Parameter
Factory setting for each circuit
Description
CP240
CP241
CP242
CP243
CP244
CIRCA1: 3
CIRCB1: 3
DHW1: 3
CIRCC1: 3
CIRCAUX1: 3
Adjustment of the influence of the zone room unit
Can be set from 0 to 10
CP270
CP271
CP272
CP273
CP274
CIRCA1: 18
CIRCB1: 18
DHW1: 18
CIRCC1: 18
CIRCAUX1: 18
Mixing flow temperature setpoint cooling of the zone
Can be set from 11 °C to 23 °C
CP280
CP281
CP282
CP283
CP284
CIRCA1: 10
CIRCB1: 10
DHW1: 10
CIRCC1: 10
CIRCAUX1: 10
Cooling set point for the flow temperature on the convection fan cir
cuit
Can be set from 7 °C to 23 °C
CP340
CP341
CP342
CP343
CP344
CIRCA1: 0
CIRCB1: 0
DHW1: 0
CIRCC1: 0
CIRCAUX1: 0
Type of Reduced Night Mode, stop or maintain heating of circuit
0 =Stop heat demand
1 =Continue heat demand
CP370
CP371
CP372
CP373
CP374
CIRCA1: 10
CIRCB1: 10
DHW1: 10
CIRCC1: 10
CIRCAUX1: 10
Holiday Domestic Hot Water Temperature Setpoint of zone
Can be set from 10 °C to 40 °C
CP380
CP381
CP382
CP383
CP384
CIRCA1: 65
CIRCB1: 65
DHW1: 65
CIRCC1: 65
CIRCAUX1: 65
Antilegionellosis Domestic Hot Water Temperature Setpoint of zone
Can be set from 40 °C to 80 °C
CP390
CP391
CP392
CP393
CP394
CIRCA1: 18
CIRCB1: 18
DHW1: 18
CIRCC1: 18
CIRCAUX1: 18
Start-up time for the anti-legionella function on the DHW circuit
Can be set from 0 HoursMinutes to 143 HoursMinutes
CP400
CP401
CP402
CP403
CP404
CIRCA1: 60
CIRCB1: 60
DHW1: 60
CIRCC1: 60
CIRCAUX1: 60
Duration of the function Antilegionellosis
Can be set from 10 Min to 600 Min
CP420
CP421
CP422
CP423
CP424
CIRCA1: 6
CIRCB1: 6
DHW1: 6
CIRCC1: 6
CIRCAUX1: 6
Trip differential for DHW production
Can be set from 1 °C to 60 °C
CP430
CP431
CP432
CP433
CP434
CIRCA1: 0
CIRCB1: 0
DHW1: 0
CIRCC1: 0
CIRCAUX1: 0
Used to force DHW tank loading according to the primary
temperature
Can be set from 0 to 1
CP440
CP441
CP442
CP443
CP444
CIRCA1: 0
CIRCB1: 0
DHW1: 0
CIRCC1: 0
CIRCAUX1: 0
Prevents the cooling of the Tank at the start
Can be set from 0 to 1
CP460
CP461
CP462
CP463
CP464
CIRCA1: 0
CIRCB1: 0
DHW1: 0
CIRCC1: 0
CIRCAUX1: 0
Choice of DHW Priority 0:TOTAL 1:RELATIVE 2:NONE
0 =Total
1 =Relative
2 =None
9 Settings
60
iHPI
7701563 - v02 - 22052018
Содержание AWHP 22 TR-2
Страница 98: ...For more information see Error messages page 92 11 Troubleshooting 98 iHPI 7701563 v02 22052018 ...
Страница 100: ...12 Decommissioning and disposal 100 iHPI 7701563 v02 22052018 ...
Страница 101: ...12 Decommissioning and disposal 7701563 v02 22052018 iHPI 101 ...
Страница 102: ...12 Decommissioning and disposal 102 iHPI 7701563 v02 22052018 ...
Страница 104: ...7701563 v02 22052018 7701563 001 02 ...