Mounting and wiring
BC3150
24
Version: 2.1.0
Baud rate in kbits/sec
9,6
19,2
93,75
187,5
500
1500
12000
Cable length in m
1200
1200
1200
1000
400
200
100
Stubs up to 1500 kbaud <6.6 m; at 12 Mbaud stub segments should not be used.
Bus segments
A bus segment consists of at most 32 devices. 126 devices are permitted in a PROFIBUS network.
Repeaters are required to refresh the signal in order to achieve this number. Each repeater is counted as
one device.
IP-Link is the subsidiary bus system for Fieldbus Boxes, whose topology is a ring structure. There is an IP
master in the coupler modules (IP230x-Bxxx or IP230x-Cxxx) to which up to 120 extension modules (IExxxx)
may be connected. The distance between two modules may not exceed 5 m. When planning and installing
the modules, remember that because of the ring structure the IP-Link master must be connected again to the
last module.
Installation guidelines
When assembling the modules and laying the cables, observe the technical guidelines provided by the
PROFIBUS User Organization (PROFIBUS Nutzerorganisation e.V.) for PROFIBUS DP/FMS (see
Checking the PROFIBUS wiring
A PROFIBUS cable (or a cable segment when using repeaters) can be checked with a few simple resistance
measurements. The cable should meanwhile be removed from all stations:
1. Resistance between A and B at the start of the lead: approx. 110 Ohm
2. Resistance between A and B at the end of the lead: approx. 110 Ohm
3. Resistance between A at the start and A at the end of the lead: approx. 0 Ohm
4. Resistance between B at the start and B at the end of the lead: approx. 0 Ohm
5. Resistance between screen at the start and screen at the end of the lead: approx. 0 Ohm
If these measurements are successful, the cable is okay. If, in spite of this, bus malfunctions still occur, this
is usually a result of EMC interference. Observe the installation notes from the PROFIBUS User
Organization (
Содержание BC3150
Страница 1: ...Documentation BC3150 Bus Terminal Controller for PROFIBUS DP 2 1 0 2017 07 11 Version Date...
Страница 2: ......
Страница 45: ...Parameterization and Commissioning BC3150 45 Version 2 1 0 Fig 41 Sample for entering associated bytes...
Страница 57: ...Programming BC3150 57 Version 2 1 0 Fig 55 Build...
Страница 87: ...PROFIBUS BC3150 87 Version 2 1 0 Fig 78 RS485 topology with 3 segments and 2 repeaters...