System loads
Diversity applied
Lighting
4A
Lighting
2.4A
Cooker
16A
Cooker
14.8A
Shower
26A
Shower
26A
Immersion
heater
11A
Immersion
heater
11A
Socket outlet
13A, 13A, 6A,
4A, 6A, 2A,
13A, (33A)
Socket outlet
30.6A
Total for circuit 84.8A
In the above example, the air source heat pump and 5kW electrical heater is 18A with diversity
calculation; the consumer unit is rated at 100A thus the total load would be under the 100A incoming fuse
rating and consumer unit rating.
Fig. 15
Page 18
5.0 Installation
5.1 Site Requirement
1. This unit can be wall-mounted using the brackets specified in the accessories section on page 5. It is
recommended that the unit is installed less than 2 metres from the ground because of service and repair
requirements. Suitable fixings should be considered relative to the wall structure and weight of the unit.
Ensure that the anti-vibration pads are fitted when wall mounting this unit.
2. In all cases, where the 5kW heater is attached to the Ambiflo
™
unit. a minimum clearance distance of
0.25m is required (Fig. 16 - dimension A) between the unit and the nearest obstacle.
NOTE: It is possible to fit the 5kW Electrical heater to the rear of this unit. The heater can be fitted within
Dimension A - no additional clearance is required. Dimension A must be a minimum 0.25m.