Product overview
EL28xx-xxxx
50
Version: 2.2
Index 1C33 SM input parameter
Index (hex) Name
Meaning
Data type
Flags
Default value
1C33:0
SM input parameter
Synchronization parameters for the inputs
UINT8
RO
0x20 (32
dec
)
1C33:01
Sync mode
Current synchronization mode:
• 0: Free Run
• 1: Synchronous with SM 3 event (no outputs
available)
• 2: DC - Synchronous with SYNC0 Event
• 3: DC - Synchronous with SYNC1 Event
• 34: Synchronous with SM 2 event (outputs
available)
UINT16
RW
0x0022 (34
dec
)
1C33:02
Cycle time
UINT32
RW
0x000F4240
(1000000
dec
)
1C33:03
Shift time
Time between SYNC0 event and reading of the inputs
(in ns, only DC mode)
UINT32
RO
0x00000384
(900
dec
)
1C33:04
Sync modes supported Supported synchronization modes:
• Bit 0 = 1: free run is supported
• Bit 1 = 1: synchronous with SM 2 event is
supported (outputs available)
• Bit 1 = 1: synchronous with SM 3 event is
supported (no outputs available)
• Bit 2-3 = 01: DC mode is supported
• Bit 4-5 = 01: input shift through local event
(outputs available)
• Bit 4-5 = 10: input shift with SYNC1 event (no
outputs available)
• Bit 14 = 1: dynamic times (measurement by
writing
) (for revision no.: 17 –
25)
UINT16
RO
0x8002
(32770
dec
)
1C33:05
Minimum cycle time
UINT32
RO
0x00002710
(10000
dec
)
1C33:06
Calc and copy time
Time between reading of the inputs and availability of
the inputs for the master (in ns, only DC mode)
UINT32
RO
0x00000000
(0
dec
)
1C33:07
Minimum delay time
UINT32
RO
0x00000384
(900
dec
)
1C33:08
Command
UINT16
RW
0x0000 (0
dec
)
1C33:09
Maximum Delay time
Time between SYNC1 event and reading of the inputs
(in ns, only DC mode)
UINT32
RO
0x00000384
(900
dec
)
1C33:0B
SM event missed
counter
UINT16
RO
0x0000 (0
dec
)
1C33:0C
Cycle exceeded
counter
UINT16
RO
0x0000 (0
dec
)
1C33:0D
Shift too short counter as
UINT16
RO
0x0000 (0
dec
)
1C33:20
Sync error
BOOLEAN
RO
0x00 (0
dec
)
Index F000 Modular device profile
Index (hex) Name
Meaning
Data type
Flags
Default
F000:0
Modular device profile General information for the modular device profile
UINT8
RO
0x02 (2
dec
)
F000:01
Module index distance Index spacing of the objects of the individual channels UINT16
RO
0x0010 (16
dec
)
F000:02
Maximum number of
modules
Number of channels
UINT16
RO
0x0001 (1
dec
)
Index F008 Code word
Index (hex) Name
Meaning
Data type
Flags
Default value
F008:0
Code word
function
:
The input code of the code word 0x12345678 activates
the
function:
Changes to the CoE directory are not saved if the func-
tion is active. The function is deactivated by:
1.) changing the code word or
2.) restarting the terminal.
UINT32
RW
0x00000000
(0
dec
)
Содержание EL28 Series
Страница 1: ...Documentation EL28xx xxxx Digital HD Output Terminals 2 2 2019 01 03 Version Date...
Страница 2: ......
Страница 72: ...Mounting and wiring EL28xx xxxx 72 Version 2 2 Fig 48 Other installation positions...
Страница 106: ...Commissioning EL28xx xxxx 106 Version 2 2 Fig 95 Incorrect driver settings for the Ethernet port...
Страница 117: ...Commissioning EL28xx xxxx 117 Version 2 2 Fig 114 EtherCAT terminal in the TwinCAT tree left TwinCAT 2 right TwinCAT 3...