Mounting
4.4 Connecting Power Supply
The external wiring consists of the connection of the power supply, the battery pack (optional) and the
connection of customized components for shutting down the PC.
4.4.1 Cable Cross Sections
For the connection of the power supply, wiring with a cable-cross-section of 1.0 mm
2
must be used.
With bigger distances between voltage source and PC, you take the voltage drop as a function of the
cable-cross-section as well as voltage fluctuations of your distribution voltage into account, so that is
secured that the voltage doesn't fall under 22 V at the power supply.
Connecting with bigger distances between voltage source and PC
Note
To avoid voltage drop, the battery pack and the power supply each can be connected by
using a second cable.
Insert fuse
Attention
The power supply must be protected with maximum 10 A.
4.4.2 Check voltage rating and connect
Fitted with the 24 V
DC
power supply unit:
1. Check that the external power supply is providing the correct voltage.
2. Insert the power supply cable that you have assembled into the Industrial PC's power supply
socket. Then connect it to your external 24 V power supply.
Use same type of rechargeable battery
Attention
If a 24 V UPS is installed, the same type of rechargeable battery must be used.
4.4.3 Configuration for shutting down the PC
The connections for shutting down the Industrial PCs are established via the
PC_ON
input and the
Power
Status
output.
4.4.4 PC_ON and Power Status functions
•
If the
PC_ON
input is connected to 24 V via a switch, the PC shuts down according to the rules.
The PC_ON signal is inverted, i.e. the PC shuts down if the 24 V connection is live.
•
If the
PC_ON
input is
NOT
connected by the user, the PC can be booted in the familiar way by
connecting the supply voltage and shut down via the battery by switching off the supply voltage.
Service life of the rechargeable battery
Attention
This procedure significantly reduces the service life of the rechargeable battery and
should therefore not be used.
•
Once the PC has shut down, the
Power Status
output is switched from 24 V to 0 V. Via this
output a signal lamp can be connected or a contactor for de-energizing the whole system. The
maximum load for the
Power Status
output is 0.5 A and a suitable fuse should be provided.
22