background image

17

Manual Manifold

2006230.03

6.0  Component Replacement 

Procedures

 

WARNING: IT IS ESSENTIAL THAT ONLY 

GENUINE BEACONMEDÆS SPARE PARTS ARE FITTED 

DURING MAINTENANCE.

 

CAUTION: Ensure no contaminates, oil 

or grease come into contact with any of the gas 

connection/internals.

6.1  Preparation For Component 

Replacement

 

CAUTION: For primary manifolds ensure an 

adequate backup supply is available and operating 

correctly before taking the main supply off line for 

maintenance.

5.3.7  To test the empty cylinder contact gauge close 

the duty bank cylinder valves and observe the alarm 

condition as the pressure drops.

 I

MPORTANT! Open the cylinder valves on 

the original duty bank once the test is completed.

Note - If there is no demand on the supply you can 

simulate this by opening the test valve ‘C’.

 

WARNING: If venting gas from valve ‘C’, for 

anaesthetic and oxygen manifolds ensure that the 

manifold room is well ventilated and no potential 

ignition sources are present while running this 

test.

 

WARNING: This check may effect the 

continuity of gas supply, ensure it is safe to carry 

out this test before proceeding.

5.3.8  Finally, tighten all joints, and inspect with 

suitable leak detection fluid.

5.3.9   Perform the steps in 

section 4.2 - Procedure 

to prime the control manifold

.

5.4  5 Years

Replace the pressure safety valve for a new certified 

relief valve,

 see section 6

.  Replacement of the 

regulators is also recommended at this time.

5.5  As Required

Replace tailpipes, pressure safety valve, pressure 

regulator, high-pressure isolation valve, isolation 

valves, contact gauges, non-return valve etc. as and 

when required 

(see section 6.0)

 

CAUTION: For emergency backup 

manifolds ensure the main supply is functioning 

correctly before taking off line for maintenance.

6.1.1  Close the manifold line isolation valve 

‘A’ 

(See figure 8)

.  Close all the cylinder isolation 

valves.

6.1.2  Open the sampling outlet valve ‘C’, to 

depressurise the system.

 

CAUTION: When exhausting anaesthetic 

and oxygen manifolds ensure that the manifold 

room is well ventilated and no potential ignition 

sources are present.

Note - If the cylinder contents gauges are not 

rapidly falling in pressure, stop draining the system 

and check all cylinders are correctly isolated.

6.2  Replace line non-return 

valve (P/N: 2005951)

6.2.1  Complete steps in 

section 6.1

 before 

carrying out any component replacement on the 

manifold control panel.

6.2.2  Slowly turn the swivel nut of the top 1” 

connection.  If you hear gas escaping do not fully 

unscrew the joint until the system is fully drained.

6.2.3  Fully disconnect all three joints as shown in 

figure 11

 and gently remove the unit by sliding it 

towards you.  Take care not to damage the seals.

6.2.4  Inspect the existing seals and replace if 

required, 

see figure 11

 for seal part numbers. 

 

6.2.5  Taking care not to damage the O-ring seals 

replace the new non-return valve as shown in 

figure 11

, and fasten the 3 flat face joints.

6.2.6  Disconnect the test point valve from the 

original non-return manifold and fit to the new 

unit.

6.2.7  Follow steps in

 section 6.11

 to bring the 

manifold back online.

Содержание Manfiold

Страница 1: ...Operation and Maintenance Instructions Manifold Control Systems Manual Manfiold Part number 2006230 Revision 03 May 24 2019...

Страница 2: ...Telephone 44 0 1246 474242 Email gbn info beaconmedaes com Website Contacts www beaconmedaes com BeaconMed s reserves the right to make changes and improvements to update products sold previously with...

Страница 3: ...Relief Valve Inspection 10 Cylinder Connection 6 Component Replace ment Procedures 11 Line Non return Valve Replacement 12 Test Sampling Point Valve Replace ment 13 2nd Stage Regulator Replacement 14...

Страница 4: ...ance must be fully trained in specialist work of this nature Oil grease and jointing compounds must not be used Do not attempt to prove the pressure relief valve under any circumstances by altering th...

Страница 5: ...ank valves 15 Single Line contact Module Not shown 16 Double Line contact Module Not shown 17 Manifold Headers C W NRVs 18 Tailpipes Notes Item 11 is recommended for indoor installations Item 15 16 ar...

Страница 6: ...ption Part Number Exhaust Pipe Connection Kit 2006233 Termination Box For Remote Alarm 2006219 4 Bar Pressure Switch with Line Contact Monitor 1829936 4 bar Pressure Switch without Line Contact Monito...

Страница 7: ...linder headers and tail pipes See table 4 for list of standard manifold assemblies Note tailpipes are supplied separate and may vary depending on required national standards enquire for details Additi...

Страница 8: ...and N2O O2 mix Entonox CAUTION Supplied fixings are for use with solid masonry type walls only Typical panel weight is 15kg selected fasteners are suitable for supporting the typical 15 kg weight of...

Страница 9: ...stall the first pipe support to the supplied 22mm OD stub pipe Item 10 figure 1 The next support fixture should typically be installed within 2m of the first 2 1 9 The 28mm exhaust line Optional suppl...

Страница 10: ...h the kit CAUTION Supplied fixings are for use with solid masonry type walls only Typical cylinder header Including bracket is 1 5kg per side 2 3 3 For additional cylinder headers remove the 3 8 BSP b...

Страница 11: ...11 Manual Manifold 2006230 03 Note For additional cylinders beyond 6 continue to add the above for either single or double racks...

Страница 12: ...inders on medical gas manifolds or medical equipment 2 4 3 Install the cylinder chains to the header brackets using the D link where shown on figure 6 Loop the chain around the cylinder to secure in p...

Страница 13: ...overall system is operable and set to the correct distribution pipeline pressure Suitably qualified competent personnel who are familiar with this manual must only undertake commissioning of the pane...

Страница 14: ...ves on the empty bank The empty cylinders must then be replaced See section 4 5 for cylinder handling and section 4 6 for cylinder operation 4 2 4 These steps must be repeated for continuous supply 4...

Страница 15: ...nts and when most explosions will occur due to adiabatic compression of any oil or grease that may be present 4 6 1 The cylinder valve should be FULLY opened slowly anticlockwise using the appropriate...

Страница 16: ...haust connections are flat face unions complete with o ring seals for ease of removal Figure 9 Relief Valve Maintenance Image shown with optional exhaust 5 3 5 Check the line pressure regulator set po...

Страница 17: ...eplace tailpipes pressure safety valve pressure regulator high pressure isolation valve isolation valves contact gauges non return valve etc as and when required see section 6 0 CAUTION For emergency...

Страница 18: ...part numbers Table 6 2nd Stage Regulator Part Numbers Regulator Nominal Pressure Part Number 4 Bar 2005689 7 Bar 2005690 6 4 1 Complete steps in section 6 1 before carrying out any component replacem...

Страница 19: ...ct the 1 connection the 5 8 header connection and the bracket M6 flange nuts as shown in figure 14 and gently remove the unit by sliding it towards you Take care not to damage the seals 6 5 4 Remove t...

Страница 20: ...raining the pipe work as shown in figure 16 Pipe line clamps may need to be unfastened to achieve this Figure 15 2nd Stage Relief Valve Replacement 2 x 1 flat face connections O ring P N 2000152 2nd S...

Страница 21: ...le 10 for part numbers Table 10 Line Pressure Gauge Part Numbers Nominal Line Pressure Part Number 4 Bar 2005765 7 Bar 2005766 CAUTION Ensure the new gauge has the same scale as the one being replaced...

Страница 22: ...ndustrial regulators are recommended to be replaced every 5 years Although the medical standards do not specifically identify the need to replace the regulators within this time scale it is considered...

Страница 23: ...CSA 2 4 4 8 10 2000179 O Ring 17 1 I D x 1 6 CSA 2 4 4 8 11 2000152 O Ring 22 1 I D x 1 6 CSA 2 4 4 8 12 2004808 1 4 Bonded Seal 2 4 4 8 13 1824977 3 8 Bonded Seal 2 4 4 8 14 1825637 1 2 Bonded Seal...

Страница 24: ...Copco Ltd trading as Atlas Copco Medical Unit 18 Nuffield Way Abingdon Oxfordshire UK OX14 1RL Tel 44 0 1246 474242 www beaconmedaes com 0088 Atlas Copco Airpower n v Boomsesteenweg 957 2610 Wilrijk B...

Отзывы: