Appendix F – Layup and Storage
F–1
Appendix F includes the recommended storage
parameters, periodic surveillance activities and layup
configuration for the M-3410A Intertie/Generator
Protection Relay.
Storage Requirements (Environment)
The recommended storage environment parameters
for the M-3410A are:
•
The ambient temperature where the
M-3410A is stored is within a range of 5°
C to 40° C
•
The maximum relative humidity is less
than or equal to 80% for temperatures up
to 31° C, decreasing to 31° C linearly to
50% for relative humidity at 40° C.
•
The storage area environment is free of
dust, corrosive gases, flammable
materials, dew, percolating water, rain and
solar radiation.
Storage Requirements (Periodic Surveillance
During Storage)
The M-3410A power supply contains electrolytic
capacitors. It is recommended that power be applied
to the relay every three to five years for a period of
not less than one hour to help prevent the electrolytic
capacitors from drying out.
F
Appendix – Layup and Storage
Layup Configuration
The M-3410A includes a removable lithium battery
(Beckwith Electric component B1, Figure 2-25).
The battery provides power to the M-3410A clock
and also provides power to the unit’s nonvolatile
memory when power is not applied to the unit.
Layup of the M-3410A requires removing the battery
which stops the system clock. The steps necessary
to remove the battery are as follows:
▲
▲
▲
▲
▲
CAUTION:
Personnel performing this procedure
should be trained in Electrostatic Discharge
prevention to prevent damage to ESD sensitive
components. Check and comply with appropriate
regulations regarding the disposal of lithium
batteries.
8
WARNING: Operating personnel must not
remove the cover or expose the printed circuit
board while power is applied. IN NO CASE may
the circuit-based jumpers be moved with power
applied.
1.
Remove the screws that retain the rear
cover, lift the rear cover off the relay.
2.
Remove the six screws that retain the
CPU board to the I/O board.
3.
Disconnect the CPU board from the I/O
board by pulling the board away from
the I/O board. Moderate force will be
needed to accomplish this.
4.
Remove the battery from the CPU board.
5.
Reinstall the CPU board onto the I/O
board by reversing the removal process.
6.
Insert the six screws that retain the
CPU board to the I/O board.
7.
Reinstall the rear cover on the relay;
insert the screws that retain the rear
cover.
Содержание Syncrocloser M-3410A
Страница 1: ...Instruction Book M 3410A Intertie Generator Protection Relay ...
Страница 39: ...xiv M 3410A Instruction Book This Page Left Intentionally Blank ...
Страница 71: ...M 3410A Instruction Book 2 28 This Page Left Intentionally Blank ...
Страница 121: ...M 3410A Instruction Book 3 50 This Page Left Intentionally Blank ...
Страница 161: ...1 3 A B C M 3410A Instruction Book 4 40 This Page Left Intentionally Blank ...
Страница 223: ...M 3410A Instruction Book F 2 This Page Left Intentionally Blank ...