Mounting 

 

 

4.4  Connecting Power Supply 

The external wiring consists of the connection of the power supply, the battery pack (optional) and the 
connection of customized components for shutting down the PC. 

4.4.1  Cable Cross Sections 

For the connection of the power supply, wiring  with a cable-cross-section of 1.0 mm

 must be used. 

With bigger distances between voltage source and PC, you take the voltage drop as a function of the 
cable-cross-section as well as voltage fluctuations of your distribution voltage into account, so that is 
secured that the voltage doesn't fall under 22 V at the power supply. 

Connecting with bigger distances between voltage source and PC 

 

Note 

To avoid voltage drop, the battery pack and the power supply each can be connected by 
using a second cable. 

 

Insert fuse 

 

Attention 

The power supply must be protected with maximum 10 A. 

 

4.4.2  Check voltage rating and connect 

Fitted with the 24 V

DC

 power supply unit: 

1.  Check that the external power supply is providing the correct voltage. 

2.  Insert the power supply cable that you have assembled into the Industrial PC's power supply 

socket. Then connect it to your external 24 V power supply. 

Use same type of rechargeable battery 

 

Attention 

If a 24 V UPS is installed, the same type of rechargeable battery must be used. 

 

4.4.3  Configuration for shutting down the PC 

The connections for shutting down the Industrial PCs are established via the 

PC_ON

 input and the 

Power 

Status

 output. 

4.4.4  PC_ON and Power Status functions 

• 

If the 

PC_ON

 input is connected to 24 V via a switch, the PC shuts down according to the rules. 

The PC_ON signal is inverted, i.e. the PC shuts down if the 24 V connection is live. 

• 

If the 

PC_ON

 input is 

NOT

 connected by the user, the PC can be booted in the familiar way by 

connecting the supply voltage and shut down via the battery by switching off the supply voltage. 

Service life of the rechargeable battery 

 

Attention 

This procedure significantly reduces the service life of the rechargeable battery and 
should therefore not be used. 

• 

Once the PC has shut down, the 

Power Status

 output is switched from 24 V to 0 V. Via this 

output a signal lamp can be connected or a contactor for de-energizing the whole system. The 
maximum load for the 

Power Status

 output is 0.5 A and a suitable fuse should be provided. 

 

22

 

CP32xx 

Содержание CP32 Series

Страница 1: ...Installation and Operating instructions for CP32xx Multi touch Panel PC Version 1 9 Date 2019 10 09...

Страница 2: ......

Страница 3: ...duct Description 7 2 1 Product overview 7 2 2 Appropriate Use 9 2 3 Access to the connectors 9 2 4 Access to the memory device and the battery 10 2 4 1 Removing the Cover 10 2 4 2 Replacing the batter...

Страница 4: ...25 5 1 2 Shutting down and switching off 25 5 1 3 First switching on and driver installation 25 5 2 Operation 25 5 3 Servicing and maintenance 26 5 3 1 Cleaning 26 5 3 2 Maintenance 26 5 3 3 Replacin...

Страница 5: ...XTS are registered trademarks of and licensed by Beckhoff Automation GmbH Other designations used in this publication may be trademarks whose use by third parties for their own purposes could violate...

Страница 6: ...duals Risk of injury WARNING If you do not adhere the safety advise adjoining this symbol there is danger to life and health of individuals Hazard to individuals CAUTION If you do not adhere the safet...

Страница 7: ...all parts of the equipment must first be switched off after which the Panel PC is to be disconnected from the equipment Disconnect the device by unplugging the connectors on the rear side of the Panel...

Страница 8: ...t open the housing of the Panel PC Note For technical support contact Beckhoff Service 1 4 1 National regulations Depending on the type of machine and plant in which the Industrial PC is used national...

Страница 9: ...ugh the mounting arm The Industrial PC connections up to six with IP 65 connectors are positioned in the large wiring space and are easily accessible The wiring area can be opened easily without dismo...

Страница 10: ...mounting arm adapter for Rittal and Rolec mounting arm systems with 48 mm tube Passive cooling through heat sink internal fan for equal heat distribution to all the walls of the housing Wiring area f...

Страница 11: ...ned for mounting arm installation Risk of explosion Danger The Control Panel must not be used where there is a risk of explosion 2 3 Access to the connectors The connectors of the Panel PC are located...

Страница 12: ...d through the mounting arm tube before connecting them in the connection area The installation of the cover takes place in reverse order 2 4 Access to the memory device and the battery The slots for t...

Страница 13: ...e pulled out Here changing the lithium battery is also possible The installation takes place in reverse order 2 4 2 Replacing the battery Danger of Explosion WARNING Replace battery only with the iden...

Страница 14: ...accords to the IP65 standard Wiring when using 8 core cables Pin Wire Function Pin Wire Function 1 1 7 6 PC_ON 2 2 Battery Pack with UPS 8 7 Power Status 3 3 NC 9 NC 4 ge gn 10 NC 5 4 11 NC 6 5 24 V D...

Страница 15: ...r set according to IEC24702 white No 09 45 145 1500 The connector and special tools for the assembly are available via the company Harting http www harting de as well as different distributors 2 5 3 A...

Страница 16: ...tch cabel Network cable with IP65 connector C9900 K281 Network cable for CP32xx or CP72xx length 3 m assembled Harting push pull Ethernet connector IP65 second end RJ 45 IP20 C9900 K282 Network cable...

Страница 17: ...ture condensation does not form on or inside the device Prior to operation the unit must be allowed to slowly adjust to room temperature Should condensation occur a delay time of approximately 12 hour...

Страница 18: ...direct sunlight Avoid extreme environmental conditions Attention Extreme environmental conditions should be avoided as far as possible Protect the Panel PC from dust moisture and heat 4 1 Earthing me...

Страница 19: ...e a diameter of 48 mm with a maximum tolerance of 0 1 mm 0 8 mm The mounting arm adapter enables to tilt the Panel PC at 20 and to rotate it about 165 Anti twist protection Note The mounting arm adapt...

Страница 20: ...After feeding the connection cables of the Panel PC through the mounting arm tube the mounting arm tube will be positioned into the mounting arm adapter Insert the mounting arm tube all the way to the...

Страница 21: ...Mounting 3 Tighten the Allen locking screw using the Allen key 2 2 4 Now the screw cap is tightened carefully clockwise using the hook wrench SW 58 62 3 3 CP32xx 19...

Страница 22: ...e Industrial PC is provided with a power supply unit with integrated UPS order option you can realize an uninterruptible power supply UPS using the battery pack C9900 U330 Danger of Explosion WARNING...

Страница 23: ...es an ON OFF switch for the machine Basically the main switch remains switched on and provides the power supply for the PC during shutdown Via the PC ON input of the power supply the PC gets the comma...

Страница 24: ...assembled into the Industrial PC s power supply socket Then connect it to your external 24 V power supply Use same type of rechargeable battery Attention If a 24 V UPS is installed the same type of r...

Страница 25: ...ording to the wiring diagram the circuit of PC_ON and Power Status is symbolical Connection of the Battery Pack and UPS Output Note Connection of the Battery Pack and UPS Output only in combination wi...

Страница 26: ...the Panel PC from the power supply Connect all cables at the Panel PC and at the devices to be connected Ensure that all screw connections between connectors and sockets are tight Reconnect all devic...

Страница 27: ...5 1 3 First switching on and driver installation When you switch on the Industrial PC for the first time the pre installed operating system optional will be started In this case all the required drive...

Страница 28: ...tice correct polarity Handling of Lithium Batteries WARNING Lithium Batteries should not be recharged exposed to fire opened and they should be protected against sunlight and moisture The used battery...

Страница 29: ...vers can be installed from the driver CD provided To install the UPS driver software execute file Beckhoff_UPS_vx xx xx exe from the subdirectory of UPS from the CD provided on the Industrial PC Drive...

Страница 30: ...ff Service Panel PC boots software starts but control does not operate correctly Cause of the fault is either in the software or in parts of the plant outside the Panel PC Call the manufacturer of the...

Страница 31: ...e Panel PC please visit our homepage Here you will find the actual drawings using the link http www beckhoff de german download technical_drawings htm Notice mounting orientation Warning The assembly...

Страница 32: ...67 W UL compliance in progress Using a power supply class 2 or Fuse protection with 4 A according to UL 60950 2 chapter 2 5 table 2C Interfaces 1 x RJ 45 Ethernet 10 100 1000 Mbit Protection class IP...

Страница 33: ...H Co KG Huelshorstweg 20 33415 Verl Germany Phone 49 0 5246 963 0 Fax 49 0 5246 963 198 E mail info beckhoff de Web http www beckhoff de Beckhoff Support Support offers you comprehensive technical ass...

Страница 34: ...enerates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this eq...

Отзывы: