11. Alarms / failures / recommendation list
Table 5 - list of alarms
Important note: all alarms cause the machine to shut down. The alarm must be
reset and restarted. To reset the unit, press the “On/Off” button for 10 seconds until
the alarm sounds.
Alarm
Code
Troubleshooting
Ignition failure
A01
Maximum time 1800 sec
- empty worm drive channel
– restart the unit
- heater resistor burnt - ignition
– replace resistor
- linear motor resistor burnt
- faulty micro switch
- the burning basket has been incorrectly installed
- linear cleaning motor is blocked
- fume temperature not exceed the activation setting
No flame or lack of pellets
A02
Fume temperature below
45 °C
- Pellet reservoir is empty
Excess heat in the pellet drum
A03
110 °C
- the fan is not working
– call for assistance
- faulty thermostat - call for assistance
- machine with faulty ventilation
Excess fume temperature
A04
Over 260 ºC
- fan not working or set to a low power level
–
increase the level to maximum (if the problem
persists, call assistance)
- insufficient extraction
- excess of pellets
- faulty fume probe
Pressure switch alarm
A05
The door is open, lack of
draught or extractor fault
for 120 sec
- close the door and clear the error message on the
faulty pressure regulator
- Obstruction of the exhaust pipe or faulty extractor
Air mass probe
A06
40 Ipm delta for 3600 sec
- pipes with insufficient extraction or obstructed pipes
The door is open
A07
Door open for 120 seconds
- close the door - clear the error message
- air mass sensor damaged
Fume extractor is faulty
A08
Connection failure
- check connection
- check the smoke extractor is not blocked
Fume probe failure
A09
Connection failure
- check connection
- smoke probe damaged
Pellet resistance error
A10
Connection failure
- check connection
- resistance damaged
Worm drive error
A11
Connection failure
- check connection
- Worm motor damaged
Pellet level alarm
A15
- check connection
- put pellets in the external silo (only active in
automatic boilers)
Water pressure outside
operating range
A16
- check connection
- check pressure in the hydraulic circuit
- adjust pressure in the hydraulic circuit (working
range 0.5 to 2.9 bar)
Excess water temperature
A18
95 ºC
- check connection
- check if the pump works
- purge hydraulic circuit
- check if the heat sinks are open
Содержание CBP Matic 18
Страница 14: ...11 Mín 2 m T Inspección a Min 4 m Min 1 m Máx 3 m Máx 2 m Incl 3 5 120 mm b ...
Страница 77: ...74 13 Esquemas eléctricos de la caldera de pellets Figura 65 Esquema eléctrico de la placa electrónica ...
Страница 78: ...75 Figura 66 Esquema eléctrico de la placa eléctrica del silo externo ...
Страница 151: ...67 Figura 58 Retirar os parafusos do extractor e aspirar a zona de passagem do ar ...
Страница 158: ...74 13 Esquemas eléctricos da Caldeira a pellets Figura 65 Esquema eléctrico placa electrónica ...
Страница 159: ...75 Figura 66 Esquema eléctrico placa eléctrica do silo externo ...
Страница 160: ...76 a b Figura 67 Sensores de nivel de pellets ...
Страница 231: ...68 c b c d e f ...
Страница 240: ...77 17 Electrical diagram of the pellet run boiler Figure 67 Electrical diagram of the circuit board ...
Страница 241: ...78 Figure 68 Electrical diagram of the external silo s circuit board ...
Страница 245: ...82 ...
Страница 246: ...83 ...
Страница 247: ...84 ...
Страница 248: ......
Страница 249: ...86 BAXI Tel 34 902 89 80 00 www baxi es informacion baxi es ...