Commissioning
EL3783
129
Version: 1.1
Summary: an array variable have to be provided which is reachable via ADS. This can be a PLC variable of
a POU or a defined array variable by the system manager or alternatively the ADS server of the terminals/
boxes device is just activated. This is then detected by Scope2.
5.5
Process data
Data flow
The amplitude values are measured with 16-bit resolution and provided as oversampling packets in the
process image for cyclic transmission.
Fig. 169: Process data flow EL3783
Data processing
The data processing is done simultaneously for all channels in the EL3783 with 16-bit conversion in the
ADC.
Scaling related to the respective (constant) measuring range:
Output value presentation
Voltage
MBE = 737,2575 V
(~= 130% * 400V * Wurzel(2)) -->
22,5 mV / digit
Current
5 A range: MBE = 9,207527
(~= 130% * 5A * root(2)) -->
281µA / digit
1 A range: MBE = 1,8415054
(~= 130% * 1A * root(2)) -->
56,2µA / digit
1. Vendor calibration (0x80p0:0B [
139])
Activation: CoE 0x80p0:0B
X
1
= (X
ADC
- Offset
Vendor
) * Gain
Vendor
2. User calibration (0x80p0:0A [
139])
Activation: CoE 0x80n0:0A
X
2
= (X
1
- Offset
User
) * Gain
User
3. Limit value evaluation (0x80p0:13 [
If the value exceeds or falls below these values, which can be entered in the indices
and
, then the bits in the indices
are set accordingly
(see example below).
The entry
serves to activate the limit value monitoring.
Output limit n (2-bit):
• 0: not active