Product Overview
KL3001, KL3002
12
Version: 4.2
Measured value
Output
dec
hex
-10 V
-32768
0x8000
-5 V
-16383
0xC001
0 V
0
0x0000
5 V
16383
0x3FFF
10 V
32767
0x7FFF
Calculation of process data
The terminal continuously takes measured values and stores the raw values of its A/D converter in register
(RAM ). The calculation of the correction with the calibration values takes place after each
sampling of the analog signal. This is followed by manufacturer and user scaling:
The process data that are transferred to the Bus Coupler are calculated using the following equations:
Y_a = (B_a + X_adc) * A_a
Y_aus = Y_a
(1.0)
Neither user nor manufacturer scaling is active.
Y_1 = B_h + A_h * Y_a
Y_aus = Y_1
(1.1)
Manufacturer scaling active: (Default setting)
Y_2 = B_w + A_w * Y_a
Y_aus = Y_2
(1.2)
User scaling active
Y_1 = B_h + A_h * Y_a
Y_2 = B_w + A_w * Y_1
Y_aus = Y_2
(1.3)
(1.4)
Manufacturer and user scaling active
Key
Name
Name
Register
X_adc
Output value of the A/D converter
-
Y_aus
Process data for controller
-
B_a
Vendor calibration: Offset
A_a
Vendor calibration: Gain
B_h
Manufacturer scaling: Offset
A_h
Manufacturer scaling: Gain
B_w
User scaling: Offset
A_w
User scaling: Gain
The equations of the straight line are enabled via register
.
Fig. 3: KL3001, KL3002 – Data flow