page Left Intentionally Blank ...