Operation
EJ6910
94
Version: 1.7.0
4.13
Project design limits of EL6910/EJ6910
Note
Project design limits
The maximum project design size for EL6910/EJ6910 is determined by the available mem-
ory. This is managed dynamically. The values specified in the following table are therefore
only guide values and may differ from the actual values, depending on the safety project.
Process image size
max. 1486 byte per data direction
(maximum memory size 0x1E00 for 3 buffers, ie with the same size of
input and output process data, a maximum size of 1280 bytes per data
direction is possible. Only straight start addresses are possible, so fill
bytes must be taken into account)
TwinSAFE connections
212 max.
(up to 255 CRCs in total; 1 CRC is required for a TwinSAFE connection
with 1 or 2 byte safe data.)
Supported hardware for
EL6910/EJ6910 TwinSAFE
connections
EL1904 (all)
EL2904 (all)
EL2902 (all)
EL6900 (all - max. 14 byte safe data)
EL6930 (all - max. 14 byte safe data)
EL6910 (all - max. 126 byte safe data)
EJ6910 (all - max. 126 byte safe data)
KL1904 (from 2008)
KL2904 (from 2008)
KL6904 as slave (from 2008)
AX5805 (all)
AX5806 (all)
Safe data per TwinSAFE
connection
maximum 126 byte (telegram length 255 byte)
PROFIsafe telegram length
4 to 16 byte PROFIsafe telegram length (user data 0 - 12 byte)
TwinSAFE blocks
maximum 512 (ESTOP with complete input and output mapping)
TwinSAFE groups
128 max.
TwinSAFE user
40 max.
Standard PLC inputs
dynamic (memory-dependent), max. 1024 byte
Standard PLC outputs
dynamic (memory-dependent), max. 1024 byte
Note
TwinSAFE connection
Only one TwinSAFE connection between two TwinSAFE terminals is possible. For commu-
nication with a EL6900, for sample, a connection with up to 14 bytes safe user data can be
used.
4.14
Sync-Manager Configuration
Depending on the size of the TwinSAFE project on the TwinSAFE logic, it may be necessary to adjust the
sync manager configuration.
As soon as the following message appears during the saving or downloading of the project, the sync
manager configuration for the device has to be adapted.
Содержание EJ6910
Страница 1: ...Operation Manual for EJ6910 TwinSAFE Logic Module 1 7 0 2017 11 15 Version Date...
Страница 2: ......
Страница 54: ...Operation EJ6910 54 Version 1 7 0 Fig 64 The Safety Project Online View tab...
Страница 56: ...Operation EJ6910 56 Version 1 7 0 Fig 66 Group Status Online ERROR Fig 67 Group Status Online STOP...
Страница 93: ...Operation EJ6910 93 Version 1 7 0 Fig 138 Activate saving of all analog group inputs...
Страница 106: ...Appendix EJ6910 106 Version 1 7 0 5 2 Certificates...