Commissioning and configuration
EPP6228-0022
60
Version: 1.3
6.6.6
Access to events
Some of the IO-Link sensors forward events that occur to the master. These events may be items of
information, warnings or error messages, e.g. short circuit or overheating.
The IO-Link master reports these events by setting the Device Diag bit. Further information on the events
can be read via the CoE directory or the DiagHistory tab.
Fig. 41: DiagHistory tab
The events are arranged according to type (information, warning, error), flag, occurrence of the event (time
stamp) and message (port number & event code).
The meaning of the individual messages can be taken from the vendor documentation. The IO-Link device
can be directly allocated on the basis of the port number. The events occurring can be managed using the
various buttons.
•
Update History:
if the "Auto Update" field is not selected, then the current events can be displayed via
the "Update History" button
•
Auto Update:
if this field is selected, then the list of events occurring is automatically updated
•
Only new Messages:
if this field is selected, then only those messages that have not yet been
confirmed are displayed.
•
Ack. Messages:
an event that occurs is reported via the Device Diag. Confirming the message will
reset the bit to 0.
•
Export Diag History:
the events that have occurred can be exported as a "txt" file and thus archived.
•
Advanced:
this field currently (as at 3
rd
quarter 2015) has no function.