Product Overview
KL3001, KL3002
11
Version: 4.2
2.2
Technical data
Technical Data
KL3001
KL3002
Number of inputs
1
2
Power supply for the electronics
via the K-Bus
Signal voltage
-10 V to +10 V
Technology
Differential input
Internal resistance
> 200 kΩ
Common-mode voltage U
CM
35 V max.
Resolution
12 bits (11 bits for the range between 0 V and 10 V)
Conversion time
~ 1 ms
~ 2 ms
Measuring error (total measuring
range)
< ±0.3 % of the full scale value
< ± 0.30 % (at 0 °C to +55 °C)
< ± 0.75 % (when the extended
temperature range is used)
Electrical isolation
500 V (K-Bus / signal voltage)
Current consumption from the K-bus
typically 65 mA
Bit width in the K-bus I/O
Input: 1 x 16 bits of data (1 x 8 bit
control/status optional)
Input: 2 x 16 bits of data (2 x 8 bit
control/status optional)
Configuration
No address or configuration settings
Weight
approx. 70 g
Dimensions (W x H x D)
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
on 35 mm mounting rail conforms to EN 60715
Permissible ambient temperature
range during operation
0 °C ... + 55°C
-25°C ... +60°C (extended
temperature range)
Permissible ambient temperature
range during storage
-25°C ... + 85°C
-40°C ... +85°C
Permissible relative air humidity
95%, no condensation
Vibration / shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27, see also
instructions for enhanced mechanical load capacity [
EMC immunity / emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protection class
IP20
Installation position
variable
Approval
CE, cULus,
CE, cULus,
2.3
Basic function principles
The analog input terminals KL3001 and KL3002 process signals in the range between -10 V and +10 V with
a resolution of 12 bits (4095 increments). The terminal inputs are differential inputs with common ground.
Due to the differential inputs, the terminals are particularly suitable for measuring earth free voltage drops.
Cross-currents caused by voltage differences at the input terminals do not lead to any appreciable
measurement distortion up to a difference in potential of 35 V (U
CM
= 35 V).
The green Run LEDs indicate the operating state of the associated terminal channel.
• On: Normal operation
• Off: Watchdog-timer overflow has occurred. If no process data are transmitted by the Bus Coupler for
100 ms, the green LEDs go out.
Process data output format
In the delivery state the process data are shown in two's complement form (integer -1 corresponds to
0xFFFF). Other presentation types can be selected via the feature register (
representation, Siemens output format).