5.
The appliance is supplied with two fireback spacers.
Do
not fit the fireback spacers if the fire is to be installed into a
precast or clay flue block system as in section 3.2.3
. These
should extend backwards to ensure sufficient clearance from
the back of the fireplace. Remove the label and retaining
screws from the rear sides of the hotbox. Position the
fireback spacer as shown in figure 11. Secure the fireback
spacers using the screws removed previously and the two
supplied with the fire.
6.
This appliance is supplied with a flue restrictor for use
where the flue draught is excessive. The restrictor must NOT
be fitted where a precast flue or a flue liner is used. For all
other installations the restrictor should be fitted. There may
however, be certain exceptional circumstances where
fitting the restrictor causes the fire to fail the spillage
test. In such cases the restrictor will have to be
removed. After removal conduct the spillage check
again.
The restrictor is packed loose with the appliance and is
fixed with two screws (See figure 12).
Page 17
INSTALLER GUIDE
Figure 12
.
Flue restrictor
Figure 11. Fireback spacers
Figure 10. ‘U’ seals