5–3
Testing – 5
Hot
Neutral
Voltage
Input 1
V
A
/V
AB
= 120 V ac
∠
0°
TB1-9
TB1-10
TB1-11
TB1-12
TB1-13
TB1-14
V
B
/V
BC
= 120 V ac
∠
–120°
V
C
/V
G
/V
sync
= 120 V ac
∠
120°
Hot
Neutral
Voltage
Input 2
Hot
Neutral
Voltage
Input 3
A
B
C
Figure 5-1
Voltage Inputs: Configuration V1
Q
NOTE
: Line-Ground and Line-Ground-to-Line-Line VT configuration uses V
A
, V
B
and V
C
inputs and L-L VT
configuration uses V
AB
, V
BC
, and V
sync
inputs.
I
A
∠
0°
TB2-22
Current Input 1
Polarity
Current Input 2
Current Input 3
I
B
∠
–120°
I
C
∠
120°
TB2-23
TB2-19
TB2-20
TB2-16
TB2-17
5A CT Configuration
I
A
∠
0°
TB2-21
Current Input 1
Polarity
Current Input 2
Current Input 3
I
B
∠
–120°
I
C
∠
120°
TB2-23
TB2-18
TB2-20
TB2-15
TB2-17
1A CT Configuration
Figure 5-2
Current Inputs: Configuration C1
Q
NOTE
: The phase angles shown here use leading angles as positive and lagging angles as negative.
Some manufacturers of test equipment have used lagging angles as positive, in which case
V
B
=120 V
s
120° and V
C
=120 V
s
240°. Similarly other voltage and current phase angles should
be adjusted. These test configurations are for ABC phase rotation. They must be adjusted
appropriately for ACB phase rotation.
Содержание Syncrocloser M-3410A
Страница 1: ...Instruction Book M 3410A Intertie Generator Protection Relay ...
Страница 39: ...xiv M 3410A Instruction Book This Page Left Intentionally Blank ...
Страница 71: ...M 3410A Instruction Book 2 28 This Page Left Intentionally Blank ...
Страница 121: ...M 3410A Instruction Book 3 50 This Page Left Intentionally Blank ...
Страница 161: ...1 3 A B C M 3410A Instruction Book 4 40 This Page Left Intentionally Blank ...
Страница 223: ...M 3410A Instruction Book F 2 This Page Left Intentionally Blank ...