Commissioning
EJ3255
45
Version: 1.1
Index 1C33 SM input parameter
Index
(hex)
Name
Meaning
Data type
Flags Default
1C33:0
SM input parameter
Synchronization parameters for the inputs
UINT8
RO
0x20 (32
dec
)
1C33:01
Sync mode
Current synchronization mode:
• 0: Free Run
• 1: Synchron with SM 3 Event (no outputs
available)
• 2: DC - Synchron with SYNC0 Event
• 3: DC - Synchron with SYNC1 Event
• 34: Synchron with SM 2 Event (outputs available)
UINT16
RW
0x0001 (1
dec
)
1C33:02
Cycle time
Cycle time (in ns):
• Free Run: Cycle time of the local timer
• Synchron with SM 2 Event: Master cycle time
• DC mode: SYNC0/SYNC1 Cycle Time
UINT32
RW
0x00030D40
(200000
dec
)
1C33:03
Shift time
Time between SYNC0 event and reading of the inputs (in
ns, DC mode only)
UINT32
RW
0x0002E630
(19000
dec
)
1C33:04
Sync modes supported
Supported synchronization modes:
• Bit 0: free run is supported
• Bit 1: Synchron with SM 2 Event is supported
(outputs available)
• Bit 1: Synchron with SM 3 Event is supported (no
outputs available)
• Bit 2-3 = 01: DC mode is supported
• Bit 4-5 = 01: Input Shift through local event
(outputs available)
• Bit 4-5 = 10: Input Shift with SYNC1 Event (no
outputs available)
• Bit 14 = 1: dynamic times (measurement through
writing of 0x1C33:08)
UINT16
RO
0x400B (16359
dec
)
1C33:05
Minimum cycle time
Minimum cycle time (in ns)
UINT32
RO
0x00030D40
(200000
dec
)
1C33:06
Calc and copy time
Time between reading of the inputs and availability of the
inputs for the master (in ns, DC mode only)
UINT32
RO
0x00002710
(10000
dec
)
1C33:07
Minimum delay time
Minimum time between Sync-1 Event and reading of the
inputs (in ns, DC mode only)
UINT32
RO
0x00000000 (0
dec
)
1C33:08
Command
• 0: Measurement of the local cycle time is stopped
• 1: Measurement of the local cycle time is started
The entries 0x1C33:03, 0x1C33:06, 0x1C33:09 are up-
dated with the maximum measured values.
For a subsequent measurement the measured values
are reset
UINT16
RW
0x0000 (0
dec
)
1C33:09
Maximum Delay time
Time between SYNC1 event and reading of the inputs (in
ns, DC mode only)
UINT32
RO
0x00000000 (0
dec
)
1C33:0B
SM event missed
counter
Number of missed SM events in OPERATIONAL (DC
mode only)
UINT16
RO
0x0000 (0
dec
)
1C33:0C
Cycle exceeded counter Number of occasions the cycle time was exceeded in
OPERATIONAL (cycle was not completed in time or the
next cycle began too early)
UINT16
RO
0x0000 (0
dec
)
1C33:0D
Shift too short counter
Number of occasions that the interval between SYNC0
and SYNC1 event was too short (DC mode only)
UINT16
RO
0x0000 (0
dec
)
1C33:20
Sync error
The synchronization was not correct in the last cycle
(outputs were output too late; DC mode only)
BOOLEAN
RO
0x00 (0
dec
)
Содержание EJ3255
Страница 2: ......