Tab.48 HP : Heat-pump Parameters = Heat pump parameters
Parameter
Description
Factory setting
EHC–05
HP000
Outside bivalent temperature above which back up are not allowed to operate
Can be set from -10 °C to 20 °C
5
HP030
Start-up time delay for back-ups in central heating mode
Can be set from 0 Min 600 Min
0
HP031
Shutdown time delay for back-ups in central heating mode
Can be set from 0 Min to 600 Min
4
HP047
Start-up time delay for back-ups corresponding to the minimum outdoor tempera
ture HP049. The dynamic time delay is activated when HP030=0
Can be set from 0 Min to 60 Min
8
HP048
Start-up time delay for back-ups corresponding to the maximum outdoor tempera
ture HP050. The dynamic time delay is activated when HP030=0
Can be set from 0 Min 60 Min
30
HP049
Minimum outdoor temperature used to set HP047.
Can be set from -30 °C to 0 °C
-10
HP050
Maximum outdoor temperature used to set HP048.
Can be set from -30 °C to 20 °C
15
HP051
Minimum outdoor temperature authorising heat pump operation.
Can be set from -20 °C to 5 °C
-20
HP108
Time delay for activating the second electrical back-up stage in central heating
mode
Can be set from 1 Min to 255 Min
4
AD
Auto detect
available
CNF
Reset factory parameters
See the data plate.
ADV
ADV advanced parameters
not available
Tab.49 NP : Network Parameters = Cascade parameters
Parameter
Description
Factory setting
SCB-10
NP005
Choice of the leading generator,.AUTO: Switching of order every 7 days
Can be set from 0 127
0
NP006
Cascading boilers by adding successively or in parallel, the boilers function
simultaneously
0 Traditional
1 parallel
0
NP007
Outdoor start temperature heating of all stages in parallel mode
Can be set from -10 °C to 20 °C
10
NP008
Duration of post operation of the cascade generator pump
Can be set from 0 Min to 30 Min
4
NP009
Switch on and switch off timing for the producer of the cascade
Can be set from 1 Min to 60 Min
4
NP010
Outdoor start temperature cooling of all stages in parallel mode
Can be set from 10 °C to 40 °C
30
NP011
Choice of Cascade Algorithm type, power or temperature
0 =Temperature
1 =Power
0
NP012
Cascade, Time to reach Temperature Septoint
Can be set from 1 to 10
1
NP013
Force Primary Pump to Stop on cascade
0 =No
1 =Yes
0
9 Settings
66
iHPI
7701563 - v02 - 22052018
Содержание AWHP 22 TR-2
Страница 98: ...For more information see Error messages page 92 11 Troubleshooting 98 iHPI 7701563 v02 22052018 ...
Страница 100: ...12 Decommissioning and disposal 100 iHPI 7701563 v02 22052018 ...
Страница 101: ...12 Decommissioning and disposal 7701563 v02 22052018 iHPI 101 ...
Страница 102: ...12 Decommissioning and disposal 102 iHPI 7701563 v02 22052018 ...
Страница 104: ...7701563 v02 22052018 7701563 001 02 ...