Operation
EJ6910
92
Version: 1.7.0
The user can select the new status via the option area. In the sample below
Deactivate Temporarily
is
selected. Use the
Finish
button to close the dialog and execute the required option.
Fig. 136: Customized TwinSAFE Group
4.12
Saving the analog group inputs persistently
EL6910, EJ6910 and EK1960 support persistent saving of analog input values in an internal memory. When
the group starts up, the stored data are compared with the current data. Under the tab
Max Start Deviation,
a
corresponding deviation can be specified for each defined analog input value of the group.
Fig. 137: Specifying deviations for analog input values
In the group properties the general settings for setting substitute values and checking the analog values on
group startup can be parameterized. Setting the parameter
Verify Analog FB Inputs at Group Startup
to
TRUE activates saving of all analog group inputs.