Tab.43 CP : Circuits Parameters = Heating circuit parameters
Parameter
Factory setting for each circuit
Description
CP000
CP001
CP002
CP003
CP004
CIRCA1: Electrical back-up: 50
CIRCB1: Electrical back-up: 50
DHW1: Electrical back-up: 95
CIRCC1: Electrical back-up: 50
CIRCAUX1: Electrical back-up: 95
Maximum Flow Temperature setpoint zone
For circuit A: Can be set from 7 °C to 100 °C
CP020
CP021
CP022
CP023
CP024
CIRCA1: 0
CIRCB1: 0
DHW1: 0
CIRCC1: 0
CIRCAUX1: 0
Functionality of the zone
0 =Disable
1 =Direct
2 =Mixing Circuit
3 =Swimming pool
4 =High Temperature
5 =Fan Convector
6 =DHW tank
7 =Electrical DHW
8 =Time Program
9 =ProcessHeat
10 =DHW Layered
11 =DHW Internal tank
12 =DHW Commercial Tank
31 =DHW FWS EXT
CP030
CP031
CP032
CP033
CP034
CIRRA1: 12
CIRCB1: 12
DHW1: 12
CIRCC1: 12
CIRCAUX1: 12
Bandwith of mixing valve zone where modulation takes place.
Can be set from 4 °C to 16 °C
CP040
CP041
CP042
CP043
CP044
CIRCA1: 4
CIRCB1: 4
DHW1: 4
CIRCC1: 4
CIRCAUX1: 4
Pump post runtime of the zone
Can be set from 0 Min to 20 Min
CP050
CP051
CP052
CP053
CP054
CIRCA1: 4
CIRCB1: 4
DHW1: 4
CIRCC1: 4
CIRCAUX1: 4
Shift between calculated setpoint and mixing valve circuit setpoint
Can be set from 0 °C to 16 °C
CP060
CP061
CP062
CP063
CP064
CIRCA1: 6
CIRCB1: 6
DHW1: 6
CIRCC1: 6
CIRCAUX1: 6
Wished room zone temperature on holiday period
Can be set from 5 °C to 20 °C
CP070
CP071
CP072
CP073
CP074
CIRCA1: 16
CIRCB1: 16
DHW1: 16
CIRCC1: 16
CIRCAUX1: 16
Max RoomTemperature limit of the circuit in reduced mode, that
allows switching to comfort mode
Can be set from 5 °C to 30 °C
CP210
CP211
CP212
CP213
CP214
CIRCA1: 15
CIRCB1: 15
DHW1: 15
CIRCC1: 15
CIRCAUX1: 15
Comfort footpoint of the temperature of heat curve of the circuit
can be set from 16 to 90 °C
set to 15 = the curve base temperature is set automatically and is
the same as the room set point temperature
CP220
CP221
CP222
CP223
CP224
CIRCA1: 15
CIRCB1: 15
DHW1: 15
CIRCC1: 15
CIRCAUX1: 15
Reduced footpoint of the temperature of heat curve of the circuit
can be set from 6 to 90 °C
set to 15 = the curve base temperature is set automatically and is
the same as the room set point temperature
CP230
CP231
CP232
CP233
CP234
CIRCA1: 0.7
CIRCB1: 0.7
DHW1: 1.5
CIRCC1: 0.7
CIRCAUX1: 1.5
Heating curve temperature gradient of the zone
Can be set from 0 to 4
9 Settings
7701563 - v02 - 22052018
iHPI
59
Содержание AWHP 22 TR-2
Страница 98: ...For more information see Error messages page 92 11 Troubleshooting 98 iHPI 7701563 v02 22052018 ...
Страница 100: ...12 Decommissioning and disposal 100 iHPI 7701563 v02 22052018 ...
Страница 101: ...12 Decommissioning and disposal 7701563 v02 22052018 iHPI 101 ...
Страница 102: ...12 Decommissioning and disposal 102 iHPI 7701563 v02 22052018 ...
Страница 104: ...7701563 v02 22052018 7701563 001 02 ...