Product description
EJ6910
11
Version: 1.7.0
3
Product description
3.1
EJ6910 - TwinSAFE logic module
The TwinSAFE logic EJ module is the link unit between the TwinSAFE input and output modules.
The EJ6910 module meets the requirements of IEC 61508:2010 SIL 3 and DIN EN ISO 13849-1:2016-06
(Cat 4, PL e).
Fig. 2: EJ6910 - TwinSAFE logic module
3.2
Intended use
WARNING
Caution - Risk of injury!
TwinSAFE EJ modules may only be used for the purposes described below!
The TwinSAFE EJ modules expand the application range of the Beckhoff EtherCAT system by functions that
enable it to be used in the field of machine safety as well. The TwinSAFE EJ modules are designed for
machine safety functions and directly associated to industrial automation tasks. It is therefore approved only
for applications with a defined fail-safe state. This safe state is the wattless state.
The TwinSAFE EJ modules are suitable for operation on an EJ distribution board.
WARNING
System limits
The TÜV-SÜD certificate applies to the TwinSAFE EJ modules, the function blocks avail-
able in it, the documentation and the engineering tool. Approved engineering tools are
TwinCAT 3.1
,
TwinSAFE Loader
and
CODESYS Safety for EtherCAT Safety Module
. Any
deviations from these procedures or tools, particularly externally generated xml files for
TwinSAFE import or externally generated automatic project creation procedures, are not
covered by the certificate.
WARNING
Power supply
An SELV/PELV power supply unit with a voltage limit of U
max
= 36 V
DC
on the output side
must be used to supply power for the TwinSAFE EJ modules with 24 V
DC
. Failure to ob-
serve this can result in a loss of safety.
Содержание EJ6910
Страница 1: ...Operation Manual for EJ6910 TwinSAFE Logic Module 1 7 0 2017 11 15 Version Date...
Страница 2: ......
Страница 54: ...Operation EJ6910 54 Version 1 7 0 Fig 64 The Safety Project Online View tab...
Страница 56: ...Operation EJ6910 56 Version 1 7 0 Fig 66 Group Status Online ERROR Fig 67 Group Status Online STOP...
Страница 93: ...Operation EJ6910 93 Version 1 7 0 Fig 138 Activate saving of all analog group inputs...
Страница 106: ...Appendix EJ6910 106 Version 1 7 0 5 2 Certificates...