1-second UPS (persistent data)
CX51x0
71
Version: 1.9
If the persistent or retain variables are not loaded, e.g. because they are invalid, the backup file is loaded by
default. In that case bit 1 of the bootDataFlags (for the RETAIN variables) in the PLC and/or bit 5 (for the
PERSISTENT variables) is set.
A registry setting can be used to determine whether the backup file is deleted or used. The backup file is
used by default (setting 0). If the backup file is to be deleted, the value of "ClearInvalidRetainData" or
"ClearInvalidPersistentData" must be set to 1 in the registry under:
[HKEY_LOCAL_MACHINE\SOFTWARE\Beckhoff\TwinCAT\Plc]
"ClearInvalidRetainData"=dword:00000000
"ClearInvalidPersistentData"=dword:00000000
the value of "ClearInvalidRetainData" or of "ClearInvalidPersistentData" must be set to 1.
Whether the backup file is to be used can also be set in the TwinCAT System Manager in the tree structure
on the left under
PLC > PLC Settings
:
The backup files are deleted if the option
Clear Invalid Retain Data
or
Clear Invalid Persistent Data
is set
in the System Manager. Corresponds to registry entry 1.
Development environment
Target platform
PLC libraries to be linked
TwinCAT v2.7.0
PC or CX (x86)
PLCSystem.Lib
TwinCAT v2.8.0
PC or CX (x86)
TcSystem.Lib
TwinCAT v2.10.0 Build >= 1301
CX (ARM)
TcSystem.Lib